Enviro EG 40 B owner manual GAS Line Connection, Never USE AN Open Flame for Leak Testing

Page 12

GAS LINE CONNECTION

ORIFICE SIZES, PRESSURE AND BTU’S

 

NATURAL GAS

PROPANE GAS

FRONT BURNER

#48 (1.93mm)

#55 (1.32mm)

REAR BURNER

#41 (2.49 mm)

#54 (1.40 mm)

Manifold pressure.

3.8” wc (.95 kPa)

11” wc (2.74 kPa)

Min. Manifold pressure.

1.1” wc (.27 kPa)

2.7” wc (.67 kPa)

Supply Pressure.

7.0” wc (1.74 kPa)

12” wc (2.98 kPa)

Min. Supply pressure.

5” wc (1.25 kPa)

11.5” wc (2.86 kPa)

Max. BTUH Input.

38,000

Btu/h (11.1 kW)

38,000

Btu/h (11.1 kW)

Min. BTUH Input.

20,000

Btu/h (5.9 kW)

20,000

Btu/h (5.9 kW)

Output fan off

27,800

Btu/h (8.14 kW)

28,900

Btu/h (8.46 kW)

Output fan on

29,400

Btu/h (8.6 kW)

30,300

Btu/h (8.86 kW)

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

NOTE: The gas line connection may be made using 3/8" rigid tubing or an approved flex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the CAN/CGA- B149 (1 or 2) Installation Code. For USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI.Z223.1.

UPON CONNECTION MARK APPROPRIATE FUEL TYPE ON WARNOCK HERSEY RATING LABEL LOCATED ON THE INSIDE OF THE RIGHT HAND SIDE PANEL.

Manifold Pressure Tap. Inlet Pressure Tap.

Milli volt Terminals

Pilot Adjustment screw.

"HI-LOW" Burner Gas Knob. Pilot "ON-OFF" Gas Knob.

The appliance and its individual manual shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds 1/2 PSIG (3.45 kPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

When using copper or flex connectors use only fittings approved for gas connections.

TO TEST

The pressure taps are located in the top right corner on the valve face (right - inlet, left - manifold pressure).

Turn set screw counter clockwise to loosen, 2 turns.

Place 5/16" hose over pressure tap system.

When finished, release pressure, remove hose

& tighten set screw.

Always check for gas leaks with a soap and water solution after completing the required pressure test.

NEVER USE AN OPEN FLAME FOR LEAK TESTING

12

Image 12
Contents For Your Safety What to do if YOU Smell GASS H E R W O O D I N D U S T R I E S L T D Safety Precautions For Your SafetyGeneral Table of Contents Assembly InstructionsCode Approvals Deciding Where to Locate Your Stove DimensionsClearances Vent Terminal Clearances Flue GAS Spill Switch VentingUsing AN Existing Chimney Manufacturers General Venting GuidelinesInstallation of LOG SET and Embers Installing the Glowing EmbersFor Your Safety Read Before Operating Operating InstructionsLighting Instructions What to do if YOU Smell GASMaintenance and Technical Cleaning of GlassTo Replace Door and Glass Assembly For Cleaning the Inside of the FireboxTrouble Shooting Problem Possible Cause SolutionNever USE AN Open Flame for Leak Testing GAS Line ConnectionOrifice SIZES, Pressure and BTU’S Installing Remote Thermostat or Wall Switch ElectricalParts and Accessories Service Parts available from your local Envirogas DealerFuel Type Conversion Warranty To a Maximum of Seven YearsTo the Dealer To the DistributorParts List EG 40 Door and Burner Assemblies EC-031 GasketExploded EG 40 Freestanding Installation Data Sheet Model EG