INSTALLATION
Continued
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from go- ing into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown in Figure 15, page 12. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sedi- ment trap traps moisture and contaminants. This keeps them from going into heater controls. If sedi- ment trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip- ing and connections, internal and external to unit, for leaks after installing or servicing. Cor- rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak de- tection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater.SeeguidelinesunderCon- necting to Gas Supply, page 12.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in ex- cess of 1/2 psig will damage heater regulator.
2.Cap off open end of gas pipe where equip- ment shutoff valve was connected.
3.Pressurize supply piping system by opening propane/LP supply tank valve or using com- pressed air.
4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
5.Correct all leaks at once.
6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1.Close equipment shutoff valve (see Figure 16).
2.Pressurize supply piping system by opening propane/LP supply tank valve or using com- pressed air.
3.Check all joints from propane/LP supply tank to equipment shutoff valve (see Figure 17). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
4.Correct all leaks at once.
Equipment | Open |
Shutoff |
|
Valve |
|
| Closed |
Figure 16 - Equipment Shutoff Valve
Thermostat Gas Valve
Propane/LP |
Supply Tank |
Equipment Shutoff Valve |
Figure 17 - Checking Gas Joints for
Propane/LP Gas
www.desatech.com | 13 |