Communication-capable Circuit Breakers
WL Circuit Breaker
Data Availability on the CubicleBUS
All modules connected to the CubicleBUS can request data from other modules via the bus and generate data themselves that can be read by other modules.
Each data point in the comprehensive WL Circuit Breaker data dictionary can only be generated by a single
This information is described and communicated in the property bytes.
If a data source (module) does not exist, the data point does not exist either.
Again, the relevant property byte contains this information.
The following table provides an overview of the internal CubicleBUS modules and the data point groups (collection of several data points) assigned to them.
See Chapter 3 Register List for a detailed description of the individual data points.
|
|
| CubicleBUS Modules | |
Data point group | ETU745, 748, | BSS | COM16 | Metering |
Data points with the same source | 755 or 776 |
|
| Function Plus |
Protection parameter set A | ✓ |
|
|
|
Protection parameter set B (N/A for ETU745 or 748) | ✓ |
|
|
|
Extended protection parameters |
|
|
| ✓ |
Parameter for setpoints |
|
|
| ✓ |
MODBUS communication parameters |
|
| ✓ |
|
Parameters for metering settings |
|
|
| ✓ |
Device identification data | ✓ |
| ✓ |
|
Circuit breaker position specifications |
|
| ✓ |
|
Status info. (circuit breaker open/closed, storage spring, etc.) | ✓ |
|
| |
Alarms | ✓ |
|
|
|
Trip log | ✓ |
|
| ✓ |
Setpoint messages |
|
|
| ✓ |
Maintenance information | ✓ |
| ✓ |
|
Circuit breaker temperature |
| ✓ |
|
|
Temperature in the cubicle |
|
| ✓ |
|
✓ |
|
|
| |
Current in neutral, | ✓ |
|
|
|
|
|
| ✓ | |
Power KW, KVAR, KVA |
|
|
| ✓ |
Power factor |
|
|
| ✓ |
Frequency, total harm. distortion, form factor, crest factor |
|
|
| ✓ |
Harmonic analysis |
|
|
| ✓ |
Waveform buffer |
|
|
| ✓ |
Event log |
|
| ✓ |
|
System time |
|
| ✓ |
|
Table
2/7
WL MODBUS Communication and Electronic Accessories • January 2005