Desa CTR22PR, CTR25NR, VTN25R, VTP22R Ventilation AIR, Ventilation Air From Inside Building

Page 6

AIR FOR COMBUSTION

AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr (kw) the space can support.

__________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr (kw) of all fuel burning appli- ances in the space.

Vent-free heater

________ Btu/Hr (kw)

Gas water heater*

________ Btu/Hr (kw)

Gas furnace

________ Btu/Hr (kw)

Vented gas heater

________ Btu/Hr (kw)

Gas fireplace logs

________ Btu/Hr (kw)

Other gas appliances* +________ Btu/Hr (kw)

Total

=________ Btu/Hr (kw)

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000 (11.7)

 

Gas water heater

Btu/Hr (kw)

Vent-free heater

+ 22,000 (6.4)

Btu/Hr (kw)

Total

= 62,000 (18.2)

Btu/Hr (kw)

C.Install a lower Btu/Hr (kw) heater, if lower Btu/Hr (kw) size makes room unconfined.

If the actual Btu/Hr (kw) used is less than the maxi- mum Btu/Hr (kw) the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING:Iftheareainwhich the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" (30.5 cm) of the ceiling and one within 12" (30.5 cm) of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr (kw) the space can support with the actual amount of Btu/Hr (kw) used.

___________Btu/Hr (kw) (maximum the space can support)

___________Btu/Hr (kw) (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (15 kw) (maximum the space can support)

62,000 Btu/Hr (18.2 kw) (actual amount of Btu/Hr used)

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12" (30,48 cm)

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the above example is a confined space because the actual Btu/Hr (kw) used is more than the maximum Btu/Hr (kw) the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

12" (30,48 cm)

Figure 2 - Ventilation Air from Inside

Building

6

www.desatech.com

113261-01A

Image 6
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product Identification Product FeaturesLocal Codes UnpackingAIR for Combustion Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation AIR Ventilation Air From Inside BuildingCheck GAS Type InstallationInstallation Items Locating HeaterInstalling Remote Control Receiver Receiver AA Batteries Battery CoverReceiver Wire Bushing Connector Bracket Installing Batteries Into Remote Replacing Battery in IgnitorMounting Heater Base to Floor Where required by local codes Connecting to GAS Supply Propane/LP External Supply Tank Regulator Vent Pointing DownChecking GAS Connections Make sure control knob of heater is in the OFF position Pressure Testing Heater GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa ClosedLighting Instructions For Your Safety Read Before LightingOperating Heater Electronic Ignitor Auxiliary Pilot Knob ButtonTo Turn OFF GAS To Appliance Manual Lighting ProcedureHAND-HELD Remote Control Operation Thermostat OperationPilot Flame Pattern Changing Set TemperatureInspecting Heater Burner Flame PatternCleaning Maintenance Service HintsTechnical Service Troubleshooting Observed Problem Possible Cause RemedyAssembly Goes out when control knob isProblem could be caused by Delayed ignition of burners Manifold pressure is too lowGas leak. See Warning Illustrated Parts Breakdown Models CTR25NR, VTN25R, CTR22PR and VTP22RParts List Specifications AccessoriesService Publications Replacement Parts Parts Central FBDPatent Pending QUÉ Hacer SI Percibe Olor a GAS Modelos CTR25NR, CTR22PR, VTN25R Y VTP22RTabla DE Contenido Información DE SeguridadContinuación Desempaque Códigos LocalesIdentificación DEL Producto Características DEL ProductoConstrucción inusualmente sellada Aire Para Combustión VentilaciónCómo Procurar LA Ventilación Adecuada Espacio confinado o no confinadoAire Para Ventilación Aire del interior de la construcción para ventilaciónArtículos DE Instalación InstalaciónVerifique EL Tipo DE GAS Ubicación DEL CalentadorCubierta de la batería Instalación DEL Receptor DE Control RemotoReceptor Baterías AA Soporte del Conector Buje Del alambre ReceptorReemplazo DE LA Batería DEL Encendedor Instalación DE LAS Baterías EN EL Control RemotoConexión AL Suministro DE GAS PRECAUCIÓNEnelcasodepro- pano o gas LP, nunca conecte el caRevisión DE LAS Conexiones DE GAS Distribuidor. Consulte Accesorios, páginaRepare todas las fugas inmediatamente Vuelva a colocar el panel anterior Cierre la válvula de cierre del equipo consulte la figuraAbra la válvula de cierre del equipo consulte la figura Válvula deInstrucciones DE Encendido Funcionamiento DEL CalentadorPara SU SEGURIDAD, LEA Esto Antes DE Encenderlo Botón de encendido Perilla Auxiliar Del Piloto ElectrónicoFuncionamiento DEL Control Remoto Portátil Funcionamiento DEL TermostatoProcedimiento DE Encendido Manual Función ManualPatrón DE LA Llama DEL Piloto Inspección DEL CalentadorFunción DEL Termostato Patrón DE LA Llama DELLimpieza Y Mantenimiento Servicio TécnicoSolución DE Problemas Problema Observado Causa Posible RemedioProblema Observado Causa Posible RemedioImportante anterior Clasificación Ilustrada DE Piezas Modelos CTR25NR, VTN25R, CTR22PR Y VTP22RLista DE Piezas Publicaciones Para Servicio EspecificacionesAccesorios Válvula DE Cierre DEL Equipo GA5010Piezas Bajo Garantía Piezas DE RepuestoCentral DE Piezas Piezas SIN GarantíaPatente en trámite 113261-01 Rev. a 07/04

CTR25NR, CTR22PR, VTN25R, VTP22R specifications

Desa VTN25R, VTP22R, CTR22PR, and CTR25NR are renowned models in the landscape of power generation and energy efficiency solutions. These products cater to varying needs, providing reliable performance for both residential and commercial applications.

The Desa VTN25R is distinguished by its robust design and high fuel efficiency, making it an ideal choice for users looking to balance power output with energy conservation. This model features a state-of-the-art EcoThrottle technology, which adjusts engine speed according to load, significantly reducing fuel consumption and noise levels. With a maximum output of 2500 watts, the VTN25R ensures that users can power a variety of appliances and equipment without concern for overloading.

Next in line, the Desa VTP22R model stands out for its versatility and compact form factor. Weighing in at just 45 pounds, this generator is incredibly portable, making it an excellent choice for outdoor enthusiasts and those needing backup power in emergency situations. It also incorporates a user-friendly digital display, allowing users to monitor fuel levels, output wattage, and engine performance at a glance. Its quiet operation and low emissions are additional highlights that make the VTP22R an environmentally conscious option.

Turning to the CTR22PR, this generator is designed with advanced inverter technology, supplying clean and stable power suitable for sensitive electronics. Its dual fuel capability allows it to run on both gasoline and propane, offering flexibility and convenience for users in diverse situations. The ergonomic handle and lightweight design facilitate easy transport, while the safety features, including overload protection and automatic shutoff, ensure peace of mind during operation.

Lastly, the CTR25NR model boasts higher wattage capacity coupled with enhanced durability. This unit features heavy-duty components, ensuring it can withstand rigorous usage over time. With features like an LED indicators panel and advanced cooling systems, the CTR25NR promises extended run times and operational efficiency. Users appreciate its ease of maintenance and serviceability, which translate into a longer lifespan.

In summary, the Desa VTN25R, VTP22R, CTR22PR, and CTR25NR generators offer a range of features and technologies tailored to meet the needs of different users. Whether it’s fuel efficiency, portability, clean power supply, or heavy-duty performance, these models demonstrate a commitment to reliability and innovation in the power generation market.