State Industries 650A, 540A, 740A warranty Motor will not RUN, Burner Lockout Once in a While

Page 31

20, and the troubleshooting section of burner manual before continuing.

Make sure the appliance is connected to a 120 Vac power supply, burner switch is “ON” and manual gas valve is in the “ON” position, and all electrical connections are secure before continuing to troubleshoot this appliance.

MOTOR WILL NOT RUN

1.Confirm 120 Vac. Also, to verify correct polarity, check for

120 Vac between black wire and G.

If there is no voltage, check for a loose connection or open switch at the high limit or thermostat.

2.If there is 120 volts between black wire and white wire, check for loose connections or a locked rotor. If the rotor cannot be freed the motor and blower assembly must be replaced.

BURNER LOCKOUT ONCE IN A WHILE

Under this condition, the burner operates properly for days, and burner lockout occurs once in a while. The root causes for the burner occasional lockout include: (1) Gas inlet pressure too low;

(2)Condensation over the ignitor area; (3) the pilot flame is too weak to light the main flame reliably; (4) the pilot air/gas ratio is out of range causing pilot flame to be unreliable.

1.Turn burner switch to “OFF” position and turn off the main gas valve (Robertshaw®).

2.Install manometers for gas inlet pressure, manifold pressure, and pilot gas pressure, see Figure 12 for the pressure ports location).

3.Check for the gas inlet pressure, reset the service regulator (if required) to get 9” w.c. (2.2 kPa) - 10” w.c. (2.4 kPa) inlet pressure while the burner is in the “OFF” position.

4.Turn the burner “ON”,

Take blower pressure at the pressure port during the purge cycle, see Figure 12 for location.

Take the pilot gas pressure at the same pressure port during the ignition period (following 45 seconds purge cycle).

The pilot gas pressure should be 0.6” - 0.9” w.c. higher than blower pressure, if not, adjust the pilot gas regulator (during the ignition cycle, see Figure 12.

If burner lights on during the ignition cycle, cycle the unit on/off several times to ensure pilot system is reliable. Turn off the burner, then follow Step 6.

5.Turn the burner “OFF”, follow burner manual instructions to remove the pilot assembly (also refer to Figure 12 in this manual) and procedures to check pilot assembly. Items to check for the pilot system include:

Check for condensation over ignitor area.

Check for the ignitor gap (1/8” - 3/16”).

Check for the thermal cutoff continuity by ohm meter, replace it if the thermal cutoff is open.

Check for the low gas pressure switch by ohm meter

(while pilot gas pressure is 7” w.c. [1.7 kPa] or higher).

Check for the continuity between the flame rod and sensor connection at Honeywell flame control module by the ohm meter.

Check for ignitor wire connections and spark leakage

(call AOS service center for steps of spark leakage checking).

Following burner manual instructions to re-install the pilot assembly.

6.Turn on the Robertshaw gas valve, turn the burner switch to “ON” position. Cycle the heater ON/OFF several times to ensure the problem is solved.

MOTORRUNSCONTINUOUSLY,PREPURGETIMEELAPSESBUT MAIN FLAME NOT ESTABLISHED (BURNER LIGHT NEVER ON)

1.When the heater is first installed, gas line must be purged properly prior to start-up. This heater is equipped with a flame control module that only allows one “trial for ignition” for

15 seconds and locks out if no flame signal is detected. For initial start-up, two or more resets may be required to ensure that all the air has been purged from the gas pilot line. To reset the heater, turn the burner power switch to “OFF” position for at least one minute, then turn it back “ON”.

2.Check for gas supply line manual valves in “ON” position, and line pressure. Make sure the pilot manual gas cock (nearby the main gas valve) is fully open.

3.After the 45-seconds prepurge cycle, the pilot gas valve (mounted on the panel) “click” sound should be heard. If you hear the pilot gas energized, proceed to Step 5.

4.Check 24 Vac control circuit in the following systematic approach:

Check for 24V between “24V” and “GND” of Honeywell Flame

Control Module, which is located inside the burner control panel. If voltage is OK, proceed to Step 5.

If there’s no voltage, check for 24V between the air switch

“COM” terminal and GND (the air switch is mounted on the control panel, the switch cover needs to be removed to access the wiring terminal “COM” and “NO”). If there’s no 24 V, check for a loose connection between the 24V transformer and air switch, or a defective transformer.

