American Water Heater Residential Gas Water Heater with the Flame Guard Safety System, 319407-002

Page 31

STATUS LIGHT CODE TROUBLESHOOTING TABLE

Status Light Code

LED FLASH

CONTROL STATUS

 

CORRECTIVE ACTION

SEQUENCE

 

 

 

Six-Two Flash, three second pause

Soft Lockout - Recycle Limit - Flame Lost -

Turn the power switch on the gas control valve to the “OFF” position and unplug the power cord from the

 

END Switch Fails

power outlet.

 

1.

Check all wiring connections to insure all harness and wire connections are seated firmly and provide

 

 

 

 

 

proper electrical contact. If no connection problems are found replace the damper. Firmly seat any

 

 

 

loose connections found. If any connections are found to be damaged consult the replacement parts

 

 

 

list on pages 31-32 for the appropriate replacement. After any connection problems are fixed restart

 

 

 

the water heater by following the lighting instructions on page 16. If the problem persists replace the

 

 

 

damper.

Six-Three Flash, three second pause

Soft Lockout - Recycle Limit - Flame Lost

Turn the power switch on the gas control valve to the “OFF” position and unplug the power cord from the

 

 

power outlet.

 

 

1.

Check the incoming gas line pressure to ensure adequate supply to the water heater. If incoming

 

 

 

gas supply pressure is adequate proceed to step 2.

 

 

2.

Check all wiring connections and insure all harness and wires connections are seated firmly and

 

 

 

provide proper electrical contact. If no connection problems are found proceed to step 3. Firmly

 

 

 

seat any loose connections found. If any connections are found to be damaged consult the

 

 

 

replacement parts list for the appropriate replacement. After any connection problems are fixed

 

 

 

restart the water heater by following the lighting instructions on page 16. If the problem persists

 

 

 

proceed to step 3.

 

 

3.

Check condition of the base ring filter and flame arrestor. If they are clogged follow the instruc-

 

 

 

tions for cleaning on page #. If parts are not clogged proceed to step 4. After cleaning follow

 

 

 

instructions for lighting on page 16. If problem persists proceed to step 4.

 

 

4.

Follow the instructions on page # to remove the burner assembly. Once the burner assembly has

 

 

 

been removed inspect the manifold tube and burner, see figure 29 , for any obstructions. If any

 

 

 

clogs or obstructions are present clear them. Inspect the electrode/flame sense rod, see figure

 

 

 

# , for corrosion buildup, degradation, or damage. If there is evidence of any damage to the

 

 

 

electrode/flame sense rod replace the igniter/pilot assembly. Follow the directions on page 25 to

 

 

 

re-install the burner assembly into the combustion chamber. Follow the instructions for lighting on

 

 

 

page 16. If the problem persists contact a certified service representative.

Six-Four Flash, three second pause

Soft Lockout - Flame out of Sequence Sensed

Turn the power switch on the gas control valve to the “OFF” position and unplug the power cord from the

 

 

power outlet. Wait 10 minutes then follow the lighting instructions on page 16. If the problem persists

 

 

replace the gas control valve.

Seven Flash, three second pause

Flammable Vapor Sensor (FVS) Lockout

1.

Do not touch any electrical switch, do not use any phone in the building and do not try to light any

 

 

 

appliance.

 

 

2.

Smell around the water heater to ensure there are no gas leaks at the gas control valve or in the

 

 

 

supply gas line or for any other type of flammable vapors in the area.

 

 

3.

Carefully inspect the area surrounding the water heater for any substances such as gasoline,

 

 

 

paint, paint thinners, varnish, or cleaners that could emit flammable vapors. Remove anything that

 

 

 

can potentially emit flammable vapors from the area and store it properly in a different location.

 

 

4.

Contact a certified service representative for inspection.

 

 

 

Eight-One Flash, three second pause

Flammable Vapor Sensor (FVS) Fault Detected

Turn the power switch on the gas control valve to the “OFF” position, wait 10-20 seconds then turn the

 

 

power switch on the gas control valve to the “ON” position. If the problem persists replace the gas valve.

 

 

 

Eight-Two Flash, three second pause

Temperature Sensor Fault Detected

Turn the power switch on the gas control valve to the “OFF” position, wait 10-20 seconds then turn the

 

 

power switch on the gas control valve to the “ON” position. If the problem persists replace the gas valve.

 

 

 

Eight-Three Flash, three second pause

Electronic Fault Detected

Turn the power switch on the gas control valve to the “OFF” position, wait 10-20 seconds then turn the

 

 

power switch on the gas control valve to the “ON” position. If the problem persists replace the gas valve.

 

 

 

Eight-Four Flash, three second pause

Gas Control Valve/Thermostat Fault Detected

Turn the power switch on the gas control valve to the “OFF” position, wait 10-20 seconds then turn the

 

 

power switch on the gas control valve to the “ON” position. If the problem persists replace the gas valve.

31

Image 31
Contents Flammable Vapor Ignition Resistant What to do if YOU Smell GASWater Heater Safety Unpacking the Water Heater Important Information About This Water HeaterConsumer Information Consumer ResponsibilitiesSite Location Location RequirementsInspection and service Clearances and AccessibilityGas Requirements Gas SupplyGas Pressure Combustion Air Supply and Ventilation Confined Space Unconfined SpaceAll Air from Inside the Building Louvers and Grilles All Air from OutdoorsVent Pipe Size Draft Hood InstallationVent Connectors Vent Pipe SystemVertical Exhaust Gas Vent Chimney ConnectionWater System Piping Piping InstallationClosed System/Thermal Expansion Relief Valve and Pipe Insulation Some Models Temperature and Pressure Relief ValveSpecial Applications Solar InstallationCombination Space Heating/Potable Water System Installation Checklist Explosion Hazard Lighting InstructionsBurner Flames Water Temperature StackingG. Bottled Propane Models Checking the Draft154 Instantaneous Second Water Temperature RegulationElectrical Connections Wiring DiagramStatus Light Code Operating the Temperature Control SystemWater Temperature Adjustment Operating Modes and SettingsOperational Conditions Draining and Flushing Routine Preventative MaintenanceReplacing the Pilot/Igniter Flame Sensor Assembly Replacement PartsRemoving the Burner from the Manifold Assembly Removing the Manifold AssemblyFilter Installation and Cleaning Cleaning the Combustion Chamber and Flame-trap External Inspection & Cleaning of the Flame-trapIgniter System Replacing the Manifold AssemblyRemoving and Replacing the Gas Control Valve/Thermostat Flame Guard Safety System Operational ChecklistBurner Flame Yellow Status Light Code Troubleshooting Table Status Light Code Troubleshooting Table Sequence of Operation Chart Repair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations