State Industries 540A, 650A, 740A warranty

Page 24

1.Check gas line pressure with a manometer.

Set initial gas line pressure at 9-10” w.c. before turning the heater “ON”.

Read gas line pressure and gas manifold pressure when the heater main gas is “ON”.

Adjust gas line regulator setting if the gas line pressure drops below 8” w.c. when heater main gas is “ON”.

Check heater gas manifold pressure (see Table 10) using a manometer connected to the manifold pressure tap on the Robertshaw gas control valve, see Figure 10.

Important Note: Use gas manifold pressure as initial setup only. The final air and gas settings should be based on fire rate and flue gas 02/C02 reading, see Table 10 for normal 02/ C02 reading.

WARNING

Excessive gas line pressure drop and/or burner manifold pressure too low may cause burner start/operate with excessive noise!

2.Cycle the burner “ON” and “OFF” several times to check its operation. Make sure the gas line pressure is below 14” w.c. when burner is “OFF”. If gas line pressure exceeds 14” w.c. when the burner is off, the gas supply line size must be increased to correct this problem (see Table 9 for gas pipe size).

3.Check the operation of the limiting and operating controls.

4.Check the vent system seams and joints and ensure that there is no discharge of flue products into the room. For standard vertical vent systems, check the barometric damper control to make sure it operates freely and there is no discharge of flue products into the room.

5.Check the input rate by clocking the gas meter.

ADJUSTMENT PROCEDURE FOR FIRE-RATE, LOW NOX AND HIGH ELEVATION (Fine-Tune)

An acceptable input rate is within 2% of the rated input for the model. Should it be necessary to adjust the gas pressure to the burner and/or air damper of the blower to obtain the full input rate, these steps should be followed:

WARNING

Never set burner combustion too lean (causing noisy operation) or too rich (causing combustion chamber premature failure) see Table 10 for proper settings.

WARNING

Never set air damper outside of its adjustment range of the rated fire rate unless authorized by a State Service Center.

Important Note: Final gas and air settings should be based on flue gas CO2 or O2 reading (see Table 10). Increase burner manifold pressure will increase fire rate and flue gas CO2 reading. Increase air damper setting will decrease fire rate and decrease flue gas CO2 reading. Adjustable air damper is preset for the rated fire-rate prior to delivery, should not be re-adjusted unless it’s

a high elevation application and/or a direct vent (long air intake vent) application.

1.Fire Rate Adjustment (including direct vent installation).

a.Make sure the gas supply line pressure reads 8” w.c. (2 kPa) or higher when the heater is running.

b.Remove the pressure regulator cover screw (Figure 10) and adjust the pressure by tuning the adjustment screw w/a small screwdriver clockwise to increase gas pressure into the burner and fire rate.

Counterclockwise to decrease gas pressure and input rate.

c.Clock gas meter, repeat above Step (b) to achieve the specific input rate.

d.Measure flue gas O2 and/or CO2 (see Table 10) for acceptable O2/CO2 range.

If the O2 or CO2 reading is within the acceptable range, then proceed to Step (f).

If the O2 or CO2 reading is out of range, adjust air damper is required.

e.Repeat Steps (b), (c), (d) if air damper is adjusted.

f.Cycle heater ON/OFF.

g.Replace the gas regulator cover, pressure tap and tighten the damper center bolt.

2.Adjustment for Low NOx Emission Application.

The water heater is preset at factory for Low Nox emission combustion. Due to the installation variations, fine-tune adjustments may be required. To lower NOx emission level (30PPM corrected at 3% O2 or lower is required by SCAQMD), air damper setting may need to be slightly increased. To increase air damper setting, loosen the center nut of the inlet air damper, rotate the damper clockwise slightly, then tighten the center nut. After re-set the air damper, cycle heater

ON/OFF and check fire-rate and flue gas CO2/O2 reading.

