12 Accessories

A. Gas Log/Lighter Provision

Warning! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire generates fumes.

DO NOT install unvented gas logs

Damper must be locked fully open when gas logs are installed

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

Maximum input is 100,000 BTU/hr.

Decorative gas appliance must be certified to ANSI Z21.60 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.

Must be installed in accordance with the National Fuel

Gas Code, ANSI Z223.1.

A gas log set must incorporate a gas shutoff.

Gas Log set requires the damper to be locked fully open.

A listed automatic damper system with safety interlock may be used in this fireplace with only compatible, listed gas log sets. See damper system manufacturer’s insturctions.

Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.

Seal refractory around pipe with fireplace mortar or a non-combustible sealant.

B. Wood Burning Inserts

Warning! Risk of Fire! Improper installation of wood in- serts may cause fireplace or chimney system to overheat.

If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.

Cooling air openings at the top of the chimney must not be obstructed in any manner.

Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.

Firebox

Refractory

Seal with fireplace mortar or non-combust- ible sealant

Outer shell of fireplace

Maintain air clearance to combustibles.

Combustible materials

Gas line

Repack insulation knockout

Gas line

4 in. (102 mm)

1 1/2 in. (38 mm) air space around

pipe

Combustible materials may be located at zero clearance to gas line beyond 4 in. (102 mm) from fireplace side.

Figure 12.1 Gas Line Installation

44

Heatilator • EL36/EL42 • 4044-132 • Rev AD • 7/12

Image 44
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Homeowner Reference Information Listing Label Information/LocationUser Guide Table of ContentsInstaller Guide Warranty Hearth & Home Technologies Inc Limited Lifetime WarrantyWarranty Conditions This warranty is void ifListing and Code Approvals Appliance CertificationNon-Combustible Materials Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Seasoned Wood Starting a FireGrate FirescreenGlass Doors Vented Gas Log Sets & Gas Log LightersOptional Components Clear SpaceWood Fuel Maintenance and Service Chimney Inspection/CleaningDisposal of Ashes Creosote Formation and Need for RemovalGlass Cleaning Check Firebox RefractoryInspect Grate Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemNegative Pressure Design and Installation ConsiderationsDraft Locating Fireplace & Chimney Recommended Chimney LocationsInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceOutside Model #Installation of Fireplace Things to ConsiderPosition the Fireplace Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet Install Outside Air Kit Outside Air InstallationChimney Assembly Chimney Requirements Chimney RequirementsUsing Offsets/Returns ExampleDegree SL306 SL312 SL318 SL324 SL336 SL348Install Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield Prepare Attic Insulation ShieldComplete Installation Install FlashingFollowing steps should be skipped if using a chase Cut out Hole in RoofChimney Termination Requirements Multiple Chimney LocationsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap CapTS345/TS345P Square Termination Cap Shrouds Radiation ShieldField Constructed Shrouds Open Top Shroud TR342 caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredTS345 TR342 TR342/344Finishing = 1/k x inches of thickness Hearth ExtensionMinimum MaterialRaised Hearth Extension Framing Model #Non-combustible Sealant Raised Platform Hearth Extension-Finishing Materi- alsFinishing Material Decorative FacingCombustible Mantel Clearances to Mantels or other Combustibles above Fireplace4 in mm Accessories Gas Log/Lighter ProvisionWood Burning Inserts Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsIn. HX3 Hearth Extension 13 mm Mm HX4 Hearth ExtensionBifold Glass Doors DM1036, DM1042 AK24Chimney Components Catalog #JB877 Chimney Joint Band Ceiling FirestopCB876 Chimney Joint Band ST375 Square Termination CapTS345/TS345P Square Termination Cap TCT375 Terra Cotta CapCT35 Chase Top Part number list on following Damper Kit Air HandleAt Depot Service PartsStocked EL42 Piece RodEL42 Contact Information