Refer to Table 2 for limitations of venting system design for horizontal venting.

TABLE 2

 

 

 

GPV-540A-740A

Flue Outlet Dia. (Inches/mm)

 

9” (228.6)

Flue Reducer

 

9” x 8”

Dimensions -Supplied (Inches/mm)

228.6 x 203.2

Minimum Outlet Vent Dia. (Inches/mm)

8” (203.2)

Maximum Number

 

90°

4

Of Elbows

 

45°

8

Maximum Total Vent System

 

75

Length, Equiv. Feet/Meters

 

(23 m)

When calculating the equivalent length of a venting system each 90° elbow is equivalent to 10 feet (3 m) of straight pipe. In no case 45° elbow is equivalent to 5 feet (1.5 m) of straight pipe. In no case may the sum of the straight pipe lengths and the equivalent length of the elbows exceeds 80 feet (24.3 m).

Note the minimum vent diameter in Table 2.

Refer to Table 3 for the correct vent terminal size for each heater. The dimensions noted in Table 3 refer to Figure 5.

TABLE 3

Heater

Terminal

 

 

 

 

Rough-In

Model

Model

A

B

C

D

Dimensions

GPV

 

 

 

 

 

 

540A-

VH-1-8”

19-7/8”

13”

10-9/16”

8-5/8”

11-1/16”

740A

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 5

Use only the sidewall vent terminal supplied with the heater. These terminals are specifically listed for use on these State heaters.

VENT TERMINAL LOCATIONS-EXHAUST

When considering location for sidewall vent terminals refer to the latest edition of the National Fuel Gas Code which recommends that vent terminals:

1.Shall be located not less than 12” (304.8 mm) above grade.

2.Shall be located not less than 7 feet (2.1 m) above grade when adjacent to a public walkway.

3.Shall terminate at least 3 feet (0.9 m) above any forced air inlet within 10 feet (3 m).

4.Shall terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from or 1 foot above any door, window or gravity air inlet into any building.

5.Shall not be closer than 3 feet (0.9 m) from the inside corner of an L- shaped structure.

6.Shall be located above the snow line in geographical areas where snow accumulates.

VENT SYSTEM INSTALLATION

This heater is a category III appliance when horizontally vented through a wall using the supplied sidewall vent terminal. All national and local codes pertaining to the installation of such venting systems must be followed.

Horizontal portions of the vent system must be installed with a minimum upward slope of 1/4” per foot of length.

All joints and seams in the venting system must be sealed gas tight. If a silicone sealer is used, it must have a continuous temperature rating of at least 500°F (260°C); Dow Corning 736 or equivalent must be used.

CAUTION

Use only the vent hood supplied with this kit. Only supplied hood provides required clearances from combustibles, both through the wall and the exterior siding. Termination of a sidewall vent system with a device other than the supplied vent hood could affect system performance and result in a safety hazard.

IMPORTANT

Plan the layout of the vent system backward from the vent termination to the water heater.

1.Use the layout of the vent system backward from the vent termination to the water heater.

BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL. REFER TO TABLE 5 FOR THE MAXIMUM WALL THICKNESS “B” FOR EACH MODEL.

2.Slide hood through opening from outside. Fasten hood to exterior wall with anchors and screws supplied.

3.Install covers plate and fasten to inside wall with 4 screws.

4.Attach a seal ring (Meltalbestos SR or equivalent) to the vent hood collar, see Figure 7. Attach Selkirk Metalbestos model PS or model G venting to the seal ring following the venting manufacturer’s instructions. For total safety, it is recommended that only venting listed for use with category III appliances (positive vent pressure, non-condensing) should be used between the heater and the vent hood, even through national or local codes may allow the use of type B or single-wall vent.

5.Install the remaining vent sections back to the heater, following the venting manufacturer’s instructions on assembling and sealing joints. Follow good venting practice regarding properly supporting vent system and keeping the number of offsets to a minimum. See Table 2 for the maximum allowable number of elbows in venting system.

6.Install the flue reducer included with the exhaust hood between the vent system and the heater.

7.Seal all vent connections and venting with sealants supplied by vent pipe manufacturer or with a high-temperature silicone sealant suitable for continuous temperatures of 500°F (260°C). Acceptable sealant include Dow Corning 736 or equivalent.

8

Image 8
Contents Models GPG/GPV-540A, 650A and 740A ROUGH-IN Dimensions ForewordTable of Contents General Safety InformationFeatures Extended NON-USE PeriodsInstallation Instructions Dishwashing Machine RequirementRequired Ability UncratingHard Water ClearancesAIR Requirements VentingBarometric Draft Control Assembly Vertical Venting for GPG ModelsHorizontal SIDE-WALL Venting For GPV Models Vent ConnectionsVent System Installation Vent Terminal LOCATIONS-EXHAUSTDirect Venting for GPV Models Vent Terminal LOCATIONS-INTAKEDirect Vent System Installation GAS Piping Vent Diameter GPV -540A, 650A & 740AGAS Meter Size City Gases only GAS Pressure RegulationGAS Valves Sources of Ignition for this PurposeSystem Connections Water Line ConnectionsRelief Valve Installation Diagrams Circulating Pump Wiring DiagramWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Heater Wiring Start UPPurging FillingPage Page For Your Safety Read Before Lighting Sequence of Operation Page Premix LOW NOx Burner Exploded View for GPG Models Premix LOW NOx Burner Exploded View for GPV Models Maintenance General InformationLime Scale Removal DrainingSediment Removal Checklist and Service Troubleshooting Water is TOO HOTWater Heater Makes Sounds Water Leakage is SuspectedMotor will not RUN Burner Lockout Once in a WhileNoisy Burner Operation GAS Fails to Shut OFFModel GPG/GPV Limited Warranty Replacement Parts List Part List for GPG Burner Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax

740A, 540A, 650A specifications

State Industries is well-known for its high-quality water heating solutions, and among its product lineup, the 650A, 540A, and 740A models stand out for their advanced features and technology. Each of these models cater to different needs, making them versatile choices for both residential and commercial applications.

The State Industries 650A model is designed for efficient hot water delivery, featuring a powerful heating element that ensures rapid heating of water. It has an impressive recovery rate, which is crucial for homes with higher hot water demands. The 650A also integrates a robust insulation system that minimizes heat loss, ensuring energy efficiency. With a capacity of 65 gallons, it is perfectly suited for larger households or small commercial setups.

Next in the lineup is the 540A model, which strikes a balance between performance and size. With a capacity of 54 gallons, this model is ideal for medium-sized homes. It employs advanced heating technology that significantly reduces energy consumption while providing consistent hot water supply. The 540A is also equipped with a user-friendly digital interface that allows homeowners to monitor temperatures and set preferences with ease. Additionally, it features durable construction materials, promoting longevity and reliability in everyday use.

Finally, the 740A model offers the highest capacity of the three, boasting an extensive 74-gallon storage tank. This model is particularly advantageous for larger families or businesses that require substantial hot water availability. Similar to the 650A, the 740A employs advanced insulation techniques, ensuring that energy loss is minimized. It's also equipped with smart technology that allows for remote monitoring and adjustment, providing convenience for busy homeowners.

All three models utilize high-efficiency heating elements and are designed for easy installation and maintenance. They incorporate safety features such as temperature and pressure relief valves to ensure safe operation. Moreover, these units are built to meet or exceed industry standards, making them a reliable choice for anyone looking to invest in a hot water solution. Overall, State Industries continues to lead the market with innovative products like the 650A, 540A, and 740A, catering to diverse hot water needs with efficiency and reliability.