Installation
9. Push the stove straight |
|
| |||
back, leaving a minimum |
|
| |||
of 100mm (4”) clearance |
|
| |||
from the back of the |
|
| |||
stove to the wall. Seal the |
|
| |||
vent pipe to the thimble |
| Exhaust | |||
with | high | temperature |
| ||
|
| ||||
silicone. |
|
|
| 80mm (3") or 100mm (4") | |
10. The pipe must extend at |
| Vent Pipe | |||
| Wall Thimble | ||||
least 30 cm (12”) away |
| ||||
from | the | building. | If |
| 45o Elbow with Screen |
necessary, bring another | Fresh Air Intake | ||||
length of pipe to the | or Termination Cap | ||||
|
| ||||
outside of | the home |
|
| ||
to connect | to the | first |
| High Temperature RTV | |
section. Do not forget to |
| ||||
| Silicone Required | ||||
place | high | temperature | Figure 9: Straight through wall Installation. | ||
silicone around the pipe |
that passes through the thimble.
11.Install a vertical pipe, or if all requirements for direct venting are met, install vent termination. The stainless steel cap termination manufactured by the vent manufacturer is recommended. However, when the vent terminates several feet above ground level and there are no trees, plants, etc. within several feet, a 45° elbow can be used as termination. The elbow must be turned down to prevent rain from entering.
NOTE:
•Some horizontal through wall installations may require a “T” and 91 to 152 cm (3 to 5 feet) of vertical pipe outside the building to help naturally draft in the unit.
•This may be required if a proper burn cannot be maintained, after the stove has been tested and the airflow set.
•This is due to the back pressure in the exhaust caused by airflow around the structure.
•All sections of pipe must have three (3) screws evenly spaced and all horizontal and vertical vent sections located within the house must have a bead of high temperature silicone installed on the male end of the pipe before installation to create a gas tight seal.
Wall framing
Horizontal frame for thimble
Vent pipe
Termination cap
Wall thimble
������ �������
Figure 10: Straight through Wall Installation - Side View.
12