State Industries GPO 86-199 manual Operation, Filling, Start-Up, Water Temperature Control

Page 10

OPERATION

GENERAL

Never operate the heater unless the tank is filled with water and a temperature and pressure relief valve is installed.

FILLING

1.Oil burner electrical disconnect switch should be in the "OFF position

2.Close the heater drain valve.

3.Open a nearby hot water faucet to allow the air in the system to escape.

4.Fully open the cold water inlet valve, filling the heater and piping.

5.Close the hot water faucet as water starts to flow from the opening, Leave the cold water inlet valve fully open. The heater is now ready to start-up if being placed in operation for the first time.

START-UP

The following checks should be made by the installer when the heater is placed into operation for the first time:

1.Check all factory and field made water, oil and electrical connections for tightness. Also check flue gas disposal provisions on top the heater.

Repair any water and oil leaks. Tighten electrical and flue connections as necessary.

2.Where the water heater or water heating systems includes a circulating pump, it may need to be lubricated before operated. The tube of lubricant supplied with the pump includes directions for use.

Field installed circulating pumps should be all bronze construction.

Be sure the oil burner, related piping, valves and controls are in place, adjusted and ready for operation before turning on the electricity.

3.Adjust the heater mounted control as follows:

THERMOSTAT (adjustable) set for desired water temperature.

It is suggested the thermostat be turned to the lowest setting which satisfies the hot water requirements of the system. This helps minimize scale formation in the heater.

HIGH LIMIT (not adjustable, manual reset) factory set to cutout at 195° F (90.5°C).

If the high limit is actuated, the safety primary control will cause the oil burner to shut down. See SAFETY PRIMARY CONTROL, page 21.

To reset the safety primary control, depress the red button on the control.

Depress red button one time only. If burner does not operate after depressing red button one time, call service man.

4.Turn on the oil burner electrical disconnect switch.

5.The heater will begin normal operation on the thermostat's "call for heat".

6.To turn the heater off, open the electrical disconnect switch. If the heater is to remain inoperative for a long period of time, close the shutoff valve on the oil supply line.

WATER TEMPERATURE CONTROL

DANGER

THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND OR DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH THE PERSONS AGE AND TIME OF EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER.

THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET TEMPERATURES.

SETTING THE WATER HEATER TEMPERATURE AT 120°F (48.9°C) WILL REDUCE THE RISK OF SCALDS. Some states require settings at specific lower temperatures.

Figure 16 shows the approximate time-to-burn relationship for normal adult skin. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F. If you experience this type of use, you should consider using lower temperature settings to reduce scald hazards.

Temperature

Time to Produce 2nd & 3rd

Setting

Degree Burns on Adult Skin

180°F (82.2°C)

Nearly instantaneous

170°F (76.6°C)

Nearly instantaneous

160°F (71.1°C)

About 1/2 second

150°F (65.5°C)

About 1-1/2 seconds

140°F (60.0°C)

Less than 5 seconds

130°F (54.4°C)

About 30 seconds

120°F (48.9°C)

More than 5 minutes

 

 

 

FIGURE 16

Values for reducing point-of-use temperature by mixing cold and hot water are available. Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority.

The water temperature is controlled by a thermostat, fig. 17, which has two sensing elements. One sensor is located near the top of the tank and the other is near the center. The thermostat is set in the lowest position before the heater leaves the factory.

The thermostat temperature dial, fig. 17, is accessible by taking off the access cover and removing the control cover. The dial is adjustable and may be set for 120°F (48.9°C) to 170°F (76.6°C) water temperature, but 120°F is the recommended starting point. It is suggested the dial be placed in the lowest setting which produces an acceptable hot water supply. This will always give the most energy efficient operation. The temperature control has a 4F° (2.2C°)fixed differential.

HIGH LIMIT SWITCH (E.C.O)

The dual bulb controller (fig.17) contains the high limit (energy cutoff) sensor. The high limit switch interrupts main burner gas flow should the water temperature reach 195°F (90.5°C).

In the event of high limit switch operation, the appliance cannot be restarted unless the water temperature is reduced by 20F° (11.1C°) (approx.) and the high limit reset button on front of limit control (fig.17) is depressed.

Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. Contact your dealer or servicer if continued high limit switch operation occurs.

10

Image 10
Contents Place These Instructions Adjacent to Heater Lindahl Parkway Ashland City, TNNotify Owner to Keep for Future Reference Recovery CAPACITIES, based on 80% efficiency Features and SpecificationsNominal Model Dimensions GPOApprovals Table of ContentsIdentification Safety InstallationCombustion and Ventilation AIR Proper Installation on Combustible FlooringClearances Chemical Vapor CorrosionFlue GAS Venting Vent Connector and Draft RegulatorProper Vent Connector Installation ChimneyClosed Water System Drain Valve and Access PanelsWater Piping Fuel SystemsGravity FEED, Supply Line ONLY, Installation Burner InstallationTypical Heater Installation Figure System TypesFuel Pump OIL Pump & Nozzle SpecificationsAssembly of the OIL Burner to the Heater BurnerOperation Water Temperature ControlHigh Limit Switch E.C.O FillingDraining MaintenanceBurner Certificate Combustion Test Relief ValvesLime Scale Removal Sediment RemovalFlo-jug Method of Deliming Vent System Circulating PumpSoot Removal Anode ROD InspectionInset B Installation DiagramsInstall in Accordance with Local Codes Inset aSingle Temperature or Booster Inset B Install in Accordance with Local Codes Inset a Not Enough or no HOT Water Check List and Service InformationElectrical Wiring Replacement Manifold KIT Commercial OIL Fired Water HeatersWater Heater Makes Sounds Burner STARTS-WONT OperateWater is TOO HOT Water Leakage is SuspectedSafety Primary Control Combustion Test SpecificationsNormal START, but Locks OUT on Safety ProcedureTroubleshooting Item no Cleanout Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 FaxDescription