LG Electronics 3828A20025U manual Piping length and the elevation

Page 8

 

 

 

 

 

Installation of Unit

 

 

 

 

 

 

3. Piping length and the elevation

 

 

 

 

 

 

 

 

MODEL

PIPE SIZE

Max.

Max.

 

 

 

Length

Elevation

(BTU/h)

GAS SIDE

 

LIQUID SIDE

 

A (m)

B (m)

 

 

 

 

 

 

 

 

20k

5/8"

 

1/4"

25

15

 

 

 

 

 

 

28k/30k/40k

5/8"

 

3/8"

30

20

 

 

 

 

 

 

44k/50k

3/4"

 

3/8"

40

25

 

 

 

 

 

 

80k

1"

 

5/8"

50

30

 

 

 

 

 

 

Indoor unit

A

B

Outdoor

unit

 

 

 

 

 

 

 

 

 

 

ENGLISH

CAUTION:

Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Oil trap should be installed every 5~7 meters.

Installation Manual 7

Image 8
Contents No A20025U LG Floor Standing Type Air Conditioner Table of Contents Installation Be sure not to do Be sure to follow the instructionAlways ground the product Use the correctly rated breaker or fuseBe sure the installation area does not deteriorate with age OperationUse two or more people to lift and transport the product Installation or repair of product Drained away properlyKeep level even when installing the product Outdoor unit Selection of the best locationIndoor unit Piping length and the elevation Refrigerant amount Indoor Unit InstallationOutdoor unit Installation Installation guide at the seaside Selecting the locationOutdoor UnitInstallation Method Installation works DescriptionsPreparation of installation parts and tools Installation Parts, Tools UsePreparation of Piping Move the indoor tubing and drain hose to the hole Precautions in bendingConnection of piping Connecting the Cable to Indoor Unit Wiring DetailsBConnect wires to the terminals on the control Connecting pipings to the outdoor unitConnecting the cables to the outdoor unit Wiring Power Supply and WiringPower supply Vacuum Drying of the Connecting Pipes and the Indoor Unit Form the Piping Final Check and Test Run