GENERAL INFORMATION

POWER BURNER

The initial start-up procedure of the gas power burner is provided on page 18 thru 21. Refer to Figure 12, burner exploded view for burner components location.

The sequence of operation of the power burner is provided on page 15. For detailed Power Burner Operation, Maintenance and Troubleshooting refer to the separate Power Burner Manual provided with this water heater.

THERMOSTAT

It is suggested the thermostat be turned to the lowest setting, which satisfies the hot water requirements of the system. This helps minimize scale formation in the heater.

HIGH LIMIT

The high limit (not adjustable) is factory set to cutout at 205°F (96°C). The high limit switch must be manually reset by depressing the reset button on front of the control when water temperature drops to about 180°F (82°C).

GAS AND AIR SUPPLY SPECIFICATIONS TABLE 10

Model

GPG/GPV-540A

GPG/GPV-650A

GPG/GPV-750A

Min. Dynamic Gas

 

 

 

 

Supply Line

8” w.c. (2 kPa) When heater is ON

Pressure

 

 

 

 

Max. Static Gas

 

 

 

 

Supply Line

14” w.c. (3.5 kPa) When heater is OFF

Pressure

 

 

 

 

Gas Manifold

4.7”w.c. (1.1 kPa)

4.7”w.c. 1.1 kPa)

4.7”w.c. (1.1 kPa)

Pressure

(Ref.)*

(Ref.)*

 

(Ref.)*

 

 

 

 

 

Gas Orifice Size

1/2”

11/16”

 

N/A

Air Inlet Damper

3**

4.5**

 

5.6**

Dial Setting

 

 

 

 

 

Combustion

Flue Gas O2: 5 - 6.5%**

 

Emissions

(or CO2 reading 8 - 9%)

 

Range

 

 

 

 

 

 

 

 

 

 

*Note: Flue gas excess O2 below 3% may cause combustion chamber premature failure; flue gas excess O2 above 7% may cause rough operation or incomplete combustion. Final manifold pressure settings should be based on flue O2/CO2 reading!

**Note: Air inlet damper setting needs to be adjusted at field for direct vent and/or high elevation installations.

MAINTENANCE

GENERAL

KEEPAPPLIANCEAREACLEARANDFREEFROMCOMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. (SEE WARNING PAGE 6).

Water heater maintenance includes periodic tank flushing and cleaning, and removal of lime scale. The power burner should be inspected and adjusted to maintain proper combustion. Refer

to the following table. A periodic inspection of the venting system should be made. Where used the water heating system circulating pump should be oiled.

MAINTENANCE SCHEDULE

Following are the instructions for performing some of the recommended maintenance. Power burner inspection and adjustment should be performed by a competent technician.

MAINTENANCE SCHEDULE

Component

Operation

Interval

Required

 

 

 

 

 

Sediment

 

 

Tank

Removal

Monthly

Flushing

 

 

 

 

 

Lime Scale

 

UN-LIME®

 

Removal

Semi-Annually

Delimer

 

 

 

 

Relief Valve

Inspect

Semi-Annually

 

 

 

 

 

 

 

 

SAE No. 20

Circulating Pump(1)

Oiling

Four Months

non-detergent

 

 

 

motor oil

 

 

 

 

PowerBurnerBlower

Clean Inlet

 

 

Screen and

As Required

Soft Brush

 

Blower Wheel

 

 

 

 

 

 

Power Burner and

 

 

 

Ignition Device(2)

Inspection

Semi-Annually

 

 

 

 

 

 

 

 

Make sure gate

Barometric Damper

Inspect

Every 3

swings freely,

 

 

Months

no spillage

 

 

 

into room

 

 

 

 

Flue

Cleaning

As Required

Wire Brush

 

 

 

 

 

 

Every 3

Joints should

Vent System

Inspect

Months

be sealed

 

 

 

 

(1)If furnished with oiling provisions.

(2)If flange gasket is damaged, it must be replaced.

ELECTRICAL SERVICING

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.

VERIFY PROPER OPERATION AFTER SERVICING.

FLUSHING

1.Turn off the heater electrical disconnect switch.

2.Open the drain valve and allow water to flow until it runs clean.

3.Close the drain valve when finished flushing.

4.Turn on the heater electrical disconnect switch.

27

Image 27 Contents
Models GPG/GPV-540A, 650A and 740A Foreword ROUGH-IN DimensionsGeneral Safety Information Table of ContentsExtended NON-USE Periods FeaturesUncrating Installation InstructionsDishwashing Machine Requirement Required AbilityVenting Hard WaterClearances AIR RequirementsVent Connections Barometric Draft Control AssemblyVertical Venting for GPG Models Horizontal SIDE-WALL Venting For GPV ModelsVent Terminal LOCATIONS-EXHAUST Vent System InstallationVent Terminal LOCATIONS-INTAKE Direct Venting for GPV ModelsDirect Vent System Installation Vent Diameter GPV -540A, 650A & 740A GAS PipingSources of Ignition for this Purpose GAS Meter Size City Gases onlyGAS Pressure Regulation GAS ValvesWater Line Connections Relief ValveSystem Connections Circulating Pump Wiring Diagram Installation DiagramsWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Filling Heater WiringStart UP PurgingPage Page For Your Safety Read Before Lighting Sequence of Operation Page Premix LOW NOx Burner Exploded View for GPG Models Premix LOW NOx Burner Exploded View for GPV Models General Information MaintenanceDraining Sediment RemovalLime Scale Removal Checklist and Service Water Leakage is Suspected TroubleshootingWater is TOO HOT Water Heater Makes SoundsBurner Lockout Once in a While Motor will not RUNGAS Fails to Shut OFF Noisy Burner OperationModel GPG/GPV Limited Warranty Replacement Parts List Part List for GPG Burner Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax