Siemens UL 489, UL1066 specifications Exception Codes, Code Name Meaning

Page 57

Communication-capable Circuit Breakers

WL Circuit Breaker

Exception Codes

Code

Name

Meaning

01 hex

Illegal Function

The function code received in the query is not an allowable action for the COM16 slave. If a

 

 

Poll Program Complete command was issued, this code indicates that no program function

 

 

preceded it.

02 hex

Illegal Data Address

The data address received in the query is not an allowable address for the COM16 slave.

03 hex

Illegal Data Value

A value contained in the query data field is not an allowable value for the COM16 slave.

04 hex

Slave Device Failure

An unrecoverable error occurred while the COM16 slave was attempting to perform the

 

 

requested action.

05 hex

Acknowledge

The COM16 slave has accepted the request and is processing it, but a long duration of time

 

 

will be required to do so. This response is returned to prevent a timeout error from occurring

 

 

in the master. The master can next issue a Poll Program Complete message to determine if

 

 

processing is completed.

06 hex

Slave Device Busy

The COM16 slave is still busy processing the previous request. The master should re-transmit

 

 

the message later when the COM16 slave is free.

07 hex

Negative Acknowledge

This code is returned for an unsuccessful programming request using function code 13 or 14

 

 

decimal. The COM16 slave will never return this exception response since it does not support

 

 

function 13 or 14.

08 hex

Memory Parity Error

The COM16 slave attempted to read extended memory, but detected a parity error in the

 

 

memory. The master can retry the request, but service may be required on the COM16 slave

 

 

device.

Table 3-4

 

 

The following functions are not supported by the COM16. If a

COM16 slave receives a query for any of these functions, an

Exception Code of 01 (Illegal Function) will be the response.

Function 06: Write Single Register

Function 17: Report Slave ID

Function 20: Read General Reference

Function 21: Write General Reference

Function 22: Mask Write 4X Register

Function 23: Read/Write 4X Registers

Function 24: Read FIFO Queue

3/10

WL MODBUS Communication and Electronic Accessories • January 2005

Image 57
Contents Global network of innovation Powerful ideasCommunication-capable Circuit Breakers Communication-capable Circuit Breaker Qualified Personnel Safety GuidelinesCorrect Usage Registered TrademarksIntroduction Overview Content of the Manual GeneralIntroduction WL Circuit Breakers-Modular Intelligent System SolutionsCost Saving Easy PlanningModbus Communication Bus SystemsCommunication Structure of the WL Circuit Breakers Ethernet WL Circuit Breaker Brief Description of the WL Circuit Breaker Introduction and OverviewCommunications Capability of the Electronic Trip Units ETUs CubicleBUSETU725 ETU727 ETU745 Functional overview of the trip unit systemBasic Functions ETU725 ETU727 ETU745 Setting range of the IgBasic Functions ETU748 ETU755 ETU776 Communication Data point group ETU745 Data Availability on the CubicleBUSMetering Data points with the same source 755 orPin Configuration Modbus COM16 Module and the BSSModbus Module COM16 Modbus Installation Guideline Modbus Write Protection DPWriteEnableData Exchange via the COM16 Module Meaning Position and text on the cable CubicleBUSCubicleBUS + Meaning Rear Microswitch S46 Middle S47 Front S48Cubicle BUS LED Meaning PositionBreaker Status Sensor BSS General Metering Function PlusMetering Function Plus Harmonic analysisWaveform buffer Voltage Transformers Parameters for the settings of the metering functionVT Accuracy Maximum distance from voltage transformerMetering range 81THDC Important functions/parameters for communications Load ManagementExtended Protective Function Setpoints Normal Positive Power Flow DirectionMinimum for Communicated Currents Event and Trip LogRotary Switches InstallationExternal CubicleBUS Modules Power Supply Maximum CubicleBUS ConfigurationCubicleBUS Installation Guidelines Meaning LED DisplayCubicleBUS LED Meaning All other LEDs MeaningDevice Testing the Digital Input and Output ModulesDigital Input Module Technical data for the digital input moduleFunctional description Functional description for changing parameter setsSelector switch position to the left Digital Output Module with Rotary SwitchSelector switch position to the right Delay timeConfigurable Digital Output Module Trigger event Waveform buffer B Technical data for the digital configurable output moduleAnalog Output Module Power value ranges W/VASwitch position cos Technical data for the analog output moduleTest function ZSI Module Operating principleExample as illustrated in Graphic It trips after tZSI = 50 ms. Time saved = 250 ms Technical data for the ZSI moduleCommunication-capable Circuit Breakers General information Output current Inrush current Type Order No Communication-capable Circuit Breakers Modbus Profile for WL Circuit Breaker Supervisory Systems COM16 Supported Function Codes Function 01 Read CoilsFunction 02 Read Discrete Inputs Function 03 Read Holding Registers Request Message to slaveReply Message from slave Function 04 Read Input Registers Function 05 Write Single CoilFunction 07 Read Exception Status Function 08 Diagnostics Function 11 Get Communication Event CounterFunction 12 Get Communication Event Log COM16 slave Send Event What the Event Bytes ContainFunction 15 Write Multiple Coils Function 16 Write Multiple Registers Exception Responses Code Name Meaning Exception CodesDefault Register Lists Basic Data Type 1 Registers and Default Data PointsBasic Data Type 2 Registers and Default Data Points Basic Data Type 3 Registers and Default Data Points Data bytes Complete List of DatasetsMin Max Bits Sample DatasetByte Register Description Bit Mapping for Breaker Status RegisterWL Configurator Brief Description Communication-capable Circuit Breakers Breaker Data Adapter BDA Breaker Data Adapter Plus BDA Plus Brief Description and System Requirements DescriptionBenefits of the BDA BDA as a Hand-Held Device or BDA Plus BDA in Offline Mode or BDA PlusIntranet and Internet BDA Plus as an Ethernet InterfaceWhat is Java? Circuit breaker requirementsGetting started with the BDA Plus Connection to WL Circuit Breakers TemporaryPermanent Meaning of the LEDs on the BDA Operation4This table provides technical data for the BDA and BDA Plus Technical data for the BDA and BDA PlusUsually have to be changed. They are shown as a reference Connection to the BDA via the Serial Communication SystemBreaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Definition of Key Terms Connection to the BDA Plus via the Ethernet InterfaceSubnet Mask IP AddressesExample BDA IP AddressOffline/Online Mode Operating Instructions and TroubleshootingLanguages and Help Displaying DataSentron Password ProtectionOperation Example PrintingTroubleshooting List Fault Description Solution Siemens Energy & Automation, Inc. All Rights Reserved Siemens Energy & Automation, Inc

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.