Hearth and Home Technologies EL36, EL42 Finishing, = 1/k x inches of thickness Hearth Extension

Page 38

11 Finishing

A. Non-Combustible Materials

Materials which will not ignite and burn, composed of any combination of the following:

-

Steel

-

Iron

-

Brick

-

Tile

-

Concrete

-

Slate

-

Glass

-

Plasters

Materials reported as passing ASTM E 136, Standard

Test Method for Behavior of Metals, in a Vertical Tube Furnace at 750° C

B. Combustible Materials

Materials made of or surfaced with any of the following materials:

-

Wood

-

Compressed paper

-

Plant fibers

-

Plastic

Any material that can ignite and burn; flame proofed or not, plastered or un-plastered

Table 11.1

R = 1/k x inches of thickness

Table 11.2

C. Hearth Extension

WARNING! Risk of fire! High temperatures, sparks, embers or other burning material falling from the fireplace may ignite flooring or concealed combustible surfaces.

Protective metal hearth strips MUST be installed.

Hearth extensions MUST be installed exactly as specified.

You MUST use a hearth extension with this fireplace.

Refer to Figure 11.1 for minimum dimensions.

This fireplace has been tested and approved for use with a hearth extension insulated to a minimum R value of 1.03.

The hearth extension material MUST be covered with tile, stone or other non-combustible material.

Manufactured hearth materials will usually have a published R value (resistance to heat) or k value (conductivity of heat). Refer to the formula in Table 11.1 to convert a k value to an R value,

Refer to Table 11.2 for hearth extension insulation alternatives.

Hearth Extension Insulation Alternatives-Total minimum R Value must equal 1.03

 

 

 

Minimum

 

k per inch

r per inch

thickness

Material

thick

thick

required

Hearth & Home HX3, HX4 (Micore 300™)

0.49

2.06

1/2 in.

USG Micore 160™

0.39

2.54

1/2 in.

 

 

 

 

USG Durock™ Cement Board

1.92

0.52

2 in.

Cement Mortor

5.0

0.20

5-1/8 in.

 

 

 

 

Common Brick

5.0

0.20

5-1/8 in.

 

 

 

 

Ceramic Tile

12.50

0.08

12-1/4 in.

Armstrong™ Privacy Guard Plus

0.46

2.18

1/2 in.

 

 

 

 

Marble

14.3-20.0

0.07-0.05

14-5/8 in. - 20-3/8 in.

38

Heatilator • EL36/EL42 • 4044-132 • Rev AD • 7/12

Image 38
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Homeowner Reference Information Listing Label Information/LocationUser Guide Table of ContentsInstaller Guide Warranty Hearth & Home Technologies Inc Limited Lifetime WarrantyWarranty Conditions This warranty is void ifNon-Combustible Materials Listing and Code ApprovalsAppliance Certification Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Grate Seasoned WoodStarting a Fire FirescreenOptional Components Glass DoorsVented Gas Log Sets & Gas Log Lighters Clear SpaceWood Fuel Disposal of Ashes Maintenance and ServiceChimney Inspection/Cleaning Creosote Formation and Need for RemovalInspect Grate Glass CleaningCheck Firebox Refractory Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemNegative Pressure Design and Installation ConsiderationsDraft Locating Fireplace & Chimney Recommended Chimney LocationsInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsOutside Sidewalls/SurroundsFrame the Fireplace Model #Position the Fireplace Installation of FireplaceThings to Consider Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet Install Outside Air Kit Outside Air InstallationChimney Assembly Chimney Requirements Chimney RequirementsDegree Using Offsets/ReturnsExample SL306 SL312 SL318 SL324 SL336 SL348Install Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield Prepare Attic Insulation ShieldFollowing steps should be skipped if using a chase Complete InstallationInstall Flashing Cut out Hole in RoofChimney Termination Requirements Multiple Chimney LocationsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap CapTS345/TS345P Square Termination Cap Field Constructed Shrouds ShroudsRadiation Shield Open Top Shroud TR342 caps require radiation shieldTS345 TR342 Mailbox Style Shroud radiation shield requiredRoofed Style Shroud radiation shield required TR342/344Minimum Finishing= 1/k x inches of thickness Hearth Extension MaterialRaised Hearth Extension Framing Model #Non-combustible Sealant Raised Platform Hearth Extension-Finishing Materi- alsFinishing Material Decorative FacingCombustible Mantel Clearances to Mantels or other Combustibles above Fireplace4 in mm Wood Burning Inserts AccessoriesGas Log/Lighter Provision Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsBifold Glass Doors DM1036, DM1042 In. HX3 Hearth Extension 13 mmMm HX4 Hearth Extension AK24Chimney Components Catalog #CB876 Chimney Joint Band JB877 Chimney Joint BandCeiling Firestop ST375 Square Termination CapTS345/TS345P Square Termination Cap TCT375 Terra Cotta CapCT35 Chase Top Part number list on following Damper Kit Air HandleAt Depot Service PartsStocked EL42 Piece RodEL42 Contact Information