State Industries GPO 86-199 manual Safety, Installation

Page 4

OIL BURNER SPECIFICATIONS

The oil burner nameplate decal includes a series code which identifies the major features of the oil burner. The series number is the last three digits of the burner code number.

Table 3 below describes the oil burner characteristics for each series number. The burners are to be used with fuel oil not heavier than No. 2.

TABLE 3 SOME NOTABLE OIL BURNER FEATURES

 

R.W.

 

 

Suntec

Nozzle Type

State

Becket

Safety

Oil Pump

Oil

 

 

Burner

Burner

Timing

Type

Pump

 

 

Series

Model

+

Mode

 

Spray

Spray

Number*

Number

 

 

 

Pattern

Angle

 

 

 

 

A2VA

 

 

 

AFG

 

 

7118

Type B

 

940

 

15 Sec.

Single

-

Solid

80°

 

SF

 

Stage

A2YA-

Cone

 

 

 

 

 

7916

 

 

 

 

 

 

B2VA

 

 

 

 

 

 

8216

Type B

 

941

AFG

15 Sec.

Two-

-

Solid

80°

 

SF

15 Sec.

Stage

BY2A

Cone

 

 

 

 

 

8916

 

 

 

 

 

 

 

 

 

*To provide the proper firing rate for each model heater, see SPECIFICATIONS: there are burner models for each heater model in table 2.

+All oil burners are UL defined as having "interrupted ignition" . . . meaning the ignition is on during the flame establishing period only. Ignition is off when the burner is off. Standard safety timing is 15 seconds.

For installations where gravity feed of fuel oil from the storage tank to the heater is practical, an oil burner with a single-stage oil pump can be used. The 940 series of burners have single-stage pumps which are shipped for installation of a supply line to the tank only. A return line back to the storage tank can be installed, if required, by making a small modification to the pump, see the oil burner installation manual.

For installations where gravity feed cannot be employed, (the storage tank is located significantly below, or remote from, the heater) an oil burner with a two-stage oil pump should be used. The 941 series of burners have two-stage pumps which are shipped for installation of a supply and return line to the tank. However, in situations where the return line is not required (low lift installations), the pump may be modified to operate without the line, see the oil burner installation manual.

IMPORTANT

The oil-fired water heater shipment consists of two packages, heater and oil burner. Check to be certain the model number on the heater and oil burner packages match. To assure matching equipment, see preceding information.

 

 

GPO 86

GPO86

GPO 84

GPO 75

GPO 75

GPO 69

Model Heater

199

245

315/315A

385/385A

455/455A

700/700/A

Min.

State

 

 

 

 

 

 

Firing

Burner

1.42

1.75

2.25

2.75

3.25

5.0

Rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In

Non

 

 

 

 

 

 

GPH

State

1.1

1.5

2.0

2.5

3.0

4.5

 

Burner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAFETY

DANGER

BE SURE TO TURN OFF POWER WHEN WORKING ON OR NEAR THE ELECTRICAL SYSTEM OF THE HEATER. NEVER TOUCH ELECTRICAL COMPONENTS WITH WET HANDS OR WHEN STANDING IN WATER. WHEN REPLACING FUSES ALWAYS USE THE CORRECT SIZE FUSE FOR CIRCUIT.

If it is necessary to reset the safety primary control, depress red button one time only. If burner does not operate after depressing red button one time, call serviceman.

INSTALLATION

REQUIRED ABILITY

INSTALLATION OF SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENCED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING , OIL BURNER AND ELECTRICAL WORK REQUIRED.

GENERAL

The installer should be guided by these instructions, local codes and the following publications.

Standards for the Installation of Oil Burning Equipment, NFPA Standard No. 31, Available from National Fire Protection Association, Batterymarch Park, MA 02269.

Code for the Installation of Heat Producing Appliances, Available from American Insurance Association, 85 John Street, New York, NY 10038.

The National Electrical Code, ANSI/NFPA No. 70-1996. Availability same as NFPA Standard No. 31-1997.

In Canada - CSA Standard No. B139, Installation Code for Oil Burning Equipment.

When other than a State burner is used, this instruction manual can be used as a general guide. The burner manufacturer's instructions will have to be consulted on specific questions of wiring, air adjustment, etc.

Do not test the burner or control system before the heater is filled with water. Follow the START-UP procedure in this manual.

UNCRATING

Uncrate the heater by removing the outside mat and top locator. The shipping pallet must be removed from the unit. It may be possible to simply unbolt the base from the pallet and, with the help of two or more persons, work the unit off the pallet. Some units will be too heavy and will require the use of jacks or lifting equipment. Safely remove the pallet and move the unit into position. Be Careful When Moving This Heater. It will tip over easily.

LEVELLING

Install the heater plumb to the ground. If it is necessary to adjust the heater, use metal shims under the channel type skid base.

LOCATION

The water heater should not be installed where the combustion air is contaminated, see COMBUSTION AND VENTILATING AIR. Temperature in the location must be above 32°F (0°C) and free of combustible dusts and flammable gases or vapors.

For the best installations, the water heater should be located:

1.On a level surface.

Shim the channel type skid base as necessary If leveling is required.

2.Near a floor drain.

The heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure.

When such locations cannot be avoided, a suitable drain pan should be installed under the heater.

The pan should be at least two inches deep, have a minimum length and width of at least two inches greater than the diameter of the heater and should be piped to an adequate drain. The pan must not restrict combustion air flow.

4

Image 4
Contents Place These Instructions Adjacent to Heater Lindahl Parkway Ashland City, TNNotify Owner to Keep for Future Reference Features and Specifications Nominal Model DimensionsRecovery CAPACITIES, based on 80% efficiency GPOApprovals Table of ContentsIdentification Safety InstallationProper Installation on Combustible Flooring ClearancesCombustion and Ventilation AIR Chemical Vapor CorrosionVent Connector and Draft Regulator Proper Vent Connector InstallationFlue GAS Venting ChimneyDrain Valve and Access Panels Water PipingClosed Water System Fuel SystemsBurner Installation Typical Heater Installation FigureGravity FEED, Supply Line ONLY, Installation System TypesOIL Pump & Nozzle Specifications Assembly of the OIL Burner to the HeaterFuel Pump BurnerWater Temperature Control High Limit Switch E.C.OOperation FillingMaintenance Burner Certificate Combustion TestDraining Relief ValvesLime Scale Removal Sediment RemovalFlo-jug Method of Deliming Circulating Pump Soot RemovalVent System Anode ROD InspectionInstallation Diagrams Install in Accordance with Local CodesInset B Inset aSingle Temperature or Booster Inset B Install in Accordance with Local Codes Inset a Check List and Service Information Electrical Wiring ReplacementNot Enough or no HOT Water Manifold KIT Commercial OIL Fired Water HeatersBurner STARTS-WONT Operate Water is TOO HOTWater Heater Makes Sounds Water Leakage is SuspectedCombustion Test Specifications Normal START, but Locks OUT on SafetySafety Primary Control ProcedureTroubleshooting Item no Cleanout Assembly Lindahl Parkway, Ashland City, TN Phone 800-821-2017 FaxDescription