LG Electronics LF300CP(LP-C303R20), LF480CE(LP-C483TA0) Operation Details, Cooling Mode Operation

Page 17

Operation Details

1. Time Delay Safety Control

3min

The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.

 

(Protection of compressor)

3sec

The indoor fan is ceased for 3 seconds to prevent relay noise.

 

(Protection of fan relay and micro chip)

30sec The 4-way valve is ceased for 30 sec. to prevent the refrigerant-gas abnormal noise when the Heating operation is OFF or switched to the other operation mode.

2. Airflow Direction Control

This function is to swing the louver left and right automatically and to set it at the desired position.

The procedure is as the following.

1st : Press the ON/OFF Button to operate the product.

2nd : Press the Airflow Direction Control Button to swing the louver left and right automatically. (Remote controller)

3rd : Repress the Airflow Direction Control Button to set the louver as the desired position. (Remote controller)

3. Cooling Mode Operation

When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the controller and the operation diagram is as following.

Intake Air temp.

Setting Temp. +1°C(1.8°F)

 

 

 

 

 

(Compressor ON)

 

 

 

 

 

Setting Temp. -1°C(1.8°F)

 

 

 

 

 

(Compressor OFF)

 

More than

 

More than

 

 

 

 

 

 

 

3 minutes

 

3 minutes

 

Indoor Fan Speed

Selecting

Selecting

Selecting

Selecting

Selecting

fan speed

fan speed

fan speed

fan speed

fan speed

 

Compressor

ON

OFF

ON

OFF

ON

4. Off Timer Function

This function is to set the time of stopping the unit operation.

The procedure is as the following.

1st: Press the timer set button on the Remocon.

2nd: The buzzer sounds and then the display window shows the Off-Time to be set as

....

-The Off-Time is shifted as the following by each press.

-If you select ' ', the Off-Timer function will be cancelled.

-During Off-Timer Operation, if you repress the timer set button, the rest time will be displayed.

–17–

Image 17
Contents Model LF300CPLP-C303R20 LF480CELP-C483TA0 Floor Standing Type Air ConditionerContents Installation Safety PrecautionsDo not install the product on a Do not install, remove, or reDefective installation stand OperationalBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units Keep level even when installing the productUse two or more people to lift and transport the product Indoor Unit FunctionsTimer Control Remote ControlFan Operation Airflow Direction ControlOutdoor Fan Speed Control Outdoor UnitDeice Control Capacity Product SpecificationsOutdoor Unit LPUC303R20 LF300CP DimensionsIndoor Unit LPNC303R20 LF300CP Outdoor Unit Indoor UnitDoor Unit LPUC483TA0 LF480CE Indoor Unit LPNC483TA0 LF480CEItems Air Outlet Vent Air Inlet Vent Control display Outdoor Wiring DiagramLF480CELP-C483TA0 Outdoor Cooling Mode Operation Time Delay Safety ControlOff Timer Function Operation DetailsHeating Mode Operation Defrost Control Hot-Start ControlProtection of the evaporator pipe from frosting Soft Dry Operation ModeAir Purifying OperationAP-Z286RC0, AP-Z286R20, AP-Z488TC0 Child Lock functionEnergy Saving Alarm mode display / only displayed while operatingFunction for test operation Operation or CancelOutline of Operation FunctionCooling Only Model Installation of Indoor, Outdoor UnitSelection of the best location Refrigerant amount Indoor Unit installationOutdoor unit Installation Test running Connection of power supplyEvaluation of the performance Operate the unit for fifteen minutes or moreHand Over Failures to Start Troubleshooting GuideOnly blowers do not work No cooling and heating operation performedOnly compressor does not work Only outdoor fan does not workUnits discontinue after the operation started Both blower and compressor are working Unit is working, but not cooling and heating sufficientlyTrouble checking by protection devices Fault Cause Check/Correcitve ActionCause for frequent stop and start operation No cooling operation performed Electronic Parts Troubleshooting GuideIndoor fan does not operate Airflow Direction does not operate Remote control does not operate Unit does not operate Timer control does not operate. Replacement MicomNo heating operation works No heater operation works Model LF300CPLP-C303R20 Exploded View and Replacement Parts ListW1WE Model LF480CELP-C483TA0 W0CZZ 435512 559010 546810 554030 Model LF480CELP-C483TA0 December No A20156T