Desa GMP26T, GMP20BT, GMP16T, GMP30BT Determining FRESH-AIR Flow for Heater Location

Page 6

AIR FOR COMBUSTION

AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a con- fined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless pas- sageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (vol- ume of space)

If additional ventilation to adjoining room is sup- plied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_______ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

______________ Btu/Hr

Gas water heater*

______________ Btu/Hr

Gas furnace

______________ Btu/Hr

Vented gas heater

______________ Btu/Hr

Gas fireplace logs

______________ Btu/Hr

Other gas appliances* + __________

Btu/Hr

Total

= __________

Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

 

Gas water heater

 

40,000

 

_________ Btu/Hr

Vent-free heater

+

20,000

_________ Btu/Hr

Total

=

60,000

_________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

______________ Btu/Hr (maximum the space

can support)

______________ Btu/Hr (actual amount of

Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used) The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must pro- vide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an ad- joining room. If the extra space provides an un- confined space, remove door to adjoining room or add ventilation grills between rooms. See Ven- tilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/ Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section

5.3or applicable local codes.

6

www.desatech.com

113048-01C

Image 6
Contents What to do if YOU Smell GAS Table of Contents Safety Information Safety Information Product Identification Local CodesUnusually Tight Construction AIR for Combustion VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceCheck GAS Type InstallationVentilation AIR Ventilation Air From Inside BuildingInstallation Items Locating HeaterInstalling Heater to Wall 20,000 Btu/Hr Models Attaching To Wall Anchor MethodPlacing Heater On Mounting Bracket Mounting Heater to Floor with Optional Floor KIT Installing Bottom Mounting ScrewsMounting Base Feet to Floor Where required by local code Mounting Base Feet to HeaterConnecting to GAS Supply Typical Inlet Pipe DiametersTest Pressures In Excess Of 1/2 Psig 3.5 kPa Pressure Testing GAS Supply Piping SystemChecking GAS Connections Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaOperating Heater For Your Safety Read Before LightingPressure Testing Heater GAS Connections Manual Control Models Lighting InstructionsManual Lighting Procedure To Select Heating Level for Infrared HeatersTo Turn OFF GAS To Appliance Thermostat Controlled Models Lighting Instructions Pilot Flame Pattern Inspecting HeaterThermostat Control Operation Control Knob GMP16TInpecting Heater Burner Flame Pattern for Blue Flame HeatersBurner Flame Pattern for Infrared Heaters Burner Pilot AIR Inlet Cleaning MaintenanceODS/PILOT and Burner CabinetTroubleshooting Observed Problem Possible Cause RemedyPressed See Cleaning and Mainte Gas leak. See Warning Statement aboveSpecifications GMP30BT GMP20BTGMP16 GMP26 GMP16T GMP26T Service Publications Replacement Parts Service HintsTechnical Service AccessoriesIllustrated Parts Breakdown Models GMP16, GMP26, GMP16T, and GMP26TParts List Parts AVAILABLE-NOT ShownIllustrated Parts Breakdown and Parts List Models GMP16 and GMP26ODS/Pilot Burner Assembly GMP16T Models GMP16T and GMP26TModels GMP20BT and GMP30BT Parts Available not Shown Warranty Information Keep this WarrantyLimited Warranty VENT-FREE Residential GAS Heaters