12. Alarm mode display / only displayed while operating.

CO : The sensor for sensing room temperature is open or short.

C1 : The sensor for sensing piping temperature is open or short.

13.Energy Saving

If setting temperature of starting energy saving operation is under 22°C(71.6°F), first, setting temperature it up to 22°C(71.6°F) and perform energy saving operation.

After energy saving operation starts, if adaptation time of the human body pass from the point which room temperature and setting temperature meet together, increase setting temperature 1°C(1.8°F) more.

If it doesn't satisfy number even in 50 minutes from the start of energy saving operation, increase 1°C(1.8°F).

After increasing setting temperature 1°C(1.8°F) more by number , , perform number , again, if setting temperature goes up to 25°C(77.0°F), maintain this temperature.

If setting temperature goes down to under 25°C(77.0°F), during the operation, do number , , again.

27°C(80.6°F)

 

 

 

 

 

26°C(78.8°F)

 

 

 

 

 

25˚C(77.0°F)

 

 

 

 

 

24°C(75.2°F)

 

 

 

 

 

23°C(73.4°F)

 

 

 

 

 

22°C(71.6°F)

 

 

 

 

 

21°C(69.8°F)

 

 

 

 

 

28min.

35min.

47min.

 

50min.

50min.

50min.

 

Setting energy

Setting temp.

Setting temp.

Setting temp.

maintains setting temp.

saving operation

23°C(73.4°F)

24°C(75.2°F)

25°C(77.0°F)

25°C(77.0°F)

14. AUTO RESTART

In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.

15. Function of changing set temperature when re-operation after stop.

Operation is set the following condition when re-operation with start/stop button.

1.Operation mode.

Cooling/soft dry mode Cooling mode Heating mode Heating mode

2.Setting the set temperature when cooling operation.

Room temperature > Set temperature: to be set to the previous set temperature. Room temperature Set temperature

a)Room temperature 26°C(78.8°F): to be set to 24°C(75.2°F)

b)22°C(71.6°F) Room temperature 25°C(77.0°F): to be set to 21°C(69.8°F)

c)19°C(66.2°F) Room temperature 21°C(69.8°F): to be set to -1°C(1.8°F) less than room temperature.

d)Room temperature 18°C(64.4°F): to be set to 18°C(64.4°F)

–21–

Image 21
Contents Model LF300CPLP-C303R20 LF480CELP-C483TA0 Floor Standing Type Air ConditionerContents Installation Safety PrecautionsDo not install the product on a Do not install, remove, or reDefective installation stand OperationalBe cautious that water could not enter the product Keep level even when installing the product Use two or more people to lift and transport the productDo not step on or put anyting on the product. outdoor units Indoor Unit FunctionsTimer Control Remote ControlFan Operation Airflow Direction ControlOutdoor Unit Deice ControlOutdoor Fan Speed Control Capacity Product SpecificationsDimensions Indoor Unit LPNC303R20 LF300CPOutdoor Unit LPUC303R20 LF300CP Outdoor Unit Indoor UnitDoor Unit LPUC483TA0 LF480CE Indoor Unit LPNC483TA0 LF480CEItems Air Outlet Vent Air Inlet Vent Control display Outdoor Wiring DiagramLF480CELP-C483TA0 Outdoor Cooling Mode Operation Time Delay Safety ControlOff Timer Function Operation DetailsHeating Mode Operation Defrost Control Hot-Start ControlProtection of the evaporator pipe from frosting Soft Dry Operation ModeAir Purifying OperationAP-Z286RC0, AP-Z286R20, AP-Z488TC0 Child Lock functionEnergy Saving Alarm mode display / only displayed while operatingFunction for test operation Operation or CancelOutline of Operation FunctionInstallation of Indoor, Outdoor Unit Selection of the best locationCooling Only Model Indoor Unit installation Outdoor unit InstallationRefrigerant amount Test running Connection of power supplyEvaluation of the performance Operate the unit for fifteen minutes or moreHand Over Failures to Start Troubleshooting GuideOnly blowers do not work No cooling and heating operation performedOnly compressor does not work Only outdoor fan does not workUnits discontinue after the operation started Both blower and compressor are working Unit is working, but not cooling and heating sufficientlyTrouble checking by protection devices Fault Cause Check/Correcitve ActionCause for frequent stop and start operation No cooling operation performed Electronic Parts Troubleshooting GuideIndoor fan does not operate Airflow Direction does not operate Remote control does not operate Unit does not operate Timer control does not operate. Replacement MicomNo heating operation works No heater operation works Model LF300CPLP-C303R20 Exploded View and Replacement Parts ListW1WE Model LF480CELP-C483TA0 W0CZZ 435512 559010 546810 554030 Model LF480CELP-C483TA0 December No A20156T