3.Adjustment for High Elevation Application

Installation above 2000 feet sea level require new air damper settings. All the final settings should be based on flue gas

CO2/O2 reading, see Table 10. To increase air damper setting, loosen the center bolt of the inlet air damper, rotate the damper clockwise slightly, then tighten the center bolt. After re-setting the air damper, cycle heater ON/OFF and check fire-rate and flue gas CO2/O2 reading.

WARNING

UNDER NO CIRCUMSTANCES SHOULD THE INPUT RATE EXCEED THE INPUT RATE SHOWN IN THE HEATER RATING PLATE. OVERFIRING COULD RESULT IN DAMAGE OR SOOTING OF THE HEATER.

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.

24

Image 24
Contents Models GPG/GPV-540A, 650A and 740A ROUGH-IN Dimensions ForewordTable of Contents General Safety InformationFeatures Extended NON-USE PeriodsInstallation Instructions Dishwashing Machine RequirementRequired Ability UncratingHard Water ClearancesAIR Requirements VentingBarometric Draft Control Assembly Vertical Venting for GPG ModelsHorizontal SIDE-WALL Venting For GPV Models Vent ConnectionsVent System Installation Vent Terminal LOCATIONS-EXHAUSTDirect Venting for GPV Models Vent Terminal LOCATIONS-INTAKEDirect Vent System Installation GAS Piping Vent Diameter GPV -540A, 650A & 740AGAS Meter Size City Gases only GAS Pressure RegulationGAS Valves Sources of Ignition for this PurposeWater Line Connections Relief ValveSystem Connections Installation Diagrams Circulating Pump Wiring DiagramWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Heater Wiring Start UPPurging FillingPage Page For Your Safety Read Before Lighting Sequence of Operation Page Premix LOW NOx Burner Exploded View for GPG Models Premix LOW NOx Burner Exploded View for GPV Models Maintenance General InformationDraining Sediment RemovalLime Scale Removal Checklist and Service Troubleshooting Water is TOO HOTWater Heater Makes Sounds Water Leakage is SuspectedMotor will not RUN Burner Lockout Once in a WhileNoisy Burner Operation GAS Fails to Shut OFFModel GPG/GPV Limited Warranty Replacement Parts List Part List for GPG Burner Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax

740A, 540A, 650A specifications

State Industries is well-known for its high-quality water heating solutions, and among its product lineup, the 650A, 540A, and 740A models stand out for their advanced features and technology. Each of these models cater to different needs, making them versatile choices for both residential and commercial applications.

The State Industries 650A model is designed for efficient hot water delivery, featuring a powerful heating element that ensures rapid heating of water. It has an impressive recovery rate, which is crucial for homes with higher hot water demands. The 650A also integrates a robust insulation system that minimizes heat loss, ensuring energy efficiency. With a capacity of 65 gallons, it is perfectly suited for larger households or small commercial setups.

Next in the lineup is the 540A model, which strikes a balance between performance and size. With a capacity of 54 gallons, this model is ideal for medium-sized homes. It employs advanced heating technology that significantly reduces energy consumption while providing consistent hot water supply. The 540A is also equipped with a user-friendly digital interface that allows homeowners to monitor temperatures and set preferences with ease. Additionally, it features durable construction materials, promoting longevity and reliability in everyday use.

Finally, the 740A model offers the highest capacity of the three, boasting an extensive 74-gallon storage tank. This model is particularly advantageous for larger families or businesses that require substantial hot water availability. Similar to the 650A, the 740A employs advanced insulation techniques, ensuring that energy loss is minimized. It's also equipped with smart technology that allows for remote monitoring and adjustment, providing convenience for busy homeowners.

All three models utilize high-efficiency heating elements and are designed for easy installation and maintenance. They incorporate safety features such as temperature and pressure relief valves to ensure safe operation. Moreover, these units are built to meet or exceed industry standards, making them a reliable choice for anyone looking to invest in a hot water solution. Overall, State Industries continues to lead the market with innovative products like the 650A, 540A, and 740A, catering to diverse hot water needs with efficiency and reliability.