Mitsubishi Electronics Understanding Mis Wiring in Mitsubishi Air Conditioners: Troubleshooting Guide

Page 24

When POWER lamp flashes ON and OFF in every 0.5-second.

Outdoor unit does not operate.

D How to check mis-wiring and serial signal error

 

 

 

 

 

Turn OFF the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there rated voltage of

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the power

 

 

 

 

 

 

 

 

 

 

 

230V AC in the power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply.

 

 

 

 

 

 

 

 

 

 

 

supply?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there 230V AC between

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor terminal block S1 and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S2?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press EMERGENCY OPERATION switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does POWER lamp light up?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Confirmation of the power to the indoor unit>

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there any mis-wiring,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the self-check of the indoor unit displayed 6

 

No

poor contact, or wire

Yes

 

 

 

Make them sure.

 

 

minutes after?

 

 

 

 

 

disconnection of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor/outdoor

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

connecting wire?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial signal error display

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER lamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blinks quickly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn OFF the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check once more if the indoor/outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connecting wire is not mis-wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Short-circuit outdoor terminal block S2 and

W1. Mis-wiring may damage indoor electronic control

 

 

 

 

 

 

 

 

 

 

S3.

 

 

 

P.C. board during the operation.

 

 

 

 

 

 

 

 

W1

 

 

 

Be sure to confirm the wiring is correct before the

operation starts.

Turn ON the power supply of the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

In 3 minutes after turning ON the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power supply of the outdoor unit, does

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the LED on the inverter P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter P.C.board

 

 

 

 

repeat quick blinking "3.6-second-OFF

 

 

No

Replace the inverter

 

 

 

 

 

 

 

 

 

 

and 0.8-second-ON"?

 

 

 

 

 

 

 

 

(Parts side)

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Be sure to check above in 3 minutes

 

 

(Lighting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

after turning ON. After 3 minutes, LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blinks 6 times. When the inverter P.C.

 

 

 

 

 

W2 Be careful to the residual

 

 

 

 

LED

 

 

 

 

 

 

 

 

board is normal, LED also blinks 6

 

 

 

 

 

voltage of smoothing capacitor.

 

 

 

 

 

 

 

 

 

 

 

 

times after 3 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

Remove the short-circuit between

 

 

Is there any error of the

 

 

 

 

·Turn OFF inverter-controlled lighting

 

 

 

 

 

 

 

 

 

outdoor terminal block S2 and S3.

 

 

indoor/outdoor connecting wire,

Yes

Replace the

 

equipment.

 

 

 

 

 

 

 

 

Is there amplitude of 10 to 20V DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

such as the damage of the wire,

 

 

indoor/outdoor

 

·Turn OFF the power supply and then

 

 

between outdoor terminal block S2

 

 

 

 

 

 

No

intermediate connection, poor

 

 

connecting.

 

turn ON again.

 

 

 

 

 

 

 

 

and S3? <Confirmation of serial

 

 

 

 

 

 

 

 

 

 

 

contact to the terminal block?

 

 

 

 

 

 

 

 

 

 

 

 

signal>

 

 

 

 

 

 

· Press EMERGENCYOPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switch.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

· Reinstall

 

 

 

 

 

 

 

Is there any error of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

either the

 

Is there 230V AC between outdoor

 

 

indoor/outdoor connecting wire,

Yes

Replace the

 

 

 

 

 

 

 

 

unit or the

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal block S1 and S2?

 

 

such as the damage of the wire,

 

 

indoor/outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

Is serial signal

 

No

 

light each

 

<Confirmation of power voltage>

No intermediate connection, poor

 

 

connecting.

 

 

 

other away.

 

 

 

 

 

error indicated

 

 

 

 

 

 

Yes

 

 

contact to the terminal block?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 minutes later?

 

 

 

 

·Attach a filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on receiving

 

Replace the indoor electronic control P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

section of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

the indoor

 

Be sure to release the failure-mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recall function after checking.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

As for outdoor unit MUZ type,refer to service manual OB372.

As for outdoor unit MXZ type,refer to service manual OB377.

24

Image 24
Contents Contents MSZ-FA25VA E1 MSZ-FA35VA E1Technical Changes Generalized stepping motorFront panel opening/closing output gear Wash reset switch Open Closed Receiving section Part Names and FunctionsIndoor Unit MSZ-FA25VA MSZ-FA35VA See control operationMSZ-FA25VA E1 MSZ-FA35VA E1 Accessories Remote ControllerSpecification Specifications and rating conditions of main electric partsWhen outdoor unit is MXZ type Noise Criteria Curves MSZ-FA25VA E1MSZ-FA35VA E1 Outlines and Dimensions MSZ-FA25VA E1 MSZ-FA35VA E1Indoor Unit Unit mmWiring Diagram Refrigerant System DiagramMSZ-FA25VA E1 Indoor Unit MSZ-FA35VA E1 Indoor UnitService Functions How to modify the remote controller P.C. boardRemote controller model KM05A OperationRemote controller Troubleshooting Install RemoveInformation for Multi System AIR Conditioner Outdoor Unit MXZ seriesFailure mode recall function OFFTo identify the error.Refer to 9-6.For G Indoor unit failure mode table Plasma DeodorizingPlasma AIR Purifying OFFInstruction of troubleshooting StartTroubleshooting check table · Flashing of Power lamp indicates abnormalitiesPlasma AIRPurifying Trouble criterion of main parts Troubleshooting flow When Power lamp flashes 3-time Indoor fan does not operateCheck of indoor fan motor Check of remote controller and receiver P.C. board Indoor electronic control P.C.Board How to check mis-wiring and serial signal error LEDCheck of installation of the horizontal vane Safety Deviceplasma Unit Plasma Deodorizing 0V?Continuously flash? AIR Purifying 0V?Check of auto front panel Indoor unit and outdoor unit do not operateElectromagnetic noise enters into TV sets or radios YesTest point diagram and voltage Power monitor receiver P.C. boardPlasma power P.C. board Indoor electronic control P.C. boardDisassembly Instructions Removing the panel PhotoOperating Procedure Photos Removing the electrical boxRemoving the horizontal vane motor unit Photo Removing the vertical vane motor unit PhotoRemoving the indoor fan motor and the line flow Photo FanRemoving the plasma power P.C. board Photo Parts List Accessory and Remote ControllerSafety Plasma Indoor Unit Electrical Parts and Functional PartsIndoor Unit Heat Exchanger Motor Receiver P.C Board HolderSymbol Qty/unit Part name Wiring Diagram E02509 504Optional Parts Deodorizing Ceramic FilterPage Specifications subject to change without notice