DDAA1000/SRM User Guide

6.The unit will now ask for the number of ADs (analog inputs) on each Remote. ‘#ADsSlv0’. The question is repeated for each Remote unit. ‘#ADsSlv1’.etc. Any units that have no (zero) active analog channels must be put after any remotes that do have analog channels. Enter the number of analogs channels for each Remote.

7.The display now asks for the number of analog inputs at the Master unit. ‘0-8 MstrAD’ The number of master analog inputs must equal the total number of analog inputs entered for each remote in step 6 above.

8.The display now asks for the number of analog outputs on each Remote ‘#DAsSlv0’. The question is repeated for each Remote unit. ‘#DAsSlv1’ etc. These values must be the same as the numbers entered in step 6 above.

9.The display now asks for number of analog outputs at the Master unit. ‘0-8 MstrDA’ This number is the same as entered in step 7 above.

10.The display now prints out a status of your entries. Write these down and keep for use when you call Data-Linc Group technical support. Note the first line may say Master or Slave/Remote. Review the settings. The EEprom has been changed. The print out has been read from the changed EEprom. The data shown is from a master unit. The Remote display is similar.

Mstr EEP:

B# AD DA Slvs

5 3 3 3

ADs/Slave 1 2 0 0 0 0 0 0

DAs/Slave 1 2 0 0 0 0 0 0

Check

11.Remove DC power, remove the serial cable, replace the jumpers on P1 and P2 back to the RUN/NORMAL position. Repeat the procedure for all of the units that you are reconfiguring.

12.After all units are changed, bench test the system. The most likely problem is the baud rate setting does not match the setting in the radio modules.

20

DATA-LINC GROUP

PN 161-09981-002C

rev 8/04

Image 22
Contents DDAA1000/SRM FCC Notification Product User GuideTable of Contents DATA-LINC Group Introduction DDAA1000 and DD1000Antenna Connectoin Type Power ConnectorTeminal Block Discrete Operation ConnectionsPoint-to-Point Discrete Operation Master RemotePoint-to-Multipoint Discrete Operation MasterPoint-to-Point Analog System Supply loop powerAnalog Operation Needed. The DDAA1000 unites do notConnection of a flow meter to the DDAA1000/SRM unit Master or RemoteFactory Configuration Process Point-to-Multipoint Analog SystemPoint-to-Multipoint Analog Operation Point-to-Multipoint Analog Example RemoteChanging System or Radio Configurations Layout DrawingTechnical Specifications Troubleshooting Technical Support Product WarrantyReturn Material Authorization Contact InformationAppendix a TOPDDAA1000 DD1000 Configuration Appendix BDATA-LINC Group Ddaa Eeprom MENU** *SET Caplck DATA-LINC Group Appendix C Radio Configuration Terminal SettingsMain Menu Point-to-Point Remote Main Menu Option 0 Set Operation ModePoint-to-point Master Point-to-Multi-Point MasterPoint-to-Point Repeater Point-to-Point Remote/Master SwitchableDDAA1000/SRM User Guide Point-to-Point Remote/Repeater Point-to-Multi-Point RepeaterAvailable data word length and parity selections Main Menu Option 1 Set Baud RateModBus RTU Main Menu Option 2 Edit Call Book Call Book MenuEdit Call Book in Multi-Point Systems Entry Number Repeater 000-0000FreqKey Main Menu Option 3 Edit Radio Transmission CharacteristicsMax Packet Size and 2 Min Packet Size Selections DDAA1000/SRM User Guide Minimum Packet Size Settings bytes Maximum Packet Size Settings where RF Data Rate=3Xmit Rate RF Data RateRemote Security DDAA1000/SRM User Guide RF Xmit PowerPower Transmit Settings RTS to CTSHigh Noise DDAA1000/SRM User Guide Lowpower ModeMCU speed Average Noise Level Average Signal LevelMain Menu Option 4 Show Radio Statistics Overall Rcv Rate %DDAA1000/SRM User Guide Number of Disconnects Radio TemperatureMulti-Point Operation Main Menu Option 5 Edit Multi-Point Parameters Multi-Point ParametersSubNet ID DiagnosticsRemote/Repeater Radio IDMain Menu Option 8 Password Changing a Password Disabling PasswordDDAA1000/SRM and DD1000/SRM Placement Locations