State Industries 740A, 540A, 650A warranty

Page 17

TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE

WITH RECIRCULATION OF SANITIZING LOOP

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE

AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON

PAGE 23. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO

OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE

FOR HOT WATER SUPPLIED TO FIXTURES.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW

PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,

PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER

SYSTEM MUST BE PROVIDED.

*PIPE TO OPEN DRAIN

INSTALL IN ACCORDANCE WITH LOCAL CODES

NOTE 1: TOGGLE SWITCH CONTROLS 180° WATER CIRCULATION.

INSTALL ON OR CLOSE TO DISHWASHING MACHINE.

TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE

RINSE OPERATION AND OPEN (OFF) WHEN DISHWASHER

IS NOT OPERATING OR WHEN ON LONG STANDBY.

NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED

TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE

SANITIZING LOOP. CONTROL SHOULD BE SET AT 185°F.

NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW

RATE DOES NOT CAUSE UNNECESSARY TURBULENCE

IN THE TANK.

NOTE 4: IF TEMPERED WATER IS RECIRCULATED, RETURN LINE

SHOULD BE CONNECTED AT POINT “’A”.

17

Image 17 Contents
Models GPG/GPV-540A, 650A and 740A Foreword ROUGH-IN DimensionsGeneral Safety Information Table of ContentsExtended NON-USE Periods FeaturesDishwashing Machine Requirement Installation InstructionsRequired Ability UncratingClearances Hard WaterAIR Requirements VentingVertical Venting for GPG Models Barometric Draft Control AssemblyHorizontal SIDE-WALL Venting For GPV Models Vent ConnectionsVent Terminal LOCATIONS-EXHAUST Vent System InstallationVent Terminal LOCATIONS-INTAKE Direct Venting for GPV ModelsDirect Vent System Installation Vent Diameter GPV -540A, 650A & 740A GAS PipingGAS Pressure Regulation GAS Meter Size City Gases onlyGAS Valves Sources of Ignition for this Purpose System Connections Water Line Connections Relief Valve Circulating Pump Wiring Diagram Installation DiagramsWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Start UP Heater WiringPurging FillingPage Page For Your Safety Read Before Lighting Sequence of Operation Page Premix LOW NOx Burner Exploded View for GPG Models Premix LOW NOx Burner Exploded View for GPV Models General Information MaintenanceLime Scale Removal DrainingSediment Removal Checklist and Service Water is TOO HOT TroubleshootingWater Heater Makes Sounds Water Leakage is SuspectedBurner Lockout Once in a While Motor will not RUNGAS Fails to Shut OFF Noisy Burner OperationModel GPG/GPV Limited Warranty Replacement Parts List Part List for GPG Burner Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax