State Industries GPO 86-199 Combustion Test Specifications, Normal START, but Locks OUT on Safety

Page 21

If the problem is not getting a spark to ignite the oil, check for the following:

1.Loose wiring.

2.Red ignition transformer.

3.Low voltage.

4.Crack in electrode porcelain insulators.

5.Electrodes carboned or out of adjustment.

6.Weak or no contact between bus bars and terminals of transformer.

NORMAL START, BUT LOCKS OUT ON SAFETY

When the thermostat calls for heat and the burner starts normally but then locks out on safety after about 15 seconds:

1.Improper setting of combustion air (too much air).

2.Weak or dirty flame detector.

3.Improper positioning of flame detector.

4.Bad flame detector.

5.Wiring from flame detector to primary not continuous or not making good contact.

6.Bad safety primary control.

7.Clogged, defective or undersized nozzle.

SAFETY PRIMARY CONTROL

Normal Burner Cycle

Although a normal burner cycle does not create a service problem, it is important to know what happens to better understand the problem when the unit is not operating properly.

The instant the thermostat calls for heat, the flame detector sees darkness and causes the sensor to conduct current. When the sensor conducts current, the motor relay coil pulls in, starting the burner motor and energizing the ignition transformer through the motor relay contacts. At the same instant the motor relay coil pulls in, the safety heater is energized.

When flame is established, the resistance of the flame detector drops (providing the flame detector can see the flame properly) which causes the sensor to block the current. When the sensor blocks, the safety heater drops out of the circuit and the motor relay coil continues to hold in through a set of holding contacts on the motor relay until the thermostat is satisfied and the burner shuts down.

FLAME FAILURE AFTER NORMAL IGNITION

If, for some reason, there is a flame out, the flame detector sees darkness which causes the sensor to conduct current and again energize the safety heater. In approximately 15 seconds the safety contact will open and shut down the burner. The safety contacts of the safety primary control are the manual reset type, which means that the red safety button must be reset before trying again for ignition. When this occurs, allow about 5 minutes for safety heater to cool before depressing the red safety button.

Depress red button one time only. If burner does not operate after depressing red button one time, check combustion chamber. If combustion chamber is soaked with oil the combustion chamber must be replaced.

Some of the possible reasons for flame failure after normal ignition has occurred are:

1.Dirt or water in the supply line.

2.Pump loosing prime.

3.Bad motor.

4.Erratic or low pressure at fuel pump.

5.Defective pump.

6.Loose wiring or connections.

7.Clogged or damaged nozzle.

8.Oil tank empty.

9.Oil tank not vented.

10.Clogged filter in oil line.

11.Ice in fuel line.

COMBUSTION TEST

SPECIFICATIONS

GENERAL

A combustion test kit, capable of testing CO2 content, stack temperature, draft and smoke must be available to aid in adjusting the unit and filling out the Oil Burner Certificate. A pressure gauge is needed to measure and adjust oil pump pressure.

PROCEDURE

1.Check nozzle size, see Table 8 on Page 9.

2.Open air band about halfway and being certain heater is filled with water, start burner.

3.Check oil pump pressure. It should be 110 psig for the GPO-199 and 100 psig for all other models. Adjust setting as necessary.

4.Allow burner to operate for 15 minutes before proceeding with test.

5.After 15 minutes operation, check the draft in chimney connector, about halfway between the heater and the draft regulator and adjust the draft regulator until the correct reading is obtained.

Draft in Chimney

.03 to .05

Connector

Inches of Water

 

 

6.Adjust air band until flame has smoky tips. Immediately increase air supply until the smoky tips just disappear.

7.Using combustion test kit, check smoke density and CO2 in the chimney connector.

 

Preferably No. 1

Spot

Smoke Density

(Not Over No. 2 Spot

CO2

9% to 12%

 

 

 

 

Adjust air supply with air band to achieve the highest CO2 readings with an acceptable smoke density reading. Test and readjust as necessary.

8.Check the stack temperature halfway between the heater and the draft regulator.

Stack

Min.

400°F (204°C)

 

 

Temperature

 

 

Max.

600°F (315°C)

 

 

 

 

If stack temperature is too high, check for a soot accumulation in heater or excessive oil pump pressure.

9.Recheck combustion efficiency against specifications when final adjustments have been made.

21

Image 21
Contents Lindahl Parkway Ashland City, TN Place These Instructions Adjacent to HeaterNotify Owner to Keep for Future Reference Nominal Model Dimensions Features and SpecificationsRecovery CAPACITIES, based on 80% efficiency GPOTable of Contents ApprovalsIdentification Installation SafetyClearances Proper Installation on Combustible FlooringCombustion and Ventilation AIR Chemical Vapor CorrosionProper Vent Connector Installation Vent Connector and Draft RegulatorFlue GAS Venting ChimneyWater Piping Drain Valve and Access PanelsClosed Water System Fuel SystemsTypical Heater Installation Figure Burner InstallationGravity FEED, Supply Line ONLY, Installation System TypesAssembly of the OIL Burner to the Heater OIL Pump & Nozzle SpecificationsFuel Pump BurnerHigh Limit Switch E.C.O Water Temperature ControlOperation FillingBurner Certificate Combustion Test MaintenanceDraining Relief ValvesSediment Removal Lime Scale RemovalFlo-jug Method of Deliming Soot Removal Circulating PumpVent System Anode ROD InspectionInstall in Accordance with Local Codes Installation DiagramsInset B Inset aSingle Temperature or Booster Inset B Install in Accordance with Local Codes Inset a Electrical Wiring Replacement Check List and Service InformationNot Enough or no HOT Water Manifold KIT Commercial OIL Fired Water HeatersWater is TOO HOT Burner STARTS-WONT OperateWater Heater Makes Sounds Water Leakage is SuspectedNormal START, but Locks OUT on Safety Combustion Test SpecificationsSafety Primary Control ProcedureTroubleshooting Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax Item no Cleanout AssemblyDescription