Siemens UL1066 Default Register Lists, Basic Data Type 1 Registers and Default Data Points

Page 58

Communication-capable Circuit Breakers

WL Circuit Breaker

Default Register Lists

(Function 04 Data Blocks)

Basic Data Type 1 Registers and Default Data Points

Register

Byte

Name

Default Data Point – WL

1

0, 1

Status Register

WL status bits

2

2, 3

Data Block 1

Phase 1 current

3

4, 5

Data Block 2

Phase 2 current

4

6, 7

Data Block 3

Phase 3 current

5

8, 9

Data Block 4

Max current in phase under highest load

6

10

Block 1 property byte

PB of phase 1 current

11

Block 2 property byte

PB of phase 2 current

 

7

12

Block 3 property byte

PB of phase 3 current

13

Block 4 property byte

PB of max current in phase under highest load

 

Table 3-5

Basic Data Type 2 Registers and Default Data Points

Register

Byte

Name

Default Data Point – WL

1

0, 1

Status Register

WL status bits

2

2, 3

Data Block 1

Phase 1 current

3

4, 5

Data Block 2

Phase 2 current

4

6, 7

Data Block 3

Phase 3 current

5

8, 9

Data Block 4

Max current in phase under highest load

6

10, 11

Data Block 5

Current in neutral conductor

7

12, 13

Data Block 6

Average phase to phase voltage

8

14, 15

Data Block 7

Average of power factors of 3 phases

9

16, 17

Data Block 8

Total active energy of 3 phases*

10

18

Block 1 property byte

PB of phase 1 current

19

Block 2 property byte

PB of phase 2 current

 

11

20

Block 3 property byte

PB of phase 3 current

21

Block 4 property byte

PB of max current in phase under highest load

 

12

22

Block 5 property byte

BP of current in neutral conductor

23

Block 6 property byte

BP of average phase to phase voltage

 

13

24

Block 7 property byte

BP of average of power factors of 3 phases

25

Block 8 property byte

BP of total active energy of 3 phases

 

*Only 2 bytes of the 4 byte data point will be communicated (range: 0 - 65535MWh)

Table 3-6

3/11

WL MODBUS Communication and Electronic Accessories • January 2005

Image 58
Contents Powerful ideas Global network of innovationCommunication-capable Circuit Breakers Communication-capable Circuit Breaker Correct Usage Safety GuidelinesQualified Personnel Registered TrademarksIntroduction Overview General Content of the ManualIntroduction Cost Saving System SolutionsWL Circuit Breakers-Modular Intelligent Easy PlanningCommunication Bus Systems ModbusCommunication Structure of the WL Circuit Breakers Ethernet WL Circuit Breaker Introduction and Overview Brief Description of the WL Circuit BreakerCubicleBUS Communications Capability of the Electronic Trip Units ETUsFunctional overview of the trip unit system ETU725 ETU727 ETU745Setting range of the Ig Basic Functions ETU725 ETU727 ETU745Basic Functions ETU748 ETU755 ETU776 Communication Metering Data Availability on the CubicleBUSData point group ETU745 Data points with the same source 755 orModbus COM16 Module and the BSS Pin ConfigurationModbus Module COM16 Modbus Write Protection DPWriteEnable Modbus Installation GuidelineMeaning Position and text on the cable CubicleBUS Data Exchange via the COM16 ModuleCubicleBUS + Cubicle BUS LED Meaning Rear Microswitch S46 Middle S47 Front S48Meaning PositionBreaker Status Sensor BSS Metering Function Plus GeneralHarmonic analysis Metering Function PlusWaveform buffer VT Accuracy Parameters for the settings of the metering functionVoltage Transformers Maximum distance from voltage transformerMetering range 81THDC Load Management Important functions/parameters for communicationsExtended Protective Function Minimum for Communicated Currents Normal Positive Power Flow DirectionSetpoints Event and Trip LogInstallation Rotary SwitchesExternal CubicleBUS Modules Maximum CubicleBUS Configuration Power SupplyCubicleBUS Installation Guidelines CubicleBUS LED Meaning LED DisplayMeaning All other LEDs MeaningTesting the Digital Input and Output Modules DeviceFunctional description Technical data for the digital input moduleDigital Input Module Functional description for changing parameter setsSelector switch position to the right Digital Output Module with Rotary SwitchSelector switch position to the left Delay timeConfigurable Digital Output Module Technical data for the digital configurable output module Trigger event Waveform buffer BPower value ranges W/VA Analog Output ModuleTechnical data for the analog output module Switch position cosTest function Operating principle ZSI ModuleExample as illustrated in Graphic Technical data for the ZSI module It trips after tZSI = 50 ms. Time saved = 250 msCommunication-capable Circuit Breakers General information Output current Inrush current Type Order No Communication-capable Circuit Breakers Modbus Profile for WL Circuit Breaker Supervisory Systems Function 01 Read Coils COM16 Supported Function CodesFunction 02 Read Discrete Inputs Request Message to slave Function 03 Read Holding RegistersReply Message from slave Function 05 Write Single Coil Function 04 Read Input RegistersFunction 07 Read Exception Status Function 11 Get Communication Event Counter Function 08 DiagnosticsFunction 12 Get Communication Event Log What the Event Bytes Contain COM16 slave Send EventFunction 15 Write Multiple Coils Function 16 Write Multiple Registers Exception Responses Exception Codes Code Name MeaningBasic Data Type 1 Registers and Default Data Points Default Register ListsBasic Data Type 2 Registers and Default Data Points Basic Data Type 3 Registers and Default Data Points Complete List of Datasets Data bytesSample Dataset Min Max BitsBit Mapping for Breaker Status Register Byte Register DescriptionWL Configurator Brief Description Communication-capable Circuit Breakers Breaker Data Adapter BDA Breaker Data Adapter Plus BDA Plus Description Brief Description and System RequirementsBenefits of the BDA BDA in Offline Mode or BDA Plus BDA as a Hand-Held Device or BDA PlusBDA Plus as an Ethernet Interface Intranet and InternetCircuit breaker requirements What is Java?Getting started with the BDA Plus Temporary Connection to WL Circuit BreakersPermanent Operation Meaning of the LEDs on the BDATechnical data for the BDA and BDA Plus 4This table provides technical data for the BDA and BDA PlusConnection to the BDA via the Serial Communication System Usually have to be changed. They are shown as a referenceBreaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Connection to the BDA Plus via the Ethernet Interface Definition of Key TermsExample IP AddressesSubnet Mask BDA IP AddressLanguages and Help Operating Instructions and TroubleshootingOffline/Online Mode Displaying DataOperation Example Password ProtectionSentron PrintingTroubleshooting List Fault Description Solution Siemens Energy & Automation, Inc Siemens Energy & Automation, Inc. All Rights Reserved

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.