Installation of Indoor, Outdoor Unit
1. Selection of the best location
1)Indoor unit
•There should not be any heat source or steam near the unit.
•There should not be any obstacles to prevent the air circulation.
•A place where air circulation in the room will be good.
•A place where drainage can be easily obtained.
•A place where noise prevention is taken into consideration.
•Do not install the unit near the door way.
•Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
2)Outdoor unit
•If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
•There should not be any animals or plants which could be affected by discharged hot air.
•Ensure the space indicated by arrows from the wall, ceiling, fence, or other obstacles.
|
| 50mm(2inch) |
400mm |
| 400mm |
(16inch) |
| (16inch) |
| 1000mm(39.4inch) | Indoor unit |
|
| |
500mm(20inch) |
| (20inch) |
| 500mm | |
|
| |
. |
| 500mm(20inch) |
|
|
3) Piping length and the elevation
Cooling Only Model
MODEL | PIPE SIZE | Max. | Max. | |
|
| Length | Elevation | |
(BTU/h) | GAS SIDE | LIQUID SIDE | A (m/ft) | B (m/ft) |
| ||||
|
|
|
|
|
48k | 3/4" | 3/8" | 40/131 | 25/82 |
|
|
|
|
|
30k | 5/8" | 3/8" | 30/98 | 20/66 |
|
|
|
|
|
Indoor unit
B
A
Outdoor unit