The Units discontinue after the operation started
|
|
|
|
|
|
| WHAT TROUBLED | COMPLAINTS | HOW TO CHECK | REMEDY |
|
|
|
|
|
|
|
|
|
|
|
| |
| Other parts than the unit | Improper opening of the | Checking | Open it properly | |
|
| service valves in the |
|
|
|
|
| refrigerant line |
|
|
|
|
|
|
|
| |
| Outdoor coil | Coil is dirty *1 | Checking | Wash it by means of | |
|
|
|
| something like chemical | |
|
|
|
| washing. | |
|
|
|
|
| |
| Air intruded into the | In the event that | Extract air by vacuum | ||
| blended. | refrigerant pipe line *1 | difference between the | pump, then recharge the | |
|
|
| saturating temperature | refrigerant. | |
|
|
| corresponding to high |
|
|
|
|
| pressure and the |
|
|
|
|
| temperature of air |
|
|
|
|
| discharged from the |
|
|
|
|
| outdoor coil is more than |
|
|
|
|
| 15°C, incondensable gas |
|
|
|
|
| may be blended. |
|
|
|
|
|
|
| |
| High pressure switch | Improper adjustment | Check it with a pressure | Readjust it to normal | |
|
|
| gauge. | operating pressure. | |
|
|
|
| (Note) | |
|
|
|
| Don't alternate the | |
|
|
|
| specified adjusting | |
|
|
|
| pressure. If the adjusted | |
|
|
|
| pressure exceeds the | |
|
|
|
| specified range, it will | |
|
|
|
| cause a great accident. | |
|
|
|
|
| |
| Refrigerant | A shortage of refrigerant |
| Recharge the | |
|
| amount. * 2 |
| refrigerant. Repair the | |
|
|
|
| spot where it leaks. | |
|
|
|
|
| |
| Outdoor Fan | Reverse rotation of fan | Confirm the wind blowing | If reversed, connect | |
|
| Obstacle | out. | interchanged wires to | |
|
| Air short circuit *1 | Check it with eyes. | each terminal. | |
|
|
| Power wirings. | ||
|
|
|
| ||
|
|
|
|
|
|
Note: Use an appropriate measuring instrument for readjustment. *1: Check the
*2: Check the Low- pressure switch indication.