CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1)Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2)Provide a circuit breaker switch between power source and the unit.
3)The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to
4)Specification of power source
5)Confirm that electrical capacity is sufficient.
6)Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7)Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8)Never fail to equip a leakage breaker where it is wet or moist.
9)The following troubles would be caused by voltage
•Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
•Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).
If Error Code happens in the display of indoor.
| Error Code | Error Contents |
| Checking Point | ||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
Indoor Air Sensor Open or Short | ||||||||||
| C0 |
| ||||||||
|
|
|
| 1.Check Sensor Connection to PCB whether it's | ||||||
|
|
|
|
|
| connected well or not. |
|
| ||
|
|
|
|
| ||||||
|
|
|
|
|
| 2.Replace it with new Sensor. |
|
| ||
| C1 | Indoor Pipe Sensor Open or Short |
| |||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
Outdoor Air Sensor Open or Short |
|
|
|
|
| |||||
| C3 |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
| C4 | Outdoor Pipe Sensor Open or Short |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |||
| C5 | Communication failure between |
| |||||||
|
|
|
| 1.Check connecting cable wiring order between | ||||||
|
|
| Indoor and outdoor unit. |
|
| Indoor and outdoor diagram. |
| |||
|
|
|
|
|
| 2.Check all wire connector whether it is connected |
| |||
|
|
|
|
|
| or not. |
| |||
|
|
|
|
| ||||||
|
|
|
|
|
| 3.Indoor AC PCB defects.(short inside). |
| |||
|
|
|
|
|
| 4.Outdoor PCB defects.(short inside) |
| |||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|