4. Indoor unit failure mode table

NOTE: Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.).

POWER lamp

Abnormal point

Detection method

Check point

(Failure mode)

 

 

 

 

 

 

 

Not lighted

Normal

 

 

 

 

1-time flash

Room temperature

When the room temperature thermistor short

Refer to the characteristics of the room

every 0.5-second

thermistor

or open circuit is detected every 8

temperature thermistor (9-7.).

seconds during operation.

 

 

 

 

 

 

 

2-time flash

 

When the indoor coil thermistor short or open

Refer to the characteristic of the main

Indoor coil thermistor

circuit is detected every 8 seconds during

indoor coil thermistor, the sub indoor coil

2.5-second OFF

 

operation.

thermistor (9-7.).

 

 

 

 

 

 

3-time flash

Serial signal error

When the serial signal from outdoor unit is

Refer to 9-6.D"How to check miswiring

2.5-second OFF

not received for a maximum of 6 minutes.

and serial signal error".

 

 

 

 

 

11-time flash

 

When the rotational frequency feedback

Refer to 9-6.A"Check of indoor fan

Indoor fan motor

signal is not emit during 12-second the

2.5-second OFF

motor".

 

indoor fan operation.

 

 

 

 

 

 

 

12-time flash

 

When it cannot properly read data in the

Replace the indoor electronic control

Indoor control system

nonvolatile memory of the indoor electronic

2.5-second OFF

P.C. board.

 

control P.C. board.

 

 

 

 

 

 

 

5. PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode table

POWER lamp

Abnormal point

Detection method

Check point

(Failure mode)

 

 

 

 

 

 

 

 

PLASMA DEODORIZING/

When PLASMA DEODORIZING/PLASMA

Replace the indoor electronic control P.C.

1-time flash

PLASMA AIR PURIFYING

AIR PURIFYING power cannot be turned

board.

 

power control

OFF.

 

 

 

 

 

 

 

 

When the voltage between CN1 1(+)

Refer to 9-6.F"Check of PLASMA

 

 

and 2(GND) on the PLASMA POWER P.C.

 

 

DEODORIZING power" or 9-6.G"Check

2-time flash

Spark discharge

board (PLASMA DEODORIZING or PLASMA

 

 

AIR PURIFYING) falls below 1.6V(spark

of PLASMA AIR PURIFYING power".

 

 

 

 

 

discharge judgment voltage).

 

 

 

 

 

 

 

When the voltage between CN1 1(+)

Refer to 9-6.F"Check of PLASMA

 

 

and 2(GND) on the PLASMA POWER P.C.

 

Abnormal electric

DEODORIZING power" or 9-6.G"Check

3-time flash

board (PLASMA DEODORIZING or PLASMA

discharge error 1

AIR PURIFYING) falls 0.9V below the normal

of PLASMA AIR PURIFYING power".

 

 

 

range voltage.

 

 

 

 

 

 

 

When the voltage between CN1 1(+)

Refer to 9-6.F"Check of PLASMA

 

Abnormal electric

and 2(GND) on the PLASMA POWER P.C.

DEODORIZING power" or 9-6.G"Check

4-time flash

board (PLASMA DEODORIZING or PLASMA

of PLASMA AIR PURIFYING power".

discharge error 2

 

AIR PURIFYING) falls significantly.

 

 

 

 

 

 

(0.4V / 0.5ms)

 

 

 

 

 

 

 

When the voltage between CN1 1(+)

Refer to 9-6.F"Check of PLASMA

 

PLASMA DEODORIZING/

and 2(GND) on the PLASMA POWER P.C.

 

DEODORIZING power" or 9-6.G"Check

5-time flash

board (PLASMA DEODORIZING or PLASMA

PLASMA AIR PURIFYING

of PLASMA AIR PURIFYING power".

 

power

AIR PURIFYING) rises above the normal

 

 

voltage value (3V).

 

 

 

 

 

 

 

 

wAs soon as an error is detected, PLASMA DEODORIZING power or PLASMA AIR PURIFYING power goes OFF, therefore measuring instrument which records the voltage wave is required in order to perform the above men- tioned voltage measurement.

16

Image 16
Contents Contents MSZ-FA25VA E1 MSZ-FA35VA E1Generalized stepping motor Technical ChangesFront panel opening/closing output gear Wash reset switch Open Closed Receiving section Part Names and FunctionsIndoor Unit MSZ-FA25VA MSZ-FA35VA See control operationMSZ-FA25VA E1 MSZ-FA35VA E1 Accessories Remote ControllerSpecifications and rating conditions of main electric parts SpecificationWhen outdoor unit is MXZ type MSZ-FA25VA E1 Noise Criteria CurvesMSZ-FA35VA E1 Outlines and Dimensions MSZ-FA25VA E1 MSZ-FA35VA E1Indoor Unit Unit mmWiring Diagram Refrigerant System DiagramMSZ-FA25VA E1 Indoor Unit MSZ-FA35VA E1 Indoor UnitService Functions How to modify the remote controller P.C. boardRemote controller model KM05A OperationRemote controller Troubleshooting Install RemoveInformation for Multi System AIR Conditioner Outdoor Unit MXZ seriesFailure mode recall function OFFTo identify the error.Refer to 9-6.For G Indoor unit failure mode table Plasma DeodorizingPlasma AIR Purifying OFFInstruction of troubleshooting StartTroubleshooting check table · Flashing of Power lamp indicates abnormalitiesAIR PlasmaPurifying Trouble criterion of main parts When Power lamp flashes 3-time Indoor fan does not operate Troubleshooting flowCheck of indoor fan motor Check of remote controller and receiver P.C. board Indoor electronic control P.C.Board How to check mis-wiring and serial signal error LEDCheck of installation of the horizontal vane Safety Deviceplasma Unit Plasma Deodorizing 0V?Continuously flash? AIR Purifying 0V?Check of auto front panel Indoor unit and outdoor unit do not operateElectromagnetic noise enters into TV sets or radios YesTest point diagram and voltage Power monitor receiver P.C. boardPlasma power P.C. board Indoor electronic control P.C. boardDisassembly Instructions Removing the panel PhotoOperating Procedure Photos Removing the electrical boxRemoving the horizontal vane motor unit Photo Removing the vertical vane motor unit PhotoRemoving the indoor fan motor and the line flow Photo FanRemoving the plasma power P.C. board Photo Parts List Accessory and Remote ControllerSafety Plasma Indoor Unit Electrical Parts and Functional PartsIndoor Unit Heat Exchanger Motor Receiver P.C Board HolderSymbol Qty/unit Part name Wiring Diagram E02509 504Optional Parts Deodorizing Ceramic FilterPage Specifications subject to change without notice