Siemens UL 489, UL1066 specifications Analog Output Module, Power value ranges W/VA

Page 39

Communication-capable Circuit Breakers

WL Circuit Breaker

Analog Output Module

The analog output module can be used to output the most important measured values sent via the CubicleBUS to analog indicators (e.g. analog meters) in the switchgear cubicle door. Each analog output module has four channels for this purpose. The signals are available at two physical interfaces: a 4 ... 20mA and a 0 ... 10V interface.

The measured values are available as 0 ... 10V via the X4 connector on the CubicleBUS module (the 4 ...

20mA interface is available at X5). Both outputs are always active at the same time, and can be used simultaneously.

The measured values, which are output via the four channels, are selected using a rotary switch. The available outputs are current, voltage, power, frequency and power factor. Up to two analog output modules can be operated on one CubicleBUS. The selection panel on the rotary switch is divided vertically. If the switch is set to a value on the left, the module is automatically addressed as module 1.

If a second module exists, it must be set to a value on the right. This is the only way that two analog output modules can operate simultaneously.

All types of analog instruments with an internal resistance of more than 20kΩ (for the voltage output) and between 50Ω and 250Ω (as a current output) can be used as

an indicator.

The LEDs for the channels are yellow if the current value exceeds the full-scale deflection by 20% (with V, I and P), power factor is greater than 0.8, or the frequency greater than 45Hz.

Switch position "I"

In switch position "I", the measured current values are output linearly:

A01: Current in phase A

A02: Current in phase B

A03: Current in phase C

A04: Current in the neutral conductor

designed for different rated currents, the full-scale value must be scaled automatically and the maximum output value of the analog output module interpreted. The value of the rating plug is used for this purpose.

The maximum value is calculated by multiplying the value of the rating plug by 1.2 and then rounding the result up to the nearest 100.

Example: With a rating plug of 1600A, the full-scale value of the analog panel meter must be 2000A (1600 x 1.2 = 1920 -> 2000A). In other words, 0V/4mA = 0A, 10V/20mA = 2000A.

Switch position "U"

When the rotary switch is in switch position "U", the following voltages are applied to the four analog outputs:

A01: Phase-to-phase voltage Vab

A02: Phase-to-phase voltage Vbc

A03: Phase-to-phase voltage Vca

A04: Phase voltage VN

In most cases, the phase-to-phase voltage is output to the switchgear cubicle doors. This is why the first three channels are assigned these measured values. If the voltage is required between a phase and the neutral conductor, this is available via output A04.

The full-scale deflection for the analog panel meter is calculated by multiplying the rated voltage of the network (primary voltage of the voltage transformer) by 1.1 and then rounding the result up to the nearest 50.

Example: If the rated voltage of the network is 480V, the full-scale value is 550V (480V x 1.1 = 528V -> 550V).

Switch position "P"

If the rotary switch is set to position "P", the power measured values are output via the four channels:

A01: Active power phase kWa

A02: Active power phase kWb

A03: Active power phase kWc

A04: Total apparent power kVATOT

The full-scale deflection of the active power in each phase is calculated by multiplying the value of the rating plug by the rated voltage of the network. The full- scale deflection value is then classified in a value range, as shown in the table below.

Before the full-scale deflection can be determined from the table, the calculated value must be multiplied by 3 for the total apparent power and the total active power (position f).

Example: IR = 1600A, rated voltage = 480V; -> full-scale deflection = 1,000,000 W

Switch position "f"

Since it can generally be assumed that the frequency will be the same across the three phases in all the networks, switch position "f" is used to provide a general overview by outputting the most important measured values (with the exception of the current values). In conjunction with another module in position "I", all the most important measured values can be displayed in this way.

Power value ranges [W/VA]

From

To

Full Scale Deflection

0

50,000

50,000

50,000

100,000

100,000

 

 

 

100,000

200,000

200,000

200,000

300,000

300,000

300,000

500,000

500,000

500,000

1,000,000

1,000,000

1,000,000

2,000,000

2,000,000

2,000,000

3,000,000

3,000,000

3,000,000

5,000,000

5,000,000

 

 

 

5,000,000

10,000,000

10,000,000

 

 

 

10,000,000

20,000,000

20,000,000

 

 

 

20,000,000

30,000,000

 

 

 

Table 2-20After multiplication, the full-scale deflection of the power is sorted into ranges.

