Omron DDAA1000/SRM manual Main Menu Option 4 Show Radio Statistics, Average Noise Level

Page 35

DDAA1000/SRM User Guide

Main Menu Option (4): Show Radio Statistics

Option (4) in the main menu allows the user to view data transmission statistics, which have been gathered by the Transceiver during the most recent session. Statistics are gathered during each data link and are reset when the next link begins. Ideally, noise levels should be below 30, and the difference between the average signal level and average noise level should be 15 or more. High noise levels tend to indicate other sources of RF interference, while low signal levels indicate a weak link. The “Local” stats are the statistics that are being gathered by the modem you are connected to while “Remote1, Remote2, and Remote3” are the stats of the repeater(s) that the modem you are attached to is using to get back to the master modem. The following sections provide information useful to the process of troubleshooting and improving radio links.

Average Noise Level

The average noise level indicates the level of background noise and interference at this modem and at each of the modems used as repeaters in the link. The number is an average of the noise levels measured at each frequency in the modems’ frequency hop table. The individual measurement values at each frequency hop channel are shown in the frequency table. The frequency table is accessed by pressing the ENTER key on the computer when the radio statistics menu is displayed. Average noise levels will typically fall in the range of 15 to 30. Average noise levels significantly higher than this are an indication of a high level of interference that may degrade the performance of the link. High noise levels can often be improved with bandpass filters, antenna placement or antenna polarization. Please contact Data-Linc Group for more information.

Average Signal Level

The average signal level indicates the level of received signal at this modem and at each of the modems used as repeaters in the link. For each of these, the signal source is the modem that transmits to it. The number is an average of the received signal levels measured at each frequency in the modem’s frequency hop table. The individual measurement values at each frequency hop channel are shown in the frequency table. The frequency table is accessed by pressing the ENTER key on the computer when the radio statistics menu is displayed.

For a reliable link, the average signal level should be at least 30 higher than the average noise level reading. The table below provides an approximate conversion of average signal level values into the more common dBm (decibel milliwatts). Low Average Signal Levels can often be corrected with higher gain antennas, antenna placement, and use of repeaters. Contact Data-Linc Group for more information.

Average Signal Level

41

49

60

66

85

 

 

 

 

 

 

Level in dBm

-110

-100

-60

-80

-70

 

 

 

 

 

 

Overall Rcv Rate (%)

The Overall Rcv Rate measures the percentage of data packets that were successfully transmitted from the master to the remote on the first attempt without requiring retransmission. A number of 75 or higher indicates a robust link that will provide very good performance even at high data transmission rates. A number of 25 or lower indicates a weak or marginal link that will provide lower data throughput. An Overall Rcv Rate of 100% will provide approximately 100 Kbaud of bandwidth with an RF data rate of 3 (Radio Transmission Parameters Menu) and approximately 150 Kbaud of bandwidth with an RF Data Rate of 2. These numbers are reduced approximately 50% if there are one or more repeaters in the network.

PN 161-09981-002C

rev 8/04

DATA-LINC GROUP

33

Image 35
Contents DDAA1000/SRM Product User Guide FCC NotificationTable of Contents DATA-LINC Group DDAA1000 and DD1000 IntroductionTeminal Block Power ConnectorAntenna Connectoin Type Connections Discrete OperationMaster Remote Point-to-Point Discrete OperationMaster Point-to-Multipoint Discrete OperationNeeded. The DDAA1000 unites do not Supply loop powerAnalog Operation Point-to-Point Analog SystemMaster or Remote Connection of a flow meter to the DDAA1000/SRM unitPoint-to-Multipoint Analog System Factory Configuration ProcessPoint-to-Multipoint Analog Example Remote Point-to-Multipoint Analog OperationLayout Drawing Changing System or Radio ConfigurationsTechnical Specifications Troubleshooting Contact Information Product WarrantyReturn Material Authorization Technical SupportTOP Appendix aAppendix B DDAA1000 DD1000 ConfigurationDATA-LINC Group Ddaa Eeprom MENU** *SET Caplck DATA-LINC Group Terminal Settings Appendix C Radio ConfigurationMain Menu Point-to-Multi-Point Master Main Menu Option 0 Set Operation ModePoint-to-point Master Point-to-Point RemotePoint-to-Multi-Point Repeater Point-to-Point Remote/Master SwitchableDDAA1000/SRM User Guide Point-to-Point Remote/Repeater Point-to-Point RepeaterModBus RTU Main Menu Option 1 Set Baud RateAvailable data word length and parity selections Call Book Menu Main Menu Option 2 Edit Call BookEntry Number Repeater 000-0000 Edit Call Book in Multi-Point SystemsMax Packet Size and 2 Min Packet Size Selections Main Menu Option 3 Edit Radio Transmission CharacteristicsFreqKey Maximum Packet Size Settings where RF Data Rate=3 DDAA1000/SRM User Guide Minimum Packet Size Settings bytesRF Data Rate Xmit RateRTS to CTS DDAA1000/SRM User Guide RF Xmit PowerPower Transmit Settings Remote SecurityMCU speed DDAA1000/SRM User Guide Lowpower ModeHigh Noise Overall Rcv Rate % Average Signal LevelMain Menu Option 4 Show Radio Statistics Average Noise LevelMulti-Point Operation Radio TemperatureDDAA1000/SRM User Guide Number of Disconnects Multi-Point Parameters Main Menu Option 5 Edit Multi-Point ParametersRadio ID DiagnosticsRemote/Repeater SubNet IDMain Menu Option 8 Password Disabling Password Changing a PasswordDDAA1000/SRM and DD1000/SRM Placement Locations