Mitsubishi Electronics MSZ-FA25VA, MSZ-FA35VA service manual Troubleshooting check table

Page 18

9-4. Troubleshooting check table

Lighted

· Flashing of POWER lamp indicates abnormalities.

Blinking

Not lighted

NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table

No.

Abnormal

Operation indicator lamp

Symptom

Detection method

Check point

 

point

 

 

 

 

 

 

POWER lamp flashes.

 

 

 

 

Mis-Wiring

0.5-second ON

Outdoor unit

When the serial signal form the outdoor unit is

• Refer to 9-6.D"How to check

1

or serial

 

does not

mis-wiring and serial signal

 

not received for a maximum of 6 minutes.

 

signal

 

operate.

error".

 

 

0.5-second OFF

 

 

 

 

Outdoor

 

 

When it cannot properly read data in the

• Check the blinking pattern of

 

 

Outdoor unit

the LED on the inverter P.C.

2

control

POWER lamp lights up

nonvolatile memory of the inverter P.C. board

board or the outdoor lectronic

does not

or the outdoor electronic control P.C. board.

 

system

 

control P.C. board.

 

 

operate.

 

 

 

 

 

 

 

Indoor coil

POWER lamp flashes.

 

 

 

 

thermistor

 

 

 

 

2-time flash

Indoor unit

When the indoor coil or the room temperature

• Refer to 9-7.the

 

 

3

 

 

and outdoor

thermistor is short or open circuit.

characteristics of indoor coil

Room

 

unit do not

 

thermistor, and the room

 

tempera-

2.5-second OFF

operate.

 

temperature thermistor.

 

ture

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

POWER lamp flashes.

Indoor unit

 

 

 

 

3-time flash

When the rotational frequency feedback

• Refer to 9-7.A"Check of

 

Indoor fan

 

and outdoor

4

 

signal is not emit during the indoor fan

motor

 

unit do not

indoor fan motor".

 

 

operation.

 

 

 

operate.

 

 

 

 

 

 

 

 

2.5-second OFF

 

 

 

 

 

POWER lamp flashes.

Indoor unit

When it consecutively occurs 3 times that the

• Refer to "Check of inverter/

 

Outdoor

5-time flash

 

compressor".

5

power

 

and outdoor

compressor stops for overcurrent protection or

Refer to service manual

 

unit do not

start-up failure protection witth in 1 minute

 

system

 

OB372 or OB377.

 

 

operate.

after start-up.

 

 

2.5-second OFF

Check the stop valve.

 

 

 

 

 

 

 

 

 

 

 

POWER lamp flashes.

 

 

 

 

 

6-time flash

Indoor unit

When the outdoor thermistors short or open

• Refer to "Check of outdoor

 

Outdoor

 

and outdoor

thermistor".

6

 

unit do not

circuit during the compressor operation.

Refer to service manual

thermistors

 

 

 

operate.

 

OB372 or OB377.

 

 

2.5-second OFF

 

 

 

 

 

 

 

 

POWER lamp flashes.

Indoor unit

 

• Replace the inverter P.C.

 

Outdoor

7-time flash

When it cannot properly read data in the

board or the outdoor

 

and outdoor

7

control

 

nonvolatile memory of the inverter P.C. board

electronic control P.C. board.

 

unit do not

 

system

 

or the outdoor electronic control P.C. board.

Refer to service manual

 

 

operate.

 

 

2.5-second OFF

 

OB372 or OB377.

 

 

 

 

 

 

POWER lamp flashes.

Indoor unit

 

 

 

Other

14-time flash

An abnormality other than above mentioned is

• Confirm the abnormarity in

8

 

and outdoor

detail using the failure mode

abnonmality

 

unit do not

deteced.

 

 

 

operate.

 

recall function.

 

 

2.5-second OFF

 

 

 

 

 

 

 

NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.

18

Image 18
Contents Contents MSZ-FA25VA E1 MSZ-FA35VA E1Technical Changes Generalized stepping motorFront panel opening/closing output gear Indoor Unit MSZ-FA25VA MSZ-FA35VA Wash reset switch Open Closed Receiving sectionPart Names and Functions See control operationMSZ-FA25VA E1 MSZ-FA35VA E1 Accessories Remote ControllerSpecification Specifications and rating conditions of main electric partsWhen outdoor unit is MXZ type Noise Criteria Curves MSZ-FA25VA E1MSZ-FA35VA E1 Indoor Unit Outlines and DimensionsMSZ-FA25VA E1 MSZ-FA35VA E1 Unit mmMSZ-FA25VA E1 Indoor Unit Wiring DiagramRefrigerant System Diagram MSZ-FA35VA E1 Indoor UnitRemote controller model KM05A Service FunctionsHow to modify the remote controller P.C. board OperationRemote controller Troubleshooting Install RemoveInformation for Multi System AIR Conditioner Outdoor Unit MXZ seriesFailure mode recall function OFFTo identify the error.Refer to 9-6.For G Plasma AIR Purifying Indoor unit failure mode tablePlasma Deodorizing OFFInstruction of troubleshooting StartTroubleshooting check table · Flashing of Power lamp indicates abnormalitiesPlasma AIRPurifying Trouble criterion of main parts Troubleshooting flow When Power lamp flashes 3-time Indoor fan does not operateCheck of indoor fan motor Check of remote controller and receiver P.C. board Indoor electronic control P.C.Board How to check mis-wiring and serial signal error LEDCheck of installation of the horizontal vane Safety Deviceplasma Unit Plasma Deodorizing 0V?Continuously flash? AIR Purifying 0V?Check of auto front panel Indoor unit and outdoor unit do not operateElectromagnetic noise enters into TV sets or radios YesPlasma power P.C. board Test point diagram and voltagePower monitor receiver P.C. board Indoor electronic control P.C. boardDisassembly Instructions Removing the panel PhotoOperating Procedure Photos Removing the electrical boxRemoving the indoor fan motor and the line flow Photo Removing the horizontal vane motor unit PhotoRemoving the vertical vane motor unit Photo FanRemoving the plasma power P.C. board Photo Parts List Accessory and Remote ControllerIndoor Unit Heat Exchanger Safety PlasmaIndoor Unit Electrical Parts and Functional Parts Motor Receiver P.C Board Holder509 Symbol Qty/unit Part name WiringDiagram E02 504Optional Parts Deodorizing Ceramic FilterPage Specifications subject to change without notice