F. Install Attic Insulation Shield

WARNING! Risk of Fire! You MUST install an attic insu- lation shield when there is any possibility of insulation or other combustible material coming into contact with the chimney.

DO NOT pack insulation between the chimney and the attic insulation shield.

Failure to keep insulation and other materials away from chimney pipe could cause fire.

DO NOT offset chimney inside insulation shield.

Installation of a ceiling firestop is required

Refer to Figures 8.6 - 8.8.

Roll the shield (around the chimney if already installed) until you have a 3 in. (76 mm) overlap and the three holes on each side match up (large holes on top).

Insert three screws into the matching holes to form a tube.

Bend three tabs on the bottom of the tube inward to 90° to maintain chimney air space (refer to Figure 8.6).

Rest the insulation shield on the ceiling firestop below.

Bend the three short tabs at the top of the shield inward to 90° to maintain the 2 in. (51 mm) air space from the chimney.

Bend the remaining top tabs to just meet the pipe.

If you wish to make a custom shield or barrier, follow these guidelines:

Metal is preferred, although any material stiff enough to hold back the insulation can be used.

WARNING! Risk of Fire! Use of cardboard or other materials that can deflect under humidity or other envi- ronmental conditions is not recommended.

The shield or barrier must be tall enough to extend above the insulation and prevent blown-in insulation from spilling into the cavity.

Maintain specified air spaces around chimney.

Check instructions and local codes for further details.

 

 

 

 

Bend remaining tabs

 

 

 

 

to rest against pipe to

Bend

 

inward

prevent insulation

90°

 

from falling in.

 

 

 

 

 

Insert three

 

 

 

 

screws

3 in. (76 mm) overlap

Figure 8.6 Prepare Attic Insulation Shield

 

 

Tabs bent in to

 

Pipe

rest against pipe

 

 

 

 

Attic Insulation Shield

 

 

17 in. (432 mm)

 

6 Tabs bent

diameter

 

in 90°

Ceiling Firestop

 

 

Insulation

Pipe

Insulation

13 in.

(330 mm)

Figure 8.7 Install Attic Insulation Shield (firestop above ceiling)

 

 

Tabs bent in to

 

 

rest against pipe

 

Pipe

 

 

 

Attic Insulation Shield

 

 

17 in. (432 mm)

 

 

diameter

 

6 Tabs bent

 

 

in 90°

 

Insulation

 

Insulation

13 in.

Pipe

Ceiling Firestop

(330 mm)

 

 

Figure 8.8 Install Attic Insulation Shield (firestop below ceiling)

Heat & Glo • EXCLAIM-36, EXCLAIM-424013-251 Rev C • 11/08

31

Image 31
Contents Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Grate Listing Label Information/LocationNumber Installer Guide Table of ContentsUser Guide CONDITIONS, Exclusions & Limitation of Liability Warranty Hearth & Home Technologies Limited WarrantyHeat & Glo EXCLAIM-36, EXCLAIM-42 4013-251 Rev C 11/08 Combustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Firescreen Seasoned WoodStarting a Fire GrateClear Space Glass DoorsVented Gas Log Sets & Gas Log Lighters Optional ComponentsWood Fuel Creosote Formation and Need for Removal Maintainance and ServiceChimney Inspection/Cleaning Disposal of AshesFrequency As desired Glass CleaningCheck Firebox Refractory Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedDraft Design and Installation ConsiderationsNegative Pressure Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesFrame the Fireplace Sidewalls/SurroundsUnpack the Fireplace EXCLAIM-36 only Installation of FireplaceUnpack the Fireplace EXCLAIM-42 only Things to ConsiderRemoving Smoke Shield Position the Fireplace EXCLAIM-42 onlyGAS Knockout Install the Refractory EXCLAIM-42 onlyLevel Fireplace Place Protective Metal Hearth StripsYES Install Outside Air KitChimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsAssemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling Firestops330 mm Install Attic Insulation ShieldCut out Hole in Roof Complete InstallationInstall Flashing Following steps should be skipped if using a chaseFlat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyST1175/ST475 Square Termination Cap Install Termination CapTCT1175 Terra Cotta Cap Open Top Shroud TR11/TR11T caps require radiation shield ShroudsRadiation Shield Field Constructed ShroudsRoofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield requiredHearth Extension Finishing= 1/k x inches of thickness Hearth Extension Construction Raised Hearth Extension FramingFlush Hearth Extension Framing Non-combustible SealantNoncombustible Facing Finishing MaterialCombustible Mantel 19 3/4 502 mm Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsReference Materials Fireplace DimensionsEXCLAIM-36 EXCLAIM-42 Catalog # Chimney Components15-1/4 387 mm 15-3/4 400 mm CT56 Chase Top LDS33/LDS46 Decorative Shroud EXCLAIM-36H, EXCLAIM-36T Service PartsEXCLAIM-42H, EXCLAIM-42T This page intentionally left blank Do not Discard this Manual