OIL BURNER SPECIFICATIONS
The oil burner nameplate decal includes a series code which identifies the major features of the oil burner. The series number is the last three digits of the burner code number.
Table 3 below describes the oil burner characteristics for each series number. The burners are to be used with fuel oil not heavier than No. 2.
TABLE 3 SOME NOTABLE OIL BURNER FEATURES
| R.W. |
|
| Suntec | Nozzle Type | |
State | Becket | Safety | Oil Pump | Oil |
|
|
Burner | Burner | Timing | Type | Pump |
|
|
Series | Model | + | Mode |
| Spray | Spray |
Number* | Number |
|
|
| Pattern | Angle |
|
|
|
| A2VA |
|
|
| AFG |
|
| 7118 | Type B |
|
940 |
| 15 Sec. | Single | - | Solid | 80° |
| SF |
| Stage | A2YA- | Cone |
|
|
|
|
| 7916 |
|
|
|
|
|
| B2VA |
|
|
|
|
|
| 8216 | Type B |
|
941 | AFG | 15 Sec. | Two- | - | Solid | 80° |
| SF | 15 Sec. | Stage | BY2A | Cone |
|
|
|
|
| 8916 |
|
|
|
|
|
|
|
|
|
*To provide the proper firing rate for each model heater, see SPECIFICATIONS: there are burner models for each heater model in table 2.
+All oil burners are UL defined as having "interrupted ignition" . . . meaning the ignition is on during the flame establishing period only. Ignition is off when the burner is off. Standard safety timing is 15 seconds.
For installations where gravity feed of fuel oil from the storage tank to the heater is practical, an oil burner with a
For installations where gravity feed cannot be employed, (the storage tank is located significantly below, or remote from, the heater) an oil burner with a
IMPORTANT
The
|
| GPO 86 | GPO86 | GPO 84 | GPO 75 | GPO 75 | GPO 69 |
Model Heater | 199 | 245 | 315/315A | 385/385A | 455/455A | 700/700/A | |
Min. | State |
|
|
|
|
|
|
Firing | Burner | 1.42 | 1.75 | 2.25 | 2.75 | 3.25 | 5.0 |
Rate |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
In | Non |
|
|
|
|
|
|
GPH | State | 1.1 | 1.5 | 2.0 | 2.5 | 3.0 | 4.5 |
| Burner |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SAFETY
DANGER
BE SURE TO TURN OFF POWER WHEN WORKING ON OR NEAR THE ELECTRICAL SYSTEM OF THE HEATER. NEVER TOUCH ELECTRICAL COMPONENTS WITH WET HANDS OR WHEN STANDING IN WATER. WHEN REPLACING FUSES ALWAYS USE THE CORRECT SIZE FUSE FOR CIRCUIT.
If it is necessary to reset the safety primary control, depress red button one time only. If burner does not operate after depressing red button one time, call serviceman.
INSTALLATION
REQUIRED ABILITY
INSTALLATION OF SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENCED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING , OIL BURNER AND ELECTRICAL WORK REQUIRED.
GENERAL
The installer should be guided by these instructions, local codes and the following publications.
•Standards for the Installation of Oil Burning Equipment, NFPA Standard No. 31, Available from National Fire Protection Association, Batterymarch Park, MA 02269.
•Code for the Installation of Heat Producing Appliances, Available from American Insurance Association, 85 John Street, New York, NY 10038.
•The National Electrical Code, ANSI/NFPA No.
•In Canada - CSA Standard No. B139, Installation Code for Oil Burning Equipment.
When other than a State burner is used, this instruction manual can be used as a general guide. The burner manufacturer's instructions will have to be consulted on specific questions of wiring, air adjustment, etc.
Do not test the burner or control system before the heater is filled with water. Follow the
UNCRATING
Uncrate the heater by removing the outside mat and top locator. The shipping pallet must be removed from the unit. It may be possible to simply unbolt the base from the pallet and, with the help of two or more persons, work the unit off the pallet. Some units will be too heavy and will require the use of jacks or lifting equipment. Safely remove the pallet and move the unit into position. Be Careful When Moving This Heater. It will tip over easily.
LEVELLING
Install the heater plumb to the ground. If it is necessary to adjust the heater, use metal shims under the channel type skid base.
LOCATION
The water heater should not be installed where the combustion air is contaminated, see COMBUSTION AND VENTILATING AIR. Temperature in the location must be above 32°F (0°C) and free of combustible dusts and flammable gases or vapors.
For the best installations, the water heater should be located:
1.On a level surface.
•Shim the channel type skid base as necessary If leveling is required.
2.Near a floor drain.
•The heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure.
•When such locations cannot be avoided, a suitable drain pan should be installed under the heater.
•The pan should be at least two inches deep, have a minimum length and width of at least two inches greater than the diameter of the heater and should be piped to an adequate drain. The pan must not restrict combustion air flow.