| WHAT TROUBLED |
| COMPLAINTS |
| HOW TO CHECK |
| REMEDY | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Electric troubles | Defective contact. | Checking | Repair and clean or | |||||||
| (Magnetic |
|
| Defective contact point. |
|
|
|
|
| replace it. |
|
| contactor) |
|
| Rusting and faults in the iron |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| core contact face. Defective |
|
|
|
|
|
|
|
|
|
|
| contact of the |
|
|
|
|
|
|
|
|
|
|
| operating switch. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
| Others |
| Improper installation |
|
|
|
|
|
| ||
|
|
|
|
|
| Correct it. | |||||
|
|
| Checking | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Trouble checking by protection devices |
|
|
|
|
|
|
| Fault |
|
|
| Cause |
|
| Check/Correcitve Action | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| High Discharge |
|
|
|
| Condenser cooling air extremely hot or |
|
| 1. Check the operation of the outdoor motor. | ||||||
|
|
|
|
|
|
|
| insufficient air flow through the condenser |
|
| 2. Check discharge and suction, air |
| |||
|
|
|
|
|
|
|
| circulation. |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Inside of the condenser tube is clogged. |
|
| Clean condenser coil. | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| Purge air from the cycle. | ||||
|
|
|
|
|
|
|
| Air in the refrigeration cooling cycle. | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Suction pressure is higher than standard. |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| See "High Suction Pressure". | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| 1. Check unit operation input | |||
| Low |
|
|
|
|
| Faulty discharge valves or suction valves of | ||||||||
| Discharge |
|
|
|
|
| the compressor. |
|
| 2. Check the suction pressure. | |||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Refrigerant | |||||||
|
|
|
|
|
|
|
|
|
| Add refrigerant: repair leakage if any. | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Suction pressure is lower than standard. |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| See "Low Suction Pressure". | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| 1. Check fresh air, intake or check for | |||
|
|
|
|
|
| Intake air extemely hot or excessive air flow | |||||||||
| High | ||||||||||||||
| Suction |
|
|
| through the evaporator coil. |
|
|
| leakage of the return air. | ||||||
| Pressure |
|
|
|
|
|
|
|
|
| 2. Check air flow quantity. | ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Refrigerant |
|
| Purge the refrigerant. | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Faulty discharge valve or suction valve of |
|
| Check the operating input. | ||||
|
|
|
|
|
|
|
| the compressor. |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| Discharge pressure is higher than standard |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| See "High discharge Pressure". | ||||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Intake air extremely cold or insufficient air |
|
| 1. Check air flow quantity. | ||||
| Low | ||||||||||||||
| Suction |
|
|
| flow through the evaporator coil. |
|
| 2. Check air filter. |
| ||||||
| Pressure |
|
|
|
|
|
|
| 3. Check evaporator coil frosting |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Add refrigerant, repair leakage, if any. | |||
|
|
|
|
|
|
|
| Refrigerant | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| Restricted liquid in the suction line. |
| Check the capillary tube and the strainer. | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|