MULTI FLUE - (1 UNIT) WITH VERTICAL STORAGE TANK

WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.

PIPE T&P TO

OPEN DRAIN

35

LEGEND

TEMPERATURE & PRESSURE

RELIEF VALVE

PRESSURE RELIEF VALVE

CIRCULATING PUMP

TANK TEMPERATURE CONTROL

DRAIN

HOT WATER

TO FIXTURES

FULL PORT BALL VALVE

CHECK VALVE

TEMPERATURE GAGE

WATER FLOW SWITCH

Water Piping

FINISHED FLOOR

HOT WATER RETURN

FROM FIXTURES

ALT. COLD WATER

CONNECTION

COLD WATER

SUPPLY

EXPANSION

TANK

Diagrams

NOTES:

1.Preferred piping diagram.

2.The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.

3.Service valves are shown for servicing unit. However, local codes shall govern their usage.

4.The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).

5.The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.

Image 35
Contents Commercial gas water heaters Table Of Contents Approvals Safe Installation, Use and ServiceFire and Explosion Hazard General Safety InformationGrounding Instructions Precautions Hydrogen Gas FlammableQualifications Qualified Installer or Service AgencyIntroduction Abbreviations UsedElectronic Ignition Control Eliminator self-cleaning systemHigh Limit Switch Low Gas Pressure SwitchRecovery CAPACITIES, based on 80% efficiency Installation considerationsRough In Dimensions ROUGH-IN-DIMENSIONSClearances Locating the Water HeaterCirculation pumps Installation on Combustible FlooringInsulation Blanket High Altitude Installations Installation Requirements Thermal Expansion Temperature-Pressure Relief ValveDishwashing Machines Closed Water SystemsValve Discharge Pipe Requirements Contaminated AirAir Requirements Venting Unconfined SpaceConfined Space Outdoor Air Through One Opening Multiple Heater ManifoldFresh Air Openings for Confined Spaces Outdoor Air Through Two OpeningsAir From Other Indoor Spaces Outdoor Air Through Two Vertical DuctsMultiple Gas Fired Tank-Type Heaters Technical Data VentingTechnical Data Venting Valve Discharge Pipe Water heater installationWater Line Connections Tube Inlet Installation Installation Diagrams Top Inlet/Outlet UsageHeater Wiring Gas Meter Size Natural Gases Only Gas Line Leak TestingGas Piping PurgingInitial Start Up Start UpPrior to Start Up Checking the Input Water Temperature AdjustmentChecking Venting Gas ValvesLighting & Operation Label Sequence of OperationSequence of Operation Flow Chart Maintenance To Drain the Water Heater Storage Tank Hot Water OdorAnode Rod Inspection Draining and FlushingExample Tank Cleanout ProcedureDeliming Using FLO-JUG Method Deliming SolventsChemical Hazard Electrical Servicing System DiagnosticsIgnition Module System Operational Conditions High Water Temperature Shut Off SystemFor Your Information Start Up ConditionsComplaint Cause Remedy User TroubleshootingQualified Service Agency Water Piping DiagramsTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Manifold Kits Conditions and Exceptions Service and Repair ExpensesClaim Procedure ALL Other Parts