LG Electronics LF300CP(LP-C303R20), LF480CE(LP-C483TA0) service manual

Page 30

The Units discontinue after the operation started

 

 

 

 

 

 

 

WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

 

 

 

 

 

 

 

 

 

 

 

 

 

Other parts than the unit

Improper opening of the

Checking

Open it properly

 

 

service valves in the

 

 

 

 

 

refrigerant line

 

 

 

 

 

 

 

 

 

Outdoor coil

Coil is dirty *1

Checking

Wash it by means of

 

 

 

 

something like chemical

 

 

 

 

washing.

 

 

 

 

 

 

In-condensable gas

Air intruded into the

In the event that

Extract air by vacuum

 

blended.

refrigerant pipe line *1

difference between the

pump, then recharge the

 

 

 

saturating temperature

refrigerant.

 

 

 

corresponding to high

 

 

 

 

 

pressure and the

 

 

 

 

 

temperature of air

 

 

 

 

 

discharged from the

 

 

 

 

 

outdoor coil is more than

 

 

 

 

 

15°C, incondensable gas

 

 

 

 

 

may be blended.

 

 

 

 

 

 

 

 

High pressure switch

Improper adjustment

Check it with a pressure

Readjust it to normal

 

 

 

gauge.

operating pressure.

 

 

 

 

(Note)

 

 

 

 

Don't alternate the

 

 

 

 

specified adjusting

 

 

 

 

pressure. If the adjusted

 

 

 

 

pressure exceeds the

 

 

 

 

specified range, it will

 

 

 

 

cause a great accident.

 

 

 

 

 

 

Refrigerant

A shortage of refrigerant

 

Recharge the

 

 

amount. * 2

 

refrigerant. Repair the

 

 

 

 

spot where it leaks.

 

 

 

 

 

 

Outdoor Fan

Reverse rotation of fan

Confirm the wind blowing

If reversed, connect

 

 

Obstacle

out.

interchanged wires to

 

 

Air short circuit *1

Check it with eyes.

each terminal.

 

 

 

Power wirings.

 

 

 

 

 

 

 

 

 

 

Note: Use an appropriate measuring instrument for readjustment. *1: Check the High-pressure switch indication.

*2: Check the Low- pressure switch indication.

–30–

Image 30
Contents Floor Standing Type Air Conditioner Model LF300CPLP-C303R20 LF480CELP-C483TA0Contents Safety Precautions InstallationDefective installation stand Do not install, remove, or reDo not install the product on a OperationalBe cautious that water could not enter the product Keep level even when installing the product Use two or more people to lift and transport the productDo not step on or put anyting on the product. outdoor units Functions Indoor UnitFan Operation Remote ControlTimer Control Airflow Direction ControlOutdoor Unit Deice ControlOutdoor Fan Speed Control Product Specifications CapacityDimensions Indoor Unit LPNC303R20 LF300CPOutdoor Unit LPUC303R20 LF300CP Indoor Unit Outdoor UnitIndoor Unit LPNC483TA0 LF480CE Door Unit LPUC483TA0 LF480CEItems Air Outlet Vent Air Inlet Vent Control display Wiring Diagram OutdoorLF480CELP-C483TA0 Outdoor Off Timer Function Time Delay Safety ControlCooling Mode Operation Operation DetailsHeating Mode Operation Hot-Start Control Defrost ControlAir Purifying OperationAP-Z286RC0, AP-Z286R20, AP-Z488TC0 Soft Dry Operation ModeProtection of the evaporator pipe from frosting Child Lock functionAlarm mode display / only displayed while operating Energy SavingOutline of Operation Operation or CancelFunction for test operation FunctionInstallation of Indoor, Outdoor Unit Selection of the best locationCooling Only Model Indoor Unit installation Outdoor unit InstallationRefrigerant amount Evaluation of the performance Connection of power supplyTest running Operate the unit for fifteen minutes or moreHand Over Troubleshooting Guide Failures to StartNo cooling and heating operation performed Only blowers do not workOnly outdoor fan does not work Only compressor does not workUnits discontinue after the operation started Unit is working, but not cooling and heating sufficiently Both blower and compressor are workingFault Cause Check/Correcitve Action Trouble checking by protection devicesCause for frequent stop and start operation Electronic Parts Troubleshooting Guide No cooling operation performedIndoor fan does not operate Airflow Direction does not operate Remote control does not operate Timer control does not operate. Replacement Micom Unit does not operateNo heating operation works No heater operation works Exploded View and Replacement Parts List Model LF300CPLP-C303R20W1WE Model LF480CELP-C483TA0 W0CZZ 435512 559010 546810 554030 Model LF480CELP-C483TA0 December No A20156T