American Water Heater Residential Gas Water Heater with the Flame Guard Safety System, 319407-002

Page 9

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 8, 9, and 10 are typical examples of each method.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.

Keep louvers and grilles clean and free of debris or other obstructions.

Table 4

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on the total BTU/HR input rating for all utilizing equip- ment within the confined space.

 

Minimum Free Area

Reference

Opening Source

Per Opening (sq. in.)

Drawing

* Direct to outdoors

1sq.in,per4000BTU/HR

Figure 8

Vertical ducts

1sq.in,per4000BTU/HR

Figure 9

Horizontal ducts

1sq.in,per2000BTU/HR

Figure 10

Single Opening

1sq.in,per3000BTU/HR

Figure 11

Example: A water heater with an input rate of 50,000 BTU/HR using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTU/HR x 1 sq. in. / 2000 BTU/HR = 25 Sq. Inches.

*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall.

Consult the local codes of your area for specific ventilation and combustion air requirements.

Gable vent

to outdoors

Install above

insulation

Outlet

air to attic

1 Sq. inch per

4000 BTU/HR

Alternate

Air Inlet

Open

Foundation

Vent

Gable vent

to outdoors

Install above

insulation

Outlet air

to attic

1 Sq. inch per

4000 BTU/HR

12” maximum

1 sq. inch

per

2000 BTU/HR

Outlet

Outdoor

Air Ducts

Inlet

1 sq. Inch

per 2000 BTU/HR

9

Image 9
Contents Flammable Vapor Ignition Resistant What to do if YOU Smell GASWater Heater Safety Consumer Information Important Information About This Water HeaterConsumer Responsibilities Unpacking the Water HeaterSite Location Location RequirementsInspection and service Clearances and AccessibilityGas Supply Gas RequirementsGas Pressure Combustion Air Supply and Ventilation Unconfined Space Confined SpaceAll Air from Inside the Building Louvers and Grilles All Air from OutdoorsVent Connectors Draft Hood InstallationVent Pipe System Vent Pipe SizeVertical Exhaust Gas Vent Chimney ConnectionWater System Piping Piping InstallationClosed System/Thermal Expansion Relief Valve and Pipe Insulation Some Models Temperature and Pressure Relief ValveSolar Installation Special ApplicationsCombination Space Heating/Potable Water System Installation Checklist Explosion Hazard Lighting InstructionsG. Bottled Propane Models Water Temperature StackingChecking the Draft Burner Flames154 Instantaneous Second Water Temperature RegulationElectrical Connections Wiring DiagramWater Temperature Adjustment Operating the Temperature Control SystemOperating Modes and Settings Status Light CodeOperational Conditions Draining and Flushing Routine Preventative MaintenanceRemoving the Burner from the Manifold Assembly Replacement PartsRemoving the Manifold Assembly Replacing the Pilot/Igniter Flame Sensor AssemblyFilter Installation and Cleaning Cleaning the Combustion Chamber and Flame-trap External Inspection & Cleaning of the Flame-trapIgniter System Replacing the Manifold AssemblyRemoving and Replacing the Gas Control Valve/Thermostat Flame Guard Safety System Operational ChecklistBurner Flame Yellow Status Light Code Troubleshooting Table Status Light Code Troubleshooting Table Sequence of Operation Chart Repair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations