Mitsubishi Electronics MSZ-FA35VA Service Functions, Operation, Remote controller model KM05A

Page 9

8

SERVICE FUNCTIONS

MSZ-FA25VA - E1

MSZ-FA35VA - E1

8-1. TIMER SHORT MODE

For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.)

Set time : 1-minute 1-second

Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.)

8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION

A maximum of 4 indoor units with wireless remote controllers can be used in a room.

In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.

How to modify the remote controller P.C. board

Remove batteries before modification.

The board has a print as shown below :

Remote controller model : KM05A

NOTE : For remodelling, take out the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first.

After finish remodelling, put back the batteries then press the RESET button.

J1 J2

The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.

Table 1

 

1 unit operation

2 units operation

3 units operation

4 units operation

 

 

 

 

 

No. 1 unit

No modification

Same as at left

Same as at left

Same as at left

 

 

 

 

 

No. 2 unit

Solder J1

Same as at left

Same as at left

No. 3 unit

Solder J2

Same as at left

 

 

 

 

 

No. 4 unit

Solder both J1 and J2

 

 

 

 

 

How to set the remote controller exclusively for particular indoor unit.

After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit.

The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set.

The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.

8-3. AUTO RESTART FUNCTION

When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.

Operation

1If the main power has been cut, the operation settings remain.

2After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3 minutes for the compressor to start running.)

9

Image 9
Contents MSZ-FA25VA E1 MSZ-FA35VA E1 ContentsTechnical Changes Generalized stepping motorFront panel opening/closing output gear Part Names and Functions Wash reset switch Open Closed Receiving sectionIndoor Unit MSZ-FA25VA MSZ-FA35VA See control operationRemote Controller MSZ-FA25VA E1 MSZ-FA35VA E1 AccessoriesSpecification Specifications and rating conditions of main electric partsWhen outdoor unit is MXZ type Noise Criteria Curves MSZ-FA25VA E1MSZ-FA35VA E1 MSZ-FA25VA E1 MSZ-FA35VA E1 Outlines and DimensionsIndoor Unit Unit mmRefrigerant System Diagram Wiring DiagramMSZ-FA25VA E1 Indoor Unit MSZ-FA35VA E1 Indoor UnitHow to modify the remote controller P.C. board Service FunctionsRemote controller model KM05A OperationRemote controller Troubleshooting Remove InstallOutdoor Unit MXZ series Information for Multi System AIR ConditionerOFF Failure mode recall functionTo identify the error.Refer to 9-6.For G Plasma Deodorizing Indoor unit failure mode tablePlasma AIR Purifying OFFStart Instruction of troubleshooting· Flashing of Power lamp indicates abnormalities Troubleshooting check tablePlasma AIRPurifying Trouble criterion of main parts Troubleshooting flow When Power lamp flashes 3-time Indoor fan does not operateCheck of indoor fan motor Check of remote controller and receiver P.C. board Indoor electronic control P.C.Board LED How to check mis-wiring and serial signal errorCheck of installation of the horizontal vane Plasma Deodorizing 0V? Safety Deviceplasma UnitAIR Purifying 0V? Continuously flash?Indoor unit and outdoor unit do not operate Check of auto front panelYes Electromagnetic noise enters into TV sets or radiosPower monitor receiver P.C. board Test point diagram and voltagePlasma power P.C. board Indoor electronic control P.C. boardRemoving the panel Photo Disassembly InstructionsRemoving the electrical box Operating Procedure PhotosRemoving the vertical vane motor unit Photo Removing the horizontal vane motor unit PhotoRemoving the indoor fan motor and the line flow Photo FanRemoving the plasma power P.C. board Photo Accessory and Remote Controller Parts ListIndoor Unit Electrical Parts and Functional Parts Safety PlasmaIndoor Unit Heat Exchanger Motor Receiver P.C Board HolderDiagram E02 Symbol Qty/unit Part name Wiring509 504Deodorizing Ceramic Filter Optional PartsPage Specifications subject to change without notice