E. Locating Fireplace & Chimney

Location of the fireplace and chimney will affect perfor- mance.

Install within the warm airspace enclosed by the building envelope. This helps to produce more draft, especially during lighting and die-down of the fire.

Penetrate the highest part of the roof. This minimizes the effects of wind loading.

Locate termination cap away from trees, adjacent structures, uneven roof lines and other obstructions.

Minimize the use of chimney offsets.

Consider the fireplace location relative to floor and ceiling and attic joists.

Take into consideration the termination requirements in Section 8 and Section 9.

NOTICE: Locating the fireplace in a basement or in a location of considerable air movement can cause intermittent smoke spillage from fireplace. Do not locate fireplace near

frequently open doors

central heat outlets or returns

 

 

 

Recommended Location:

 

 

 

 

Recommended Location:

• Above peak

 

 

 

 

 

• Above peak

• Inside heated space

 

 

 

 

 

Marginal Location:

Marginal Location:

 

 

 

Wind loading possible

 

 

 

• Below peak

 

 

 

Location NOT recommended:

 

 

 

 

 

Not the highest point of the roof

 

 

 

 

 

Wind loading possible

 

 

 

 

 

 

 

 

 

 

Location NOT recommended:

 

 

 

 

 

Too close to tree

 

 

Recommended:

 

 

Below adjacent structure

 

 

• Insulated exterior chase

 

Lower roof line

 

 

in cooler climates

 

Avoid outside wall

 

Windward

 

 

 

 

 

 

 

 

 

 

 

Leeward

 

 

 

Multi-level Roofs

 

 

 

Figure 5.2 Recommended Chimney Locations

 

 

 

 

16

Heat & Glo • EXCLAIM-36, EXCLAIM-424013-251 Rev C • 11/08

 

Image 16
Contents Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Grate Listing Label Information/LocationNumber Installer Guide Table of ContentsUser Guide Warranty Hearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeat & Glo EXCLAIM-36, EXCLAIM-42 4013-251 Rev C 11/08 Listing and Code Approvals Appliance CertificationNon-Combustible Materials Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Seasoned Wood Starting a FireGrate FirescreenGlass Doors Vented Gas Log Sets & Gas Log LightersOptional Components Clear SpaceWood Fuel Maintainance and Service Chimney Inspection/CleaningDisposal of Ashes Creosote Formation and Need for RemovalGlass Cleaning Check Firebox RefractoryInspect Grate Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemDraft Design and Installation ConsiderationsNegative Pressure Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceInstallation of Fireplace Unpack the Fireplace EXCLAIM-42 onlyThings to Consider Unpack the Fireplace EXCLAIM-36 onlyPosition the Fireplace EXCLAIM-42 only Removing Smoke ShieldInstall the Refractory EXCLAIM-42 only GAS KnockoutPlace Protective Metal Hearth Strips Level FireplaceInstall Outside Air Kit YESChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield 330 mmComplete Installation Install FlashingFollowing steps should be skipped if using a chase Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST1175/ST475 Square Termination CapTCT1175 Terra Cotta Cap Shrouds Radiation ShieldField Constructed Shrouds Open Top Shroud TR11/TR11T caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredHearth Extension Finishing= 1/k x inches of thickness Raised Hearth Extension Framing Hearth Extension ConstructionNon-combustible Sealant Flush Hearth Extension FramingFinishing Material Noncombustible FacingCombustible Mantel 19 3/4 502 mm Accessories Gas Log/Lighter ProvisionWood Burning Inserts Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsEXCLAIM-36 EXCLAIM-42 Chimney Components Catalog #15-1/4 387 mm 15-3/4 400 mm CT56 Chase Top LDS33/LDS46 Decorative Shroud Service Parts EXCLAIM-36H, EXCLAIM-36TEXCLAIM-42H, EXCLAIM-42T This page intentionally left blank Do not Discard this Manual