If there’s 24V at “COM” terminal, check for 24V between the air switch terminal “NO” (normally open) and GND. If there’s no 24V, the air switch pressure may be set too high or a defective air switch or loose connections of pressure sensing tubings. To lower the air switch setting, make sure the blower is running and blower wheel and air inlet are free from dirt, counterclockwise turn the switch setting-screw until the switch is closed. Call the State Technical Center before you reset the switch.

If there’s 24V at “NO” terminal of the air switch, check for 24V at the air intake pressure switch connectors, (this switch is only supplied for direct vent systems). If there’s no 24V at the switch connectors, check for loose connections, air intake blockage, or a defective air switch.

Do not proceed to Step 5 unless 24V is detected at “24V” terminal of the Honeywell Module.

31

Image 31
Contents Models GPG/GPV-540A, 650A and 740A Foreword ROUGH-IN DimensionsGeneral Safety Information Table of ContentsExtended NON-USE Periods FeaturesUncrating Installation InstructionsDishwashing Machine Requirement Required AbilityVenting Hard WaterClearances AIR RequirementsVent Connections Barometric Draft Control AssemblyVertical Venting for GPG Models Horizontal SIDE-WALL Venting For GPV ModelsVent Terminal LOCATIONS-EXHAUST Vent System InstallationVent Terminal LOCATIONS-INTAKE Direct Venting for GPV ModelsDirect Vent System Installation Vent Diameter GPV -540A, 650A & 740A GAS PipingSources of Ignition for this Purpose GAS Meter Size City Gases onlyGAS Pressure Regulation GAS ValvesRelief Valve Water Line ConnectionsSystem Connections Circulating Pump Wiring Diagram Installation DiagramsWiring Diagram for Tempered Water Loop if Used Circulating Pump Wiring Diagram Page Manifold Kits Filling Heater WiringStart UP PurgingPage Page For Your Safety Read Before Lighting Sequence of Operation Page Premix LOW NOx Burner Exploded View for GPG Models Premix LOW NOx Burner Exploded View for GPV Models General Information MaintenanceSediment Removal DrainingLime Scale Removal Checklist and Service Water Leakage is Suspected TroubleshootingWater is TOO HOT Water Heater Makes SoundsBurner Lockout Once in a While Motor will not RUNGAS Fails to Shut OFF Noisy Burner OperationModel GPG/GPV Limited Warranty Replacement Parts List Part List for GPG Burner Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax

740A, 540A, 650A specifications

State Industries is well-known for its high-quality water heating solutions, and among its product lineup, the 650A, 540A, and 740A models stand out for their advanced features and technology. Each of these models cater to different needs, making them versatile choices for both residential and commercial applications.

The State Industries 650A model is designed for efficient hot water delivery, featuring a powerful heating element that ensures rapid heating of water. It has an impressive recovery rate, which is crucial for homes with higher hot water demands. The 650A also integrates a robust insulation system that minimizes heat loss, ensuring energy efficiency. With a capacity of 65 gallons, it is perfectly suited for larger households or small commercial setups.

Next in the lineup is the 540A model, which strikes a balance between performance and size. With a capacity of 54 gallons, this model is ideal for medium-sized homes. It employs advanced heating technology that significantly reduces energy consumption while providing consistent hot water supply. The 540A is also equipped with a user-friendly digital interface that allows homeowners to monitor temperatures and set preferences with ease. Additionally, it features durable construction materials, promoting longevity and reliability in everyday use.

Finally, the 740A model offers the highest capacity of the three, boasting an extensive 74-gallon storage tank. This model is particularly advantageous for larger families or businesses that require substantial hot water availability. Similar to the 650A, the 740A employs advanced insulation techniques, ensuring that energy loss is minimized. It's also equipped with smart technology that allows for remote monitoring and adjustment, providing convenience for busy homeowners.

All three models utilize high-efficiency heating elements and are designed for easy installation and maintenance. They incorporate safety features such as temperature and pressure relief valves to ensure safe operation. Moreover, these units are built to meet or exceed industry standards, making them a reliable choice for anyone looking to invest in a hot water solution. Overall, State Industries continues to lead the market with innovative products like the 650A, 540A, and 740A, catering to diverse hot water needs with efficiency and reliability.