Hearth and Home Technologies EXCLAIM-36 Finishing, Hearth Extension, = 1/k x inches of thickness

Page 40

11 Finishing

A. Non-Combustible Materials

Materials which will not ignite and burn, composed of any combination of the following:

-

Steel

-

Iron

-

Brick

-

Tile

-

Concrete

-

Slate

-

Glass

-

Plasters

Materials reported as passing ASTM E 136, Standard

Test Method for Behavior of Metals, in a Vertical Tube Furnace at 750° C

B. Combustible Materials

Materials made of or surfaced with any of the following materials:

-

Wood

-

Compressed paper

-

Plant fibers

-

Plastic

Any material that can ignite and burn; flame proofed or not, plastered or un-plastered

C. Hearth Extension

WARNING! Risk of fire! High temperatures, sparks, embers or other burning material falling from the fireplace may ignite flooring or concealed combustible surfaces.

Protective metal hearth strips MUST be installed.

Hearth extensions MUST be installed exactly as specified.

Table 11.1

R = 1/k x inches of thickness

Table 11.2

You MUST use a hearth extension with this fireplace.

This fireplace has been tested and approved for use with a hearth extension insulated to a minimum R value of 1.03.

The hearth extension material MUST be covered with tile, stone or other non-combustible material.

Manufactured hearth materials will usually have a published R value (resistance to heat) or k value (conductivity of heat). Refer to the formula in Table 11.1 to convert a k value to an R value,

Refer to Table 11.2 for hearth extension insulation alternatives.

 

A

C

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAT. #

 

 

A

B

 

C

HX4

 

in

66

20

 

12

 

 

 

 

 

 

 

 

 

mm

1676

508

 

305

Figure 11.1 Hearth Extension Dimensions

Hearth Extension Insulation Alternatives-Total minimum R Value must equal 1.03

 

 

 

Minimum

 

k per inch

r per inch

thickness

Material

thick

thick

required

Hearth & Home HX3, HX4 (Micore 300™)

0.49

2.06

1/2 in.

 

 

 

 

USG Micore 160™

0.39

2.54

1/2 in.

USG Durock™ Cement Board

1.92

0.52

2 in.

Cement Mortor

5.0

0.20

5-1/8 in.

 

 

 

 

Common Brick

5.0

0.20

5-1/8 in.

Ceramic Tile

12.50

0.08

12-1/4 in.

 

 

 

 

Armstrong™ Privacy Guard Plus

0.46

2.18

1/2 in.

Marble

14.3-20.0

0.07-0.05

14-5/8 in. - 20-3/8 in.

40

Heat & Glo • EXCLAIM-36, EXCLAIM-424013-251 Rev C • 11/08

Image 40
Contents Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Grate Listing Label Information/LocationNumber Installer Guide Table of ContentsUser Guide Warranty Hearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeat & Glo EXCLAIM-36, EXCLAIM-42 4013-251 Rev C 11/08 Listing and Code Approvals Appliance CertificationNon-Combustible Materials Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Seasoned Wood Starting a FireGrate FirescreenGlass Doors Vented Gas Log Sets & Gas Log LightersOptional Components Clear SpaceWood Fuel Maintainance and Service Chimney Inspection/CleaningDisposal of Ashes Creosote Formation and Need for RemovalGlass Cleaning Check Firebox RefractoryInspect Grate Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemDraft Design and Installation ConsiderationsNegative Pressure Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceInstallation of Fireplace Unpack the Fireplace EXCLAIM-42 onlyThings to Consider Unpack the Fireplace EXCLAIM-36 onlyPosition the Fireplace EXCLAIM-42 only Removing Smoke ShieldInstall the Refractory EXCLAIM-42 only GAS KnockoutPlace Protective Metal Hearth Strips Level FireplaceInstall Outside Air Kit YESChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield 330 mmComplete Installation Install FlashingFollowing steps should be skipped if using a chase Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST1175/ST475 Square Termination CapTCT1175 Terra Cotta Cap Shrouds Radiation ShieldField Constructed Shrouds Open Top Shroud TR11/TR11T caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredHearth Extension Finishing= 1/k x inches of thickness Raised Hearth Extension Framing Hearth Extension ConstructionNon-combustible Sealant Flush Hearth Extension FramingFinishing Material Noncombustible FacingCombustible Mantel 19 3/4 502 mm Accessories Gas Log/Lighter ProvisionWood Burning Inserts Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsEXCLAIM-36 EXCLAIM-42 Chimney Components Catalog #15-1/4 387 mm 15-3/4 400 mm CT56 Chase Top LDS33/LDS46 Decorative Shroud Service Parts EXCLAIM-36H, EXCLAIM-36TEXCLAIM-42H, EXCLAIM-42T This page intentionally left blank Do not Discard this Manual