
Removing and Replacing the Gas Control Valve/Thermostat
IMPORTANT: The gas control valve/thermostat is a standard valve with wire leads that connect to a thermal switch, flue damper, igniter, and flammable vapor sensor
Removing the Gas Control Valve/Thermostat:
1.Turn off the gas at the manual
2.Move the ON/OFF switch on the gas control valve/ thermostat to the “OFF” position to turn off the water heater and unplug from the wall outlet. (Figure 22).
3.Drain the water heater. Refer to the section of “Draining and Flushing” and follow the procedure.
4.Disconnect the wire harness, flammable vapor sensor wires, and igniter wire from the gas control valve/ thermostat. Disconnect pilot tube (7/16” wrench) and manifold tube (3/4” wrench) at the gas control valve/ thermostat (Figure 27). NOTE: L.P. Gas systems use reverse
5.Refer to “Gas Piping” (Figure 5) and disconnect the ground joint union in the gas piping. Disconnect the remaining pipe from the gas control valve/thermostat.
6.To remove the gas control valve/thermostat, thread a 4” section of gas pipe into the inlet and use it to turn the gas control valve/thermostat (counterclockwise.) Do not use pipe wrench or equivalent to grip body. Damage may result, causing leaks. Do not insert any sharp
objects into the inlet or outlet connections. Damage to the gas control valve/thermostat may result.
Gas Control Valve/Thermostat:
To replace the gas control valve/thermostat, reassemble in reverse order. When replacing the gas control valve/ thermostat, thread a 4” section of gas pipe into the inlet and use it to turn the gas control valve/thermostat (clockwise.) DO NOT OVER TIGHTEN, damage may result.
•Be sure to use approved Teflon® tape or pipe joint compound on the gas piping connections and fitting on the back of the gas control valve that screws into tank.
•Be sure to remove the pilot ferrule nut from the new gas control valve/thermostat.
•Turn the gas supply on and check for leaks. Test the water heater by brushing on an approved noncorrosive leak detection solution. Bubbles forming indicate a leak. Correct any leak found.
•Be sure tank is completely filled with water before lighting and activating the water heater. Follow the “Lighting Instructions” on page 16.
•With the burner lit, check the gas control valve/ thermostat supply line, manifold component block, manifold tube, and pilot tube connections for leaks. Check for leaks by brushing on an approved noncorrosive leak detection solution. Bubbles forming indicate a leak. Correct any leak found. IMPORTANT: All leaks must be fixed immediately
•If additional information is required, contact the Service Department at:
Flame Guard™ Safety System Operational Checklist
1.Manifold gasket properly sealed.
2.Viewport not damaged or cracked.
3.
4.Manifold component block properly installed.
5.No leaks at pilot and manifold connection.
6.Manifold door screws securely tightened.
7.Depress the button on the thermal switch.
TROUBLESHOOTING CHART
PROBLEM |
| POSSIBLE CAUSE(S) |
| CORRECTIVE ACTION |
BURNER WILL NOT IGNITE | 1. | Pilot will not light | 1. | See PILOT WILL NOT LIGHT OR REMAIN |
| 2. | Thermostat set too low | 2. | LIT |
| Turn temp. dial to desired temperature | |||
| 3. | No gas | 3. | Check with gas utility company |
| 4. | Dirt in the gas lines | 4. | Notify |
| 5. | Pilot line clogged | 5. | Clean, locate source and correct |
| 6. | Main burner line clogged | 6. | Clean, locate source and correct |
| 7. | 7. | Replace gas control valve/thermostat | |
| 8. | Heater installed in a confined area | 8. | Provide fresh air ventilation |
| 9. | Flue Damper not functioning | 9. | Cycle power to the water heater off and on. If |
|
|
|
| problem persists replace the flue damper |
PILOT WILL NOT LIGHT OR | 1. | 1. | See Status Light Code Troubleshooting Table | |
REMAIN LIT | 2. | The thermal switch tripped | 2. | section |
| See Pilot Light Troubleshooting Flowchart | |||
| 3. | Igniter wire connection loose | 3. | section |
| Seat connector firmly in socket | |||
| 4. | Air in gas line | 4. | Bleed the air from the gas line |
| 5. | Low gas pressure | 5. | Check with gas utility company |
| 6. | No gas | 6. | Check with gas utility company |
| 7. | Dirt in gas lines | 7. | Notify |
| 8. | Cold drafts | 8. | Locate source and correct |
| 9. | Thermostat ECO switch open | 9. | Replace thermostat |
| 10. | Pilot line or orifice clogged | 10. | Clean, locate source and correct |
| 11. | Air for combustion obstructed | 11. | See maintenance section for inspection and |
| 12. | FV Senor Lockout | 12. | cleaning of flame trap. |
| Contact a qualified person to reset the sensor | |||
| 13. | Flue Damper not functioning | 13. | Cycle power to the water heater off and on. If |
|
|
|
| problem persists replace the flue damper |
28