R
5100-I WOOD INSERT
INSTALLATION OPTIONS
Refer to: Clearances to Combustibles on page 5, Canadian Installation requirements on page 12,
Hearth Requirements on page 5 and Zero Clearance Adjustable Support Kit on page 16.
MASONRY FIREPLACE
USING DIRECT-CONNECT METHOD
The
1.Secure the fireplace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper.
2.Seal either the damper area around the chimney liner with a high temperature sealant or the fireplace front with fiberglass batting.
3.The chimney should be examined for cracks, loose mortar, and other signs of deterioration and blockage. The insert should not be installed until it is determined that the chim- ney is safe for use. Since an oversized flue contributes to the accumulation of creosote, the size of the flue should be checked to determine that it is not too large for the insert. The chimney should also be checked to ensure it meets the minimum standard of the National Fire Protection Associa- tion (NFPA) Standard 211. The following bullets list the more critical requirements for a properly constructed chimney:
•The masonry wall of the chimney, if brick or modular block, must be a minimum of 4 inches (102mm) nominal thickness. A chimney of rubble stone must be at least 12 inches (305mm) thick
•The chimney must have a fire clay flue liner (or equiva- lent) with a minimum thickness of 5/8” (16mm) and must be installed with refractory mortar. An equivalent liner must be a listed chimney liner system or other approved material.
•A chimney inside the house must have at least 2 inches (51mm) of clearance to the combustible structure. A chim- ney outside the house must have at least 1 inch (25mm) clearance to the combustible structure.
Masonry Chimney
Flue Tile
Mantel | Full Listed |
Liner Option | |
Direct Connect | |
| Seal Option |
Damper Area | Minimum Starter |
|
Pipe Option
SEAL DAMPER AREA OR FACE SEAL
Figure 10A - Installation Into Masonry Fireplace
METAL HEAT CIRCULATING MASONRY
The
Mantel |
Listed Liner |
SEAL DAMPER AREA OR FACE SEAL
NOTE: In Canada, a full reline is required.
Figure 10B - Installation Into Metal Heat Circulating
Showing Use Of Starter Pipe
Page 10 | January 30, 2004 |