Fault

Cause

Check/Correcitve Action

 

 

 

 

Discharge pressure is lower than standard.

See "Low Discharge Pressure".

 

 

 

 

Single or three phases running.

Check the power supply line and the

 

 

contactor.

 

 

 

 

High or low voltage or phase unbalance.

Check the voltage and phase unbalance.

 

 

 

Internal

Refrigerant short charge or leakage.

Add refrigerant, repair leakage, if any.

Thermostat

 

 

Cut-Off

 

 

Compressor frequently stops and starts.

Check thermistor operation, or any other

 

 

 

cause for frequent stop and start operation.

 

 

 

 

Discharge and suction pressure are

See "High Discharge Pressure" or "High

 

extremely high.

Suction Pressure".

 

 

 

Overcurrent

High or low voltage, or phase unbalance.

Check the voltage and phase unbalance.

 

 

Relay for

Single or three phases running

Check the power supply line and the

Compressor

 

contact.

Cut-Off

 

 

 

Faulty compressor motor.

Check electric resistance among the

 

 

 

compressor terminals, and from the

 

 

terminals to ground.

 

 

 

 

Loose connections.

Check the electric connections.

 

 

 

 

Compressor frequently stops and starts.

Check the operation of the thermistor, or

 

 

any other cause for frequent stop.

 

 

 

Overcurrent

High or low voltage, or phase unbalance.

Check the voltage and electric wiring.

 

 

Relay for

Single or three phases running.

Check the power supply line and the

Fan Motor

 

contactor.

Cut-Off

 

 

Faulty fan motor.

Check the fan motor and wiring.

 

 

 

 

 

Loose connection.

Check the elelctric connections.

 

 

 

 

Faulty fan bearing.

Check repair or replace the bearing.

 

 

 

 

Loose connections.

Check the electric connections.

Fuse Blown

 

 

Single or three phase running.

Check the power supply line.

 

 

 

 

 

Faulty motor.

Check electric resistance among motor

 

 

housing, and from the terminals to

 

 

ground.

 

 

 

Disconnection

Disconnection.

1. Check the wires and connect where

and Faulty

 

necessary.

 

2. Check the contact holding coil.

Contact

 

 

 

 

 

 

 

Faulty contact.

Check the contact in the magnetic

 

 

contact, the over-current relay, the

 

 

pressure control switch, the operation

 

 

switch, the auxiliary relay.

 

 

 

–33–

Image 33
Contents Model LF300CPLP-C303R20 LF480CELP-C483TA0 Floor Standing Type Air ConditionerContents Installation Safety PrecautionsDo not install the product on a Do not install, remove, or reDefective installation stand OperationalBe cautious that water could not enter the product Keep level even when installing the product Use two or more people to lift and transport the productDo not step on or put anyting on the product. outdoor units Indoor Unit FunctionsTimer Control Remote ControlFan Operation Airflow Direction ControlOutdoor Unit Deice ControlOutdoor Fan Speed Control Capacity Product SpecificationsDimensions Indoor Unit LPNC303R20 LF300CPOutdoor Unit LPUC303R20 LF300CP Outdoor Unit Indoor UnitDoor Unit LPUC483TA0 LF480CE Indoor Unit LPNC483TA0 LF480CEItems Air Outlet Vent Air Inlet Vent Control display Outdoor Wiring DiagramLF480CELP-C483TA0 Outdoor Cooling Mode Operation Time Delay Safety ControlOff Timer Function Operation DetailsHeating Mode Operation Defrost Control Hot-Start ControlProtection of the evaporator pipe from frosting Soft Dry Operation ModeAir Purifying OperationAP-Z286RC0, AP-Z286R20, AP-Z488TC0 Child Lock functionEnergy Saving Alarm mode display / only displayed while operatingFunction for test operation Operation or CancelOutline of Operation FunctionInstallation of Indoor, Outdoor Unit Selection of the best locationCooling Only Model Indoor Unit installation Outdoor unit InstallationRefrigerant amount Test running Connection of power supplyEvaluation of the performance Operate the unit for fifteen minutes or moreHand Over Failures to Start Troubleshooting GuideOnly blowers do not work No cooling and heating operation performedOnly compressor does not work Only outdoor fan does not workUnits discontinue after the operation started Both blower and compressor are working Unit is working, but not cooling and heating sufficientlyTrouble checking by protection devices Fault Cause Check/Correcitve ActionCause for frequent stop and start operation No cooling operation performed Electronic Parts Troubleshooting GuideIndoor fan does not operate Airflow Direction does not operate Remote control does not operate Unit does not operate Timer control does not operate. Replacement MicomNo heating operation works No heater operation works Model LF300CPLP-C303R20 Exploded View and Replacement Parts ListW1WE Model LF480CELP-C483TA0 W0CZZ 435512 559010 546810 554030 Model LF480CELP-C483TA0 December No A20156T