Siemens UL1066 Switch position cos, Test function, Technical data for the analog output module

Page 40

Communication-capable Circuit Breakers

WL Circuit Breaker

A01: Network frequency

A02: Average value of the phase-to- phase voltages

A03: Total active power

A04: Average value of the power factors

The scale for displaying the frequency must range from 45Hz to 65Hz. This enables the standard frequencies in countries where IEC and UL standards apply to be displayed.

Example: 45Hz = 0 V/4mA and 65Hz = 10V/20mA.

The scalings of the other measured values can be read in the appropriate switch positions.

Switch position "cos "

The following measured values are output in switch position "cos ":

A01: Power factor cos L1

A02: Power factor cos L2

A03: Power factor cos L3

A04: Phase unbalance - current (%)

The power factors are displayed from

The test mode is started by pressing the "TEST" key and indicated by the yellow DEVICE LED. Although the measured values continue to be updated in the test mode, they are not output at their respective channels.

The test mode is started by pressing the "TEST" key.

Pressing the "TEST" key again selects output 1, which is indicated by LED A01. The test signal is output. For currents, voltages, and power rating values, this is equivalent to the full-scale value, with cos 1 and with a frequency of 55Hz.

Pressing the key again selects output 2, which is indicated by LED A02. This automatically deletes the value at output 1 and sets the value at output 2.

By repeating the above steps, the output and scaling of all four outputs can be checked one after the other.

Selecting output A04 and pressing the "TEST" key activates all four LEDs, but does not activate an output. Pressing the key again selects output 1 again.

If the "TEST" key is not pressed within 30 seconds after an output has been selected, the system exits the test mode automatically and returns to the standard operating mode. The values, which are constantly updated in the background, are then updated at the outputs again.

0.7(leading) (= 0V/4mA) through 1 (= 5V/12mA) to 0.7 (lagging) (= 10 V/20mA). The phase unbalance of the three currents is displayed from 0% (0V/4mA) to 50% (10V/20mA).

Note: Ensure that the polarity is correct during connection.

Test function

Technical data for the analog output module

Operating voltage min. / max.

19.2V / 28.8V

Operating current min. / max.

63mA / 150mA

Min. resistance connected to voltage output

20k Ω

Resistance range for connection to current output - min./max.

20 Ω / 250 Ω

Max. no. of analog output modules on one WL Circuit Breaker

2

Power loss min. / max.

0.74W / 5.4W

Dimensions W / H / D

70mm / 86mm / 95mm

Weight

0.223 kg

Temperature range

-20°C / 60°C

 

 

Table 2-21This table provides technical data for the analog output module on the CubicleBUS.

Figure

The analog channels are selected using the Rotary

2-16Switch.

2/29

WL MODBUS Communication and Electronic Accessories • January 2005

Image 40
Contents Powerful ideas Global network of innovationCommunication-capable Circuit Breakers Communication-capable Circuit Breaker Safety Guidelines Qualified PersonnelCorrect Usage Registered TrademarksIntroduction Overview General Content of the ManualIntroduction System Solutions WL Circuit Breakers-Modular IntelligentCost Saving Easy PlanningCommunication Bus Systems ModbusCommunication Structure of the WL Circuit Breakers Ethernet WL Circuit Breaker Introduction and Overview Brief Description of the WL Circuit BreakerCubicleBUS Communications Capability of the Electronic Trip Units ETUsFunctional overview of the trip unit system ETU725 ETU727 ETU745Setting range of the Ig Basic Functions ETU725 ETU727 ETU745Basic Functions ETU748 ETU755 ETU776 Communication Data Availability on the CubicleBUS Data point group ETU745Metering Data points with the same source 755 orModbus COM16 Module and the BSS Pin ConfigurationModbus Module COM16 Modbus Write Protection DPWriteEnable Modbus Installation GuidelineMeaning Position and text on the cable CubicleBUS Data Exchange via the COM16 ModuleCubicleBUS + Rear Microswitch S46 Middle S47 Front S48 MeaningCubicle BUS LED Meaning PositionBreaker Status Sensor BSS Metering Function Plus GeneralHarmonic analysis Metering Function PlusWaveform buffer Parameters for the settings of the metering function Voltage TransformersVT Accuracy Maximum distance from voltage transformerMetering range 81THDC Load Management Important functions/parameters for communicationsExtended Protective Function Normal Positive Power Flow Direction SetpointsMinimum for Communicated Currents Event and Trip LogInstallation Rotary SwitchesExternal CubicleBUS Modules Maximum CubicleBUS Configuration Power SupplyCubicleBUS Installation Guidelines LED Display MeaningCubicleBUS LED Meaning All other LEDs MeaningTesting the Digital Input and Output Modules DeviceTechnical data for the digital input module Digital Input ModuleFunctional description Functional description for changing parameter setsDigital Output Module with Rotary Switch Selector switch position to the leftSelector switch position to the right Delay timeConfigurable Digital Output Module Technical data for the digital configurable output module Trigger event Waveform buffer BPower value ranges W/VA Analog Output ModuleTechnical data for the analog output module Switch position cosTest function Operating principle ZSI ModuleExample as illustrated in Graphic Technical data for the ZSI module It trips after tZSI = 50 ms. Time saved = 250 msCommunication-capable Circuit Breakers General information Output current Inrush current Type Order No Communication-capable Circuit Breakers Modbus Profile for WL Circuit Breaker Supervisory Systems Function 01 Read Coils COM16 Supported Function CodesFunction 02 Read Discrete Inputs Request Message to slave Function 03 Read Holding RegistersReply Message from slave Function 05 Write Single Coil Function 04 Read Input RegistersFunction 07 Read Exception Status Function 11 Get Communication Event Counter Function 08 DiagnosticsFunction 12 Get Communication Event Log What the Event Bytes Contain COM16 slave Send EventFunction 15 Write Multiple Coils Function 16 Write Multiple Registers Exception Responses Exception Codes Code Name MeaningBasic Data Type 1 Registers and Default Data Points Default Register ListsBasic Data Type 2 Registers and Default Data Points Basic Data Type 3 Registers and Default Data Points Complete List of Datasets Data bytesSample Dataset Min Max BitsBit Mapping for Breaker Status Register Byte Register DescriptionWL Configurator Brief Description Communication-capable Circuit Breakers Breaker Data Adapter BDA Breaker Data Adapter Plus BDA Plus Description Brief Description and System RequirementsBenefits of the BDA BDA in Offline Mode or BDA Plus BDA as a Hand-Held Device or BDA PlusBDA Plus as an Ethernet Interface Intranet and InternetCircuit breaker requirements What is Java?Getting started with the BDA Plus Temporary Connection to WL Circuit BreakersPermanent Operation Meaning of the LEDs on the BDATechnical data for the BDA and BDA Plus 4This table provides technical data for the BDA and BDA PlusConnection to the BDA via the Serial Communication System Usually have to be changed. They are shown as a referenceBreaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Connection to the BDA Plus via the Ethernet Interface Definition of Key TermsIP Addresses Subnet MaskExample BDA IP AddressOperating Instructions and Troubleshooting Offline/Online ModeLanguages and Help Displaying DataPassword Protection SentronOperation Example PrintingTroubleshooting List Fault Description Solution Siemens Energy & Automation, Inc Siemens Energy & Automation, Inc. All Rights Reserved

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.