R
5100-I WOOD INSERT
OPERATING TIPS
For maximum operating efficiency with the lowest emissions, follow these operating procedures:
1.Regardless of desired heat output, when loading stove, burn your
2.Regulate burn rate (heat output) by using the Primary Control (under ashcather). The
3.Heat output settings: Follow burn rate instructions listed below.
4.Burn only dry,
BTU / Hr |
| Primary Control |
Below 10,000 | Closed after 5 to 15 minutes | Pull to Stop |
10,000 - 15,000 | Closed after 5 to 15 minutes | 3/4” - 1” open |
15,000 - 30,000 | Closed after 5 to 15 minutes | 1” - |
Maximum Heat | Closed after 5 to 15 minutes | Fully open |
|
|
|
These are approximate settings, and will vary with type of wood or chimney draft.
WARNING: Do not operate with
BURN RATES
STARTING FIRE: Open both controls (push in) completely. After a wood load has been burning on high for 5 to 15 minutes or longer for very large pieces, close the
HIGH: Leave the Primary Air Control fully open (under ashcatcher). It is especially important to fully open both controls when reloading the insert as failure to do so could result in excessive emissions, also referred to as ‘opacity’.
After a wood load has been burning on high for 5 to 15 minutes on High to achieve the following burn rates set the controls as listed below:
MEDIUM HIGH: Close the Primary Air Control to 1” to
MEDIUM: Close the Primary Air Control to 3/4” to 1” (19mm to 25mm) open.
LOW: Gradually close down the Primary Air Control by pulling out making sure to maintain flames in the insert.
OPACITY
Opacity is the measure of how clean your insert is burning and is measured in percentages. An opacity of 100% in the smoke column from a chimney will totally obscure an object. Whereas 0% opacity means that no smoke column can be seen. A periodic check of the opacity emitted from your chimney will enable you to burn your insert as smoke free as possible.
FAN OPERATING INSTRUCTIONS
1.Initial (cold) startup: Leave fan off until your insert is hot and a good coal bed is established, approximately 30 minutes after fuel is lit.
2.High Burn Setting: The fan may be left on throughout the burn.
3.Medium or Medium High Burn Setting: The fan should be left off until a good burn is established, then turned on a medium
or high rate.
4.Low Burn Setting: The fan tends to cool the insert. Leave fan off until the burn is well established; then, if you wish, turn the fan on at a low rate.
5.The fan is equipped with a rheostat (speed control). The highest fan speed is obtained by turning the rheostat on, then adjusting back towards “OFF” as far as possible without turning the fan off. For a low fan speed, turn the control knob clockwise as far as possible.
ASH REMOVAL
Remove cold ashes (not hot) from the insert at regular intervals, depending on your usage. Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a
Page 18 | January 30, 2004 |