F. Install Attic Insulation Shield

Warning! Risk of Fire! You MUST install an attic insu- lation shield when there is any possibility of insulation or other combustible material coming into contact with the chimney.

Do NOT pack insulation between the chimney and the attic insulation shield.

Failure to keep insulation and other materials away from chimney pipe could cause fire.

Do NOT offset chimney inside insulation shield.

Installation of a ceiling firestop is required

Refer to Figures 8.6 - 8.8.

Roll the shield (around the chimney if already installed) until you have a 3 in. (76 mm) overlap and the three holes on each side match up (large holes on top).

Insert three screws into the matching holes to form a tube.

Bend three tabs on the bottom of the tube inward to 90° to maintain chimney air space (refer to Figure 8.6).

Rest the insulation shield on the ceiling firestop below.

Bend the three short tabs at the top of the shield inward to 90° to maintain the 2 in. (51 mm) air space from the chimney.

Bend the remaining top tabs to just meet the pipe.

If you wish to make a custom shield or barrier, follow these guidelines:

Metal is preferred, although any material stiff enough to hold back the insulation can be used.

Warning! Risk of Fire! Use of cardboard or other materials that can deflect under humidity or other envi- ronmental conditions is not recommended.

The shield or barrier must be tall enough to extend above the insulation and prevent blown-in insulation from spilling into the cavity.

Maintain specified air spaces around chimney.

Check instructions and local codes for further details.

 

 

 

 

Bend remaining tabs

 

 

 

 

to rest against pipe to

Bend

 

inward

prevent insulation

90°

 

from falling in.

 

 

 

 

 

Insert three

 

 

 

 

screws

3 in. (76 mm) overlap

Figure 8.6 Prepare Attic Insulation Shield

 

 

Tabs bent in to

 

Pipe

rest against pipe

 

 

 

 

Attic Insulation Shield

 

 

14-1/2 in. (368 mm)

 

6 Tabs bent

diameter

 

in 90°

Ceiling Firestop

 

 

Insulation

Pipe

Insulation

10-1/2 in.

(267 mm)

Figure 8.7 Install Attic Insulation Shield (firestop above ceiling)

 

 

Tabs bent in to

 

 

rest against pipe

 

Pipe

 

 

 

Attic Insulation Shield

 

 

14-1/2 in. (368 mm)

 

 

diameter

 

6 Tabs bent

 

 

in 90°

 

Insulation

 

Insulation

10-1/2 in.

Pipe

Ceiling Firestop

(267 mm)

 

 

Figure 8.8 Install Attic Insulation Shield (firestop below ceiling)

Heatilator • EL36/EL42 • 4044-132 • Rev AD• 7/12

29

Image 29
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Listing Label Information/Location Homeowner Reference InformationUser Guide Table of ContentsInstaller Guide Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if Warranty ConditionsAppliance Certification Listing and Code ApprovalsNon-Combustible Materials Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Starting a Fire Seasoned WoodGrate FirescreenVented Gas Log Sets & Gas Log Lighters Glass DoorsOptional Components Clear SpaceWood Fuel Chimney Inspection/Cleaning Maintenance and ServiceDisposal of Ashes Creosote Formation and Need for RemovalCheck Firebox Refractory Glass CleaningInspect Grate Frequency As desiredStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedNegative Pressure Design and Installation ConsiderationsDraft Recommended Chimney Locations Locating Fireplace & ChimneyInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesFrame the Fireplace Sidewalls/SurroundsOutside Model #Things to Consider Installation of FireplacePosition the Fireplace Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet Outside Air Installation Install Outside Air KitChimney Assembly Chimney Requirements Chimney RequirementsExample Using Offsets/ReturnsDegree SL306 SL312 SL318 SL324 SL336 SL348Assemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling FirestopsPrepare Attic Insulation Shield Install Attic Insulation ShieldInstall Flashing Complete InstallationFollowing steps should be skipped if using a chase Cut out Hole in RoofMultiple Chimney Locations Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyCap Install Termination CapTS345/TS345P Square Termination Cap Radiation Shield ShroudsField Constructed Shrouds Open Top Shroud TR342 caps require radiation shieldRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield requiredTS345 TR342 TR342/344= 1/k x inches of thickness Hearth Extension FinishingMinimum MaterialModel # Raised Hearth Extension FramingRaised Platform Hearth Extension-Finishing Materi- als Non-combustible SealantDecorative Facing Finishing MaterialClearances to Mantels or other Combustibles above Fireplace Combustible Mantel4 in mm Gas Log/Lighter Provision AccessoriesWood Burning Inserts Gas Code, Ansi Z223.1Reference Materials Fireplace DimensionsMm HX4 Hearth Extension In. HX3 Hearth Extension 13 mmBifold Glass Doors DM1036, DM1042 AK24Catalog # Chimney ComponentsCeiling Firestop JB877 Chimney Joint BandCB876 Chimney Joint Band ST375 Square Termination CapTS345/TS345P Square Termination Cap TCT375 Terra Cotta CapCT35 Chase Top Damper Kit Air Handle Part number list on followingAt Depot Service PartsStocked Piece Rod EL42EL42 Contact Information