R
5100-I WOOD INSERT
CLEARANCES TO COMBUSTIBLES
United States and Canada
|
| Mantel |
|
SideWall | B | Fascia or Trim | |
| C |
| |
|
|
| |
| A | Insert | D |
|
| ||
|
|
| |
| F | E |
|
Hearth Extension
In Canada a full length 6” (152mm) S635 flue liner required as per ULC S628.
NOTE: When installling into a masonry fireplace, the fire- place must be built to UBC Chapter 37 standards. Do not remove brick or mortar from masonry fireplace to accomo- date insert. The permanent metal warning plate provided must be attached to the back of the fireplace stating the fire- place may have been altered to accomodate the insert and must be returned to original condition for use as a conven- tional fireplace.
| A | B | C | D | E | F |
|
| INSTALLATION: Masonry, Heat Circulating and *Zero Clearance |
|
|
| |||
| 12" (305) | 40" (1016) | 35" (889) | 7" (178) | 16" (406) | 8"(200) |
|
|
|
|
|
| 18" (457) Canada |
|
|
|
|
|
|
|
| ||
| With 5" Mantel Deflector, Part No. |
|
|
|
| ||
|
|
|
|
|
|
|
|
| 12" (305) | 29" (737) | 20" (889) | 7" (178) | 16" (406) | 8"(200) |
|
|
|
|
|
| 18" (457) Canada |
|
|
|
|
|
|
|
| ||
| With 8" Mantel Deflector, Part No. |
|
|
|
| ||
|
|
|
|
|
|
|
|
| 12" (305) | 23" (585) | 16" (406) | 7" (178) | 16" (406) | 8"(200) |
|
|
|
|
|
| 18" (457) Canada |
|
|
*Zero Clearance in USA Only.
THERMAL PROTECTION USA & CANADA
Thermal protection must be 1 inch (25mm) minimum thickness (“k” value = 0.84) or equivalent material. See Alternate Floor Protection Work Sheet on page 7.
SERIAL NUMBER LABEL LOCATION:
ON RIGHT SIDE OF INSERT AS YOU FACE THE APPLIANCE
January 30, 2004 | Page 5 |