5. Heating Mode Operation

The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Intake Air Temp.

Setting Temp. +1°C(1.8°F)

(Compressor OFF)

Setting Temp.

 

 

 

 

 

 

 

A

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Compressor ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting Temp. -1°C(1.8°F)

 

 

minimum

minimum

minimum

 

 

 

 

 

 

 

 

 

Hot

 

 

 

 

 

 

 

 

 

 

 

 

minimum

 

10sec.

10sec.

10sec.

 

Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Fan Speed OFF

 

Selecting

 

LOW

 

 

 

OFF

 

Selecting

LOW

OFF

 

fan speed

 

 

 

 

 

fan speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

ON

 

 

OFF

 

 

ON

OFF

 

A point: The indoor pipe temperature to be less then 35°C(95.0°F) & Discharge air Temperature to be less than 29°C(84.2°F). The indoor fan operates for minimum 10sec. even if falls lower than 34°C(93.2°F).

During heating operation, the operating procedure of the indoor fan is as the following.

Stop(VI)

Low(V)

Selecting Fan Speed(IV)

39°C(102.2°F)

 

Discharge Air Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

34°C(93.2°F)

 

 

 

 

 

 

 

 

 

 

 

28°C(82.4°F)

 

 

 

 

(Hot-Start Release Point)

 

 

 

Indoor Pipe Temp.

 

 

 

 

 

 

 

 

 

 

26°C(78.8°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Start

 

 

 

 

 

 

 

 

 

Stop(I)

 

 

Low(II)

 

Selecting Fan Speed(III)

 

 

 

(Hot-Start Operating)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step

Indoor fan speed

 

Pipe temp.

 

Air discharge temp.

 

 

 

 

 

 

 

 

 

 

Off

 

 

 

28 C(82.4°F)(Hot start operating)

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

28

C(82.4°F)

 

< 39°C(102.2°F)

 

 

 

 

 

 

 

 

Selecting speed

 

28

C(82.4°F)

 

39°C(102.2°F)

 

 

 

 

 

 

 

 

Selecting speed

 

28

C(82.4°F)

 

> 34°C(93.2°F)

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

26

C(78.8°F)

 

34°C(93.2°F)

 

 

 

 

 

 

 

 

 

 

 

Off

 

 

 

26

C(78.8°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

–18–

Image 18
Contents Floor Standing Type Air Conditioner Model LF300CPLP-C303R20 LF480CELP-C483TA0Contents Safety Precautions InstallationDefective installation stand Do not install, remove, or reDo not install the product on a OperationalBe cautious that water could not enter the product Keep level even when installing the product Use two or more people to lift and transport the productDo not step on or put anyting on the product. outdoor units Functions Indoor UnitFan Operation Remote ControlTimer Control Airflow Direction ControlOutdoor Unit Deice ControlOutdoor Fan Speed Control Product Specifications CapacityDimensions Indoor Unit LPNC303R20 LF300CPOutdoor Unit LPUC303R20 LF300CP Indoor Unit Outdoor UnitIndoor Unit LPNC483TA0 LF480CE Door Unit LPUC483TA0 LF480CEItems Air Outlet Vent Air Inlet Vent Control display Wiring Diagram OutdoorLF480CELP-C483TA0 Outdoor Off Timer Function Time Delay Safety ControlCooling Mode Operation Operation DetailsHeating Mode Operation Hot-Start Control Defrost ControlAir Purifying OperationAP-Z286RC0, AP-Z286R20, AP-Z488TC0 Soft Dry Operation ModeProtection of the evaporator pipe from frosting Child Lock functionAlarm mode display / only displayed while operating Energy SavingOutline of Operation Operation or CancelFunction for test operation FunctionInstallation of Indoor, Outdoor Unit Selection of the best locationCooling Only Model Indoor Unit installation Outdoor unit InstallationRefrigerant amount Evaluation of the performance Connection of power supplyTest running Operate the unit for fifteen minutes or moreHand Over Troubleshooting Guide Failures to StartNo cooling and heating operation performed Only blowers do not workOnly outdoor fan does not work Only compressor does not workUnits discontinue after the operation started Unit is working, but not cooling and heating sufficiently Both blower and compressor are workingFault Cause Check/Correcitve Action Trouble checking by protection devicesCause for frequent stop and start operation Electronic Parts Troubleshooting Guide No cooling operation performedIndoor fan does not operate Airflow Direction does not operate Remote control does not operate Timer control does not operate. Replacement Micom Unit does not operateNo heating operation works No heater operation works Exploded View and Replacement Parts List Model LF300CPLP-C303R20W1WE Model LF480CELP-C483TA0 W0CZZ 435512 559010 546810 554030 Model LF480CELP-C483TA0 December No A20156T