Mitsubishi Electronics MSZ-FA35VA, MSZ-FA25VA service manual Continuously flash?, AIR Purifying 0V?

Page 27

When PLASMA/WASH lamp flashes 2-time.

wThe power failure mode for PLASMA AIR PURIFYING power is memorized when the failure mode is called.

G Check of PLASMA AIR PURIFYING power

After performing the check, make sure to release the failure mode recall function.

Turn ON the power supply.

High voltage (approx. -3.9kV) is generated during PLASMA AIR PURIFYING power operation.

Pay careful attention and never touch PLASMA/WASH unit and the high-voltage lead part (red wire).

While the operation is being

Yes

 

stopped, does

Replace the indoor electronic control P.C. board is out of order.

 

PLASMA/WASH lamp flash

 

 

 

twice?

 

1 During pressing both OPERATION SELECT

 

 

No

 

button and TOO COOL button on the remote

Make sure that the front panel is firmly closed.

 

controller at the same time, press RESET button.

 

2 First, release RESET button.

1 During pressing both OPERATION SELECT button and

And release the other two buttons since

TOO COOL button on the remote controller at the same time,

all LCD in operation display section of the

press RESET button.

 

remote controller is displayed after 3 seconds.

2 First, release RESET button.

 

(Failure mode recall function is set.)

And release the other two buttons since

 

3 Press OPERATE/STOP (ON/OFF) button.

all LCD in operation display section of the

 

4 After a short beep sound is emitted, press

remote controller is displayed after 3 seconds.

 

twice PLASMA button.

(Failure mode recall function is set.)

 

PLASMA AIR PURIFYING operation is

3 Press OPERATE/STOP (ON/OFF) button.

 

selected.

4After a short beep sound is emitted, press

twice PLASMA button.

PLASMA AIR

PLASMA AIR PURIFYING operation is

PURIFYING

selected.

operation

wThe plasma power operation check mode is set.(Refer to 9-2.5.)

 

Does PLASMA/WASH lamp stay OFF, or

Stays OFF

 

continuously flash?

 

PLASMA AIR PURIFYING power supply is normal. The front panel is not firmly closed, therefore the protection by the interlock switch is active.

 

 

 

 

 

 

 

w1 Turn PLASMA AIR PURIFYING power OFF and ON again.

 

 

Continuously flashes.

 

 

(For turning off PLASMA AIR PURIFYING power, refer to 9-2.3.)

 

 

 

 

(If it goes normal without turning OFF and ON, PLASMA/WASH lamp

 

 

 

 

 

 

 

doesn't go OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove the plasma unit, firmly close the

 

 

 

 

If the plasma unit is dirty, clean the unit.

 

 

 

 

 

 

After cleaning, make sure to attach the unit when it is

 

 

front panel, and then perform PLASMA AIR

 

Stays OFF

 

 

 

completely dry.

 

 

PURIFYING power operation check (w1).

 

 

 

 

 

 

 

 

 

 

 

 

If the air conditioner goes ON with the plasma unit

 

 

Does PLASMA/WASH lamp stay OFF, or

 

 

 

 

 

 

 

 

 

 

being wet, protection gets active and PLASMA/WASH

 

 

continuously flash?

 

 

 

 

 

 

 

 

 

 

lamp continuously flashes.

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuously flashes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn OFF the power supply, and check the

 

No

 

 

 

 

 

 

 

SAFETY DEVICE(PLASMA UNIT).

 

 

 

 

Firmly fix the SAFETY DEVICE.

 

 

 

 

 

 

 

 

 

 

Is it firmly fixed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON and OFF the SAFETY DEVICE

 

No

 

 

 

 

 

 

(PLASMA UNIT) using something like a screw

 

 

 

 

 

 

 

driver, and measure the resistance value between

 

 

 

 

Replace the SAFETY DEVICE(PLASMA UNIT).

 

 

 

 

 

 

 

 

CN1T2 1 and 3 on the indoor electronic control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board. Does the switch work?

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep the SAFETY DEVICE(PLASMA UNIT)

 

No

 

 

 

 

 

 

 

ON using something like a screw driver.

 

 

 

 

 

 

 

 

 

9.5V DC is generated.

 

Turn ON the power supply.

 

 

While the operation is being stopped, is the

 

 

 

 

Replace the indoor electronic control P.C. board.

 

 

 

 

 

 

 

 

 

voltage between CN1 1(+) and 2(GND) on

 

 

 

 

 

 

 

 

 

the PLASMA POWER P.C. board (PLASMA

 

 

 

 

 

 

 

 

 

AIR PURIFYING) 0V?

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the plasma power failure mode recall function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When PLASMA button is pressed, is

 

No

 

 

Replace the indoor electronic control P.C. board.

 

there voltage of 12.5V DC between CN1

 

 

 

 

Check the wiring of CN1T1 on the indoor electronic control

 

 

 

 

 

 

1(+) and 2(GND)?

 

 

 

 

P.C. board.

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the PLASMA POWER P.C. board

 

 

 

 

 

 

 

 

 

 

 

(PLASMA AIR PURIFYING).

 

 

 

 

 

 

 

 

 

 

27

Image 27
Contents MSZ-FA25VA E1 MSZ-FA35VA E1 ContentsTechnical Changes Generalized stepping motorFront panel opening/closing output gear See control operation Wash reset switch Open Closed Receiving sectionPart Names and Functions Indoor Unit MSZ-FA25VA MSZ-FA35VARemote Controller MSZ-FA25VA E1 MSZ-FA35VA E1 AccessoriesSpecification Specifications and rating conditions of main electric partsWhen outdoor unit is MXZ type Noise Criteria Curves MSZ-FA25VA E1MSZ-FA35VA E1 Unit mm Outlines and DimensionsMSZ-FA25VA E1 MSZ-FA35VA E1 Indoor UnitMSZ-FA35VA E1 Indoor Unit Wiring DiagramRefrigerant System Diagram MSZ-FA25VA E1 Indoor UnitOperation Service FunctionsHow to modify the remote controller P.C. board Remote controller model KM05ARemote controller Troubleshooting Remove InstallOutdoor Unit MXZ series Information for Multi System AIR ConditionerOFF Failure mode recall functionTo identify the error.Refer to 9-6.For G OFF Indoor unit failure mode tablePlasma Deodorizing Plasma AIR PurifyingStart Instruction of troubleshooting· Flashing of Power lamp indicates abnormalities Troubleshooting check tablePlasma AIRPurifying Trouble criterion of main parts Troubleshooting flow When Power lamp flashes 3-time Indoor fan does not operateCheck of indoor fan motor Check of remote controller and receiver P.C. board Indoor electronic control P.C.Board LED How to check mis-wiring and serial signal errorCheck of installation of the horizontal vane Plasma Deodorizing 0V? Safety Deviceplasma UnitAIR Purifying 0V? Continuously flash?Indoor unit and outdoor unit do not operate Check of auto front panelYes Electromagnetic noise enters into TV sets or radiosIndoor electronic control P.C. board Test point diagram and voltagePower monitor receiver P.C. board Plasma power P.C. boardRemoving the panel Photo Disassembly InstructionsRemoving the electrical box Operating Procedure PhotosFan Removing the horizontal vane motor unit PhotoRemoving the vertical vane motor unit Photo Removing the indoor fan motor and the line flow PhotoRemoving the plasma power P.C. board Photo Accessory and Remote Controller Parts ListMotor Receiver P.C Board Holder Safety PlasmaIndoor Unit Electrical Parts and Functional Parts Indoor Unit Heat Exchanger504 Symbol Qty/unit Part name WiringDiagram E02 509Deodorizing Ceramic Filter Optional PartsPage Specifications subject to change without notice