PACKAGE AIR CONDITIONER VOLTAGE LIMITS

NAME PLATE RATING

MINIMUM

MAXIMUM

 

 

 

380 V

342 V

418 V

 

 

 

220 V

198 V

242 V

 

 

 

380 - 415 V

342 V

456 V

 

 

 

No cooling and heating operation performed

 

 

 

 

 

 

 

WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

 

 

 

 

 

 

 

 

 

 

 

 

Other parts than the unit

Electric supply interrupted

Measure it with a tester in

Repair a switch box and

 

 

Defective power wiring Cut

case that the same

 

 

of power fuse

power source is supplied

is relative instrument.

 

 

 

to other equipment than

Replacement of fuse

 

 

 

the unit, what and where

Request a power

 

 

 

trouble can be discovered

 

 

 

supplier to repair.

 

 

 

by checking the operation

 

 

 

 

 

 

 

 

of other equipment.

 

 

 

 

 

 

 

 

 

Too low voltage

Measure it with a tester.

Check the power source.

 

 

 

 

Use a thick cable if

 

 

 

 

necessary.

 

 

 

 

Magnetic switch for

Control point is on

Make short-circuit, then

Replace it if necessary.

compressor & fan motor

condition of "OFF" due to

measure it with a tester.

 

 

 

 

trouble.

 

 

 

 

 

 

 

Operating switch

Troubled or defective

Check it with the eyes or

Repair or replace it.

 

 

contactor

tester.

 

 

 

 

 

 

Protection devices

Opened the contact point

Check it with the eyes or

Discover the trouble

 

 

with trouble

tester.

cause and push the rest

 

 

 

 

button.

 

 

 

 

 

 

2) Only blowers do not work

 

 

 

 

 

 

 

WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

 

 

 

 

 

 

 

 

 

 

 

 

 

Air volume change over

Troubled or defective

Check it with the eyes or a

Repair or replace it.

 

switch

contact point

tester

 

 

 

 

 

 

 

 

Capacitor

Defected

Check it with a tester.

Replace it.

 

 

 

 

 

 

–28–

Image 28
Contents Floor Standing Type Air Conditioner Model LF300CPLP-C303R20 LF480CELP-C483TA0Contents Safety Precautions InstallationDo not install, remove, or re Do not install the product on aDefective installation stand OperationalBe cautious that water could not enter the product Use two or more people to lift and transport the product Keep level even when installing the productDo not step on or put anyting on the product. outdoor units Functions Indoor UnitRemote Control Timer ControlFan Operation Airflow Direction ControlDeice Control Outdoor UnitOutdoor Fan Speed Control Product Specifications CapacityIndoor Unit LPNC303R20 LF300CP DimensionsOutdoor Unit LPUC303R20 LF300CP Indoor Unit Outdoor UnitIndoor Unit LPNC483TA0 LF480CE Door Unit LPUC483TA0 LF480CEItems Air Outlet Vent Air Inlet Vent Control display Wiring Diagram OutdoorLF480CELP-C483TA0 Outdoor Time Delay Safety Control Cooling Mode OperationOff Timer Function Operation DetailsHeating Mode Operation Hot-Start Control Defrost ControlSoft Dry Operation Mode Protection of the evaporator pipe from frostingAir Purifying OperationAP-Z286RC0, AP-Z286R20, AP-Z488TC0 Child Lock functionAlarm mode display / only displayed while operating Energy SavingOperation or Cancel Function for test operationOutline of Operation FunctionSelection of the best location Installation of Indoor, Outdoor UnitCooling Only Model Outdoor unit Installation Indoor Unit installationRefrigerant amount Connection of power supply Test runningEvaluation of the performance Operate the unit for fifteen minutes or moreHand Over Troubleshooting Guide Failures to StartNo cooling and heating operation performed Only blowers do not workOnly outdoor fan does not work Only compressor does not workUnits discontinue after the operation started Unit is working, but not cooling and heating sufficiently Both blower and compressor are workingFault Cause Check/Correcitve Action Trouble checking by protection devicesCause for frequent stop and start operation Electronic Parts Troubleshooting Guide No cooling operation performedIndoor fan does not operate Airflow Direction does not operate Remote control does not operate Timer control does not operate. Replacement Micom Unit does not operateNo heating operation works No heater operation works Exploded View and Replacement Parts List Model LF300CPLP-C303R20W1WE Model LF480CELP-C483TA0 W0CZZ 435512 559010 546810 554030 Model LF480CELP-C483TA0 December No A20156T