Siemens UL1066 Digital Output Module with Rotary Switch, Selector switch position to the left

Page 36

Communication-capable Circuit Breakers

WL Circuit Breaker

Digital Output Module with Rotary Switch

The digital output module can be used to output six events. These events can be warnings or trips and can be used for external annunciation or control. A circuit breaker trip can be wired to an Alarm Horn or Stack Light.

The load shedding and load restoring signals can enable a load to be switched ON or OFF automatically depending on the load.

The digital output module is available in two versions. The "optocoupler" version features solid state outputs. The current carrying capacity of this output is 150mA, and the nominal voltage is 24V DC. Only DC voltage can be switched. The "relay" version, uses a relay contact with a maximum load of 12A. Voltages of up 250V AC/DC are possible. The relay contacts are isolated.

The module is configured using a rotary switch, which not only selects one of the two output module versions, but also sets the appropriate delay time.

Selector switch position to the left

If the rotary switch is positioned to the left, outputs 1 through 6 are assigned the following events:

Output 1: Long-time trip (L)

Output 2: Short-time trip (S)

Output 3: Instantaneous trip (I)

Output 4: Ground fault trip (G)

Output 5: Ground fault alarm signal

Output 6: Trip as a result of overload in the neutral conductor

(N)

Selector switch position to the right

If the rotary switch is positioned to the right, the 6 outputs are automatically assigned the following functions:

Output 1: Leading overload trip signal (delay time 0s)

Output 2: Trip unit error (ETU)

Output 3: Load shedding

Output 4: Load restoring

Output 5: Temperature alarm

Output 6: Current phase unbalance

Delay time

The rotary switch can also be used to set an additional delay time. Available times are 0, 0.2 s, 0.5 s, 1 s, and 2 s.

These can be used, for example, to suppress events that only last a short time and not output them until they have been present for a long period (e.g. phase unbalance).

Irrespective of the delay time that has been set, the signal for the leading overload trip, which can be used to switch off and protect connected frequency converters, is always instantaneous.

A maximum of two digital output modules with rotary switches can be operated simultaneously on one WL Circuit Breaker, otherwise erroneous outputs may occur. They must be configured opposite each other. One in the operating mode with the switch position to the left and one with the switch position

to the right.

The LEDs display the current state of the 6 outputs. If the LED is OFF, the corresponding output is OFF. If the LED is yellow, the output is ON.

Technical data for the digital output module with a rotary selection switch

Operating voltage min. / max.

19.2V / 28.8V

 

 

Operating current min. / max. optocoupler

29mA / 63mA

 

 

Operating current min. / max. relay

29mA / 250mA

No. of isolated channels per digital output module

6

 

 

Max. current rating for optocoupler output with 24V DC

100mA

 

 

Max. current rating for relay output with 24V DC / 250 V AC / 250V DC

5A / 5A / 0.25A

 

 

Max. no. of digital output modules on one CubicleBUS

2

 

 

Power loss min. / max.

0.74W / 5.4W

 

 

Dimensions W / H / D

70mm / 86mm /95mm

 

 

Weight (optocoupler / relay)

0.223 kg / 0.321 kg

 

 

Temperature range

-20°C / 60°C

 

 

Table 2-16This table provides accurate technical data for the digital output module with rotary switch on the CubicleBUS.

2/25

 

 

Figure

Switch positioned to left / right

selects events in dark-gray /

2-14

light-gray fields.

 

 

 

WL MODBUS Communication and Electronic Accessories • January 2005

Image 36
Contents Powerful ideas Global network of innovationCommunication-capable Circuit Breakers Communication-capable Circuit Breaker Safety Guidelines Qualified PersonnelCorrect Usage Registered TrademarksIntroduction Overview Content of the Manual GeneralIntroduction System Solutions WL Circuit Breakers-Modular IntelligentCost Saving Easy PlanningCommunication Bus Systems ModbusCommunication Structure of the WL Circuit Breakers Ethernet WL Circuit Breaker Introduction and Overview Brief Description of the WL Circuit BreakerCubicleBUS Communications Capability of the Electronic Trip Units ETUsFunctional overview of the trip unit system ETU725 ETU727 ETU745Setting range of the Ig Basic Functions ETU725 ETU727 ETU745Basic Functions ETU748 ETU755 ETU776 Communication Data Availability on the CubicleBUS Data point group ETU745Metering Data points with the same source 755 orPin Configuration Modbus COM16 Module and the BSSModbus Module COM16 Modbus Write Protection DPWriteEnable Modbus Installation GuidelineData Exchange via the COM16 Module Meaning Position and text on the cable CubicleBUSCubicleBUS + Rear Microswitch S46 Middle S47 Front S48 MeaningCubicle BUS LED Meaning PositionBreaker Status Sensor BSS Metering Function Plus GeneralMetering Function Plus Harmonic analysisWaveform buffer Parameters for the settings of the metering function Voltage TransformersVT Accuracy Maximum distance from voltage transformerMetering range 81THDC Important functions/parameters for communications Load ManagementExtended Protective Function Normal Positive Power Flow Direction SetpointsMinimum for Communicated Currents Event and Trip LogRotary Switches InstallationExternal CubicleBUS Modules Power Supply Maximum CubicleBUS ConfigurationCubicleBUS Installation Guidelines LED Display MeaningCubicleBUS LED Meaning All other LEDs MeaningTesting the Digital Input and Output Modules DeviceTechnical data for the digital input module Digital Input ModuleFunctional description Functional description for changing parameter setsDigital Output Module with Rotary Switch Selector switch position to the leftSelector switch position to the right Delay timeConfigurable Digital Output Module Technical data for the digital configurable output module Trigger event Waveform buffer BPower value ranges W/VA Analog Output ModuleSwitch position cos Technical data for the analog output moduleTest function ZSI Module Operating principleExample as illustrated in Graphic Technical data for the ZSI module It trips after tZSI = 50 ms. Time saved = 250 msCommunication-capable Circuit Breakers General information Output current Inrush current Type Order No Communication-capable Circuit Breakers Modbus Profile for WL Circuit Breaker Supervisory Systems COM16 Supported Function Codes Function 01 Read CoilsFunction 02 Read Discrete Inputs Function 03 Read Holding Registers Request Message to slaveReply Message from slave Function 04 Read Input Registers Function 05 Write Single CoilFunction 07 Read Exception Status Function 08 Diagnostics Function 11 Get Communication Event CounterFunction 12 Get Communication Event Log What the Event Bytes Contain COM16 slave Send EventFunction 15 Write Multiple Coils Function 16 Write Multiple Registers Exception Responses Exception Codes Code Name MeaningDefault Register Lists Basic Data Type 1 Registers and Default Data PointsBasic Data Type 2 Registers and Default Data Points Basic Data Type 3 Registers and Default Data Points Complete List of Datasets Data bytesSample Dataset Min Max BitsBit Mapping for Breaker Status Register Byte Register DescriptionWL Configurator Brief Description Communication-capable Circuit Breakers Breaker Data Adapter BDA Breaker Data Adapter Plus BDA Plus Brief Description and System Requirements DescriptionBenefits of the BDA BDA in Offline Mode or BDA Plus BDA as a Hand-Held Device or BDA PlusBDA Plus as an Ethernet Interface Intranet and InternetWhat is Java? Circuit breaker requirementsGetting started with the BDA Plus Connection to WL Circuit Breakers TemporaryPermanent Operation Meaning of the LEDs on the BDATechnical data for the BDA and BDA Plus 4This table provides technical data for the BDA and BDA PlusConnection to the BDA via the Serial Communication System Usually have to be changed. They are shown as a referenceBreaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Connection to the BDA Plus via the Ethernet Interface Definition of Key TermsIP Addresses Subnet MaskExample BDA IP AddressOperating Instructions and Troubleshooting Offline/Online ModeLanguages and Help Displaying DataPassword Protection SentronOperation Example PrintingTroubleshooting List Fault Description Solution Siemens Energy & Automation, Inc Siemens Energy & Automation, Inc. All Rights Reserved

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.