American Water Heater 319407-002 installation instructions Temperature and Pressure Relief Valve

Page 14

Temperature and Pressure Relief Valve

WARNING

Explosion Hazard

If the temperature and pressure relief valve is dripping or leaking, have a qualified person replace it.

Examples of a qualified person include: licensed plumbers, authorized gas company personnel, and authorized service personnel.

Do not plug valve. Do not remove valve.

Failure to follow these instructions can result in death, or explosion.

Figure 18

Temperature and Pressure

Relief Valve Installation

Temperature and

Pressure Relief Valve

Discharge Pipe

(Do not cap or plug.)

Drain Line

3/4” ID minimum

6" Maximum

Air Gap

Floor

Drain

Metal Drain Pan

For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE” (see Figure 18). This valve must be design certified by

a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meeting the requirements for Relief Valves and Automatic Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22. The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure developing

in the water heater. The valve’s relief pressure must not exceed the working pressure of the water heater as stated on the data plate.

14

IMPORTANT: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.

The Temperature & Pressure Relief Valve:

Must not be in contact with any electrical part.

Must be connected to an adequate discharge line.

Must not be rated higher than the working pressure shown on the data plate of the water heater.

The Discharge Line:

Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line.

Must not be capped, blocked, plugged or contain any valve between the relief valve and the end of the dis- charge line.

Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.

Must be capable of withstanding 250°F (121°C) without distortion.

Must be installed to allow complete drainage of both the valve and discharge line.

T&P Relief Valve and Pipe Insulation (Some Models)

1.Locate the temperature and pressure relief valve on the water heater (also known as a T&P relief valve). See Figure 18.

2.Locate the slit running the length of the T&P relief valve insulation.

3.Spread the slit open and fit the insulation over the T&P relief valve. See Figure 19. Apply gentle pressure to the insulation to ensure that it is fully seated on the T&P Relief Valve. Once seated, secure the insulation with duct tape, electrical tape, or equivalent. IMPORTANT: The insulation or tape should not block or cover the T&P relief valve drain opening. Also,

the insulation or tape should not block or hinder access to the manual relief lever (Figure 19). Ensure that a discharge pipe is installed into the T&P valve discharge opening per the instructions in this manual.

4.Locate the hot water (outlet) & cold water (inlet) pipes to the water heater.

5.Locate the slit running the length of a section of pipe insulation.

6.Spread the slit open and slip the insulation over the cold water (inlet) pipe. Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe. Also, ensure that the base of the insulation is flush with the water heater. Once seated, secure the insulation with duct tape, electrical tape, or equivalent.

7.Repeat steps 5 and 6 for the hot water (outlet) pipe.

8.Add additional sections of pipe insulation as needed.

Figure 19

T&P Relief Valve Insulation

T&P Relief Valve Insulation

Manual Relief Lever

T&P Relief Valve

T&P Relief Valve

Drain Line

Image 14
Contents What to do if YOU Smell GAS Flammable Vapor Ignition ResistantWater Heater Safety Consumer Responsibilities Important Information About This Water HeaterConsumer Information Unpacking the Water HeaterLocation Requirements Site LocationClearances and Accessibility Inspection and serviceGas Pressure Gas SupplyGas Requirements Combustion Air Supply and Ventilation All Air from Inside the Building Unconfined SpaceConfined Space All Air from Outdoors Louvers and GrillesVent Pipe System Draft Hood InstallationVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingClosed System/Thermal Expansion Temperature and Pressure Relief Valve Relief Valve and Pipe Insulation Some ModelsCombination Space Heating/Potable Water System Solar InstallationSpecial Applications Installation Checklist Lighting Instructions Explosion HazardChecking the Draft Water Temperature StackingG. Bottled Propane Models Burner FlamesWater Temperature Regulation 154 Instantaneous SecondWiring Diagram Electrical ConnectionsOperating Modes and Settings Operating the Temperature Control SystemWater Temperature Adjustment Status Light CodeOperational Conditions Routine Preventative Maintenance Draining and FlushingRemoving the Manifold Assembly Replacement PartsRemoving the Burner from the Manifold Assembly Replacing the Pilot/Igniter Flame Sensor AssemblyFilter Installation and Cleaning External Inspection & Cleaning of the Flame-trap Cleaning the Combustion Chamber and Flame-trapReplacing the Manifold Assembly Igniter SystemFlame Guard Safety System Operational Checklist Removing and Replacing the Gas Control Valve/ThermostatBurner Flame Yellow Status Light Code Troubleshooting Table Status Light Code Troubleshooting Table Sequence of Operation Chart Repair Parts Illustration Repair Parts ListListed Parts Kits and Illustrations