Since the circuit breaker can be

2/28

WL MODBUS Communication and Electronic Accessories • January 2005

Image 39
Contents Global network of innovation Powerful ideasCommunication-capable Circuit Breakers Communication-capable Circuit Breaker Registered Trademarks Safety GuidelinesQualified Personnel Correct UsageIntroduction Overview Content of the Manual GeneralIntroduction Easy Planning System SolutionsWL Circuit Breakers-Modular Intelligent Cost SavingModbus Communication Bus SystemsCommunication Structure of the WL Circuit Breakers Ethernet WL Circuit Breaker Brief Description of the WL Circuit Breaker Introduction and OverviewCommunications Capability of the Electronic Trip Units ETUs CubicleBUSETU725 ETU727 ETU745 Functional overview of the trip unit systemBasic Functions ETU725 ETU727 ETU745 Setting range of the IgBasic Functions ETU748 ETU755 ETU776 Communication Data points with the same source 755 or Data Availability on the CubicleBUSData point group ETU745 MeteringPin Configuration Modbus COM16 Module and the BSSModbus Module COM16 Modbus Installation Guideline Modbus Write Protection DPWriteEnableData Exchange via the COM16 Module Meaning Position and text on the cable CubicleBUSCubicleBUS + Position Rear Microswitch S46 Middle S47 Front S48Meaning Cubicle BUS LED MeaningBreaker Status Sensor BSS General Metering Function PlusMetering Function Plus Harmonic analysisWaveform buffer Maximum distance from voltage transformer Parameters for the settings of the metering functionVoltage Transformers VT AccuracyMetering range 81THDC Important functions/parameters for communications Load ManagementExtended Protective Function Event and Trip Log Normal Positive Power Flow DirectionSetpoints Minimum for Communicated CurrentsRotary Switches InstallationExternal CubicleBUS Modules Power Supply Maximum CubicleBUS ConfigurationCubicleBUS Installation Guidelines All other LEDs Meaning LED DisplayMeaning CubicleBUS LED MeaningDevice Testing the Digital Input and Output ModulesFunctional description for changing parameter sets Technical data for the digital input moduleDigital Input Module Functional descriptionDelay time Digital Output Module with Rotary SwitchSelector switch position to the left Selector switch position to the rightConfigurable Digital Output Module Trigger event Waveform buffer B Technical data for the digital configurable output moduleAnalog Output Module Power value ranges W/VASwitch position cos Technical data for the analog output moduleTest function ZSI Module Operating principleExample as illustrated in Graphic It trips after tZSI = 50 ms. Time saved = 250 ms Technical data for the ZSI moduleCommunication-capable Circuit Breakers General information Output current Inrush current Type Order No Communication-capable Circuit Breakers Modbus Profile for WL Circuit Breaker Supervisory Systems COM16 Supported Function Codes Function 01 Read CoilsFunction 02 Read Discrete Inputs Function 03 Read Holding Registers Request Message to slaveReply Message from slave Function 04 Read Input Registers Function 05 Write Single CoilFunction 07 Read Exception Status Function 08 Diagnostics Function 11 Get Communication Event CounterFunction 12 Get Communication Event Log COM16 slave Send Event What the Event Bytes ContainFunction 15 Write Multiple Coils Function 16 Write Multiple Registers Exception Responses Code Name Meaning Exception CodesDefault Register Lists Basic Data Type 1 Registers and Default Data PointsBasic Data Type 2 Registers and Default Data Points Basic Data Type 3 Registers and Default Data Points Data bytes Complete List of DatasetsMin Max Bits Sample DatasetByte Register Description Bit Mapping for Breaker Status RegisterWL Configurator Brief Description Communication-capable Circuit Breakers Breaker Data Adapter BDA Breaker Data Adapter Plus BDA Plus Brief Description and System Requirements DescriptionBenefits of the BDA BDA as a Hand-Held Device or BDA Plus BDA in Offline Mode or BDA PlusIntranet and Internet BDA Plus as an Ethernet InterfaceWhat is Java? Circuit breaker requirementsGetting started with the BDA Plus Connection to WL Circuit Breakers TemporaryPermanent Meaning of the LEDs on the BDA Operation4This table provides technical data for the BDA and BDA Plus Technical data for the BDA and BDA PlusUsually have to be changed. They are shown as a reference Connection to the BDA via the Serial Communication SystemBreaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Breaker Data Adapter BDA Definition of Key Terms Connection to the BDA Plus via the Ethernet InterfaceBDA IP Address IP AddressesSubnet Mask ExampleDisplaying Data Operating Instructions and TroubleshootingOffline/Online Mode Languages and HelpPrinting Password ProtectionSentron Operation ExampleTroubleshooting List Fault Description Solution Siemens Energy & Automation, Inc. All Rights Reserved Siemens Energy & Automation, Inc